420010263000 BLU 500.1 ÷ 1200.1 PAB
EN
To calculate the burner's working output, in kW, proceed as follows:
- Check at the meter the quantity of supplied litres and the duration,
in seconds, of the reading, then calculate the burner's output through
the following formula:
WARNING: In order to have a correct combustion and thermal output adjustments, these must be carried out together
with a combustion analysis, to be executed through suitable devices, taking care that the values are the correct ones and
are in accordance with the local safety regulations. The adjustments must be carried out by qualified and skilled techni-
cians authorised by Ecoflam S.p.A.
The adjustment of the position of the firing head is made to obtain
the best combustion performance. When used at the minimum
power output the firing head is move back, whilst is forwarded at
the maximum output. Execution : -loosen the locking screw of
adjusting device A; - move the adjusting device until the desired
position is reached; - tighten the locking screw.
REMOVING THE NOSEPIECE
SEZIONE B-
CALCULATION OF WORKING OUTPUT OF THE BURNER

COMBUSTION ADJUSTMENT

SETTING THE FIRING HEAD
POSITION OF ELECTRODES
B
Ignition electrode
B
A
B
A
14
e =
Litres of gas
s =
Time in seconds
G20 = 34,02
G25 = 29,25
e x f = kW
f
G30 = 116
s
G31 = 88
Ionization probe
SE
ZION
A
A A
-
E