Carrier 48TJD008-014 Installation, Start-Up And Service Instructions Manual page 7

Single-package rooftop heating/cooling units
Hide thumbs Also See for 48TJD008-014:
Table of Contents

Advertisement

STANDARD
CORNER
CORNER
UNIT
WEIGHT
WEIGHT
UNIT
WEIGHT
(A)
48TJ
Lb
Kg
Lb
Kg
Lb
D/E/F008
870
395
189
86
161
D/E/F009
880
399
191
87
163
D/E/F012 1035
469
225 102
192
D/E014
1050
476
228 103
195
CORNER
CORNER
WEIGHT
WEIGHT
''H''
(B)
(C)
(D)
Kg
Lb
Kg
Lb
Kg
ft-in.
mm
73
239 109 280 127 1-2
7
8
74
242 110 284 129 3-3
7
1013 3-5
8
87
285 129 333 151 2-5
7
8
88
289 131 338 153 1-2
7
8
Fig. 7 — Base Unit Dimensions
''J''
''K''
''L''
ft-in.
mm
ft-in.
mm
ft-in.
378 3-5
5
1050 2-9
11
856 2- 2
7
16
16
5
1050 2-9
11
856 2- 2
7
16
16
759 4-1
5
1253 3-0
3
924 2-10
7
16
8
378 4-1
5
1253 3-0
3
924 2-10
7
16
8
NOTES:
1. Dimensions in [ ] are in millimeters.
2.
Center of gravity.
3.
Direction of airflow.
4. On vertical discharge units, ductwork to be attached to accessory roof curb only. For
horizontal discharge units field-supplied flanges should be attached to horizontal dis-
charge openings, and all ductwork should be attached to the flanges.
5. Minimum clearance (local codes or jurisdiction may prevail):
a. Between unit (flue side) and combustible surfaces, 48 inches.
b. Bottom of unit to combustible surfaces (when not using curb) 1 inch.
Bottom of base rail to combustible surfaces (when not using curb) 0 inches.
c. Condenser coil, for proper airflow, 36 in. one side, 12 in. the other. The side get-
ting the greater clearance is optional.
d. Overhead, 60 in. to assure proper condenser fan operation.
e. Between units, control box side, 42 in. per NEC (National Electrical Code).
f. Between unit and ungrounded surfaces, control box side, 36 in. per NEC.
g. Between unit and block or concrete walls and other grounded surfaces, control
box side, 42 in. per NEC.
h. Horizontal supply and return end, 0 inches.
6. With the exception of the clearance for the condenser coil and combustion side as
stated in Notes 5a, b, and c, a removable fence or barricade requires no clearance.
7. Units may be installed on combustible floors made from wood or Class A, B, or C
roof covering material if set on base rail.
8. The vertical center of gravity is 1 -7 [483] up from the bottom of the base rail. Hori-
zontal center of gravity is shown.
7
CONNECTION SIZES
A 1
3
Dia [35] Field Power Supply Hole
8
B 2-
1
Dia [64] Power Supply Knock-Out
2
mm
C 1
3
Dia [44] Charging Port Hole
4
672
16
D
7
Dia [22] Field Control Wiring Hole
8
672
16
E
3
—14 NPT Condensate Drain
4
875
16
—14 NPT Gas Connection 48TJD008 & 009
1
2
875
16
F
—14 NPT Gas Connection 48TJE/F008 & 009;
3
4
48TJD/E012,014, 48TJF012
G 2 Dia [51] Power Supply Knock-Out
BOTTOM POWER CHART, THESE HOLES
REQUIRED FOR USE WITH ACCESSORY
PACKAGES — CRBTMPWR001A00,
OR CRBTMPWR002A00
THREADED
WIRE SIZE
CONDUIT SIZE
1
24 V
2
3
Power*
4
1
1
Power*
4
*Select either
3
or 1
1
for power, depending on wire size.
4
4
REQUIRED HOLE
SIZES (MAX)
7
[22.2]
8
1
1
[28.4]
8
1
3
[44.4]
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents