Performance Data Curves

12
Figure 3. High Temperature Rise Duct Furnace — 30–90°F (17–50°C)
Pressure drop through the heat exchanger is based on the CFM throughput. The desired data
is obtained in the following manner:
Select heater size based on heat loss of the building to be heated.
Select temperature rise desired.
Based on temperature rise, the horizontal line intersects heater temperature vs. CFM
curve.
Follow vertical line down to select CFM.
For pressure drop selection, follow vertical CFM line until it intersects the selected heater
performance curve vs. pressure drop.
Follow the horizontal pressure drop line to the left, and read pressure drop of the selected
heater.
MUA-SVX004B-EN