Figure 13. Example of Piping Layout for Determining Size
GAS METER
Table 3. Gas Pipe Size
Nominal
Pipe Size
1 1/4
1 1/2
2 1/2
MUA-SVX004B-EN
250 cfh is supplied from B to D, requiring 1 inch pipe.
100 cfh is supplied from D to E, requiring 3/4 inch pipe.
150 cfh is supplied from D to F, requiring 1 inch pipe.
For SI calculations, refer to metric conversion chart in general safety section of this
manual.
If more than one gas duct furnace is to be served by the same piping arrangement, the
total cu. ft./hr. input and length of pipe must be considered.
If the gas duct furnace is to be fired with LP gas, consult local LP gas dealer for pipe
size information. Heater installation for use with propane (bottled) gas must be made
by a qualified LP gas dealer or installer. He will insure proper joint compounds are
used for making pipe connections; that air is purged from lines; that a thorough test is
made for leaks before operating heater; and that it is properly connected to propane
gas supply system.
Before any connection is made to an existing line supplying other gas appliances, contact the
local gas company to make certain that the existing line is of adequate size to handle the
combined load.
Check all connections with a soap solution before leaving job.
20 ft.
6.56 m.
20 ft.
6.56 m.
A
Maximum Capacity of Pipe in Cubic Feet of Gas per Hour for Gas Pressures of 0.5 psig (3.5 kPa) or Less,
Iron
Internal
Dia.
in.
in.
10
20
30
(mm)
(3.0)
(6.1)
(9.1)
1
2 /
0.622
175
120
97
(16)
(4.96)
(3.40)
(2.75)
3
4 /
0.824
360
250
200
(21)
(10.2)
(7.08)
(5.66)
1
1.049
680
465
375
(27)
(19.3)
(13.2)
(10.6)
1.380
1400
950
770
(35)
(39.6)
(26.9)
(21.8)
1.610
2100
1460
1180
(41)
(59.5)
(41.3)
(33.4)
2
2.067
3950
2750
2200
(53)
(112)
(77.9)
(62.3)
2.469
6300
4350
3520
(63)
(178)
(123)
(99.7)
3
3.068
11000
7700
6250
(78)
(311)
(218)
(177)
4
4.026
23000
15800
12800
(102)
(651)
(447)
(362)
HEATER(S)
200 CFH
C
5 ft.
1.64 m.
10 ft.
3.48 m.
D
B
5 ft.
1.64 m.
F
HEATER(S)
150 CFH
and a Pressure Drop of 0.5 Inch Water Column (124.4 Pa)
(Based on a 0.60 Specifi c Gravity Gas)
Length of Pipe, ft. (Meters)
40
50
60
70
(12.2)
(15.2) (18.3)
(21.3)
82
73
66
61
(2.32)
(2.07) (1.87)
(1.73)
170
151
138
125
(4.81)
(4.28) (3.91)
(3.54)
320
285
260
240
(9.06)
(8.07) (7.36)
(6.80)
660
580
530
490
(18.7)
(16.4) (15.0)
(13.9)
990
900
810
750
(28.0)
(25.5) (22.9)
(21.2)
1900
1680
1520
1400
(53.8)
(47.6) (43.0)
(39.6)
3000
2650
2400
2250
(85.0)
(75.0) (68.0)
(63.7)
5300
4750
4300
3900
(150)
(135)
(122)
(110)
10900
9700
8800
8100
(309)
(275)
(249)
(229)
G G a a s s C C o o n n n n e e c c t t i i o o n n s s
10 ft.
E
3.28 m.
HEATER(S)
100 CFH
80
90
100
125
(24.4)
(27.4)
(30.5)
(38.1)
57
53
50
44
(1.61)
(1.50)
(1.42)
(1.25)
118
110
103
93
(3.34)
(3.11)
(2.92)
(2.63)
220
205
195
175
(6.23)
(5.80)
(5.52)
(4.96)
460
430
400
360
(13.0)
(12.2)
(11.3)
(10.2)
690
650
620
550
(19.5)
(18.4)
(17.6)
(15.6)
1300
1220
1150
1020
(36.8)
(34.5)
(32.6)
(28.9)
2050
1950
1850
1650
1500
(58.0)
(55.2)
(52.4)
(46.7)
3700
3450
3250
2950
2650
(105)
(97.7)
(92.0)
(83.5)
(75.0)
7500
7200
6700
6000
5500
(212)
(204)
(190)
(170)
(156)
150
175
200
(45.7)
(53.3)
(61.0)
40
37
35
(1.13)
(1.05)
(0.99)
84
77
72
(2.38)
(2.18)
(2.04)
160
145
135
(4.53)
(4.11)
(3.82)
325
300
280
(9.20)
(8.50)
(7.93)
500
460
430
(14.2)
(13.0)
(12.2)
950
850
800
(26.9)
(24.1)
(22.7)
1370
1280
(42.5)
(38.8)
(36.2)
2450
2280
(69.4)
(64.6)
5000
4600
(142)
(130)
23

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

GrbaGrcaGrdaGfaaGfbaGfca ... Show all

Table of Contents