PROBLEM
Burners will not
Misaligned spark electrodes.
ignite.
No gas at main burners.
Water in gas line.
No power to furnace.
No 24 v power supply to control circuit.
Miswired or loose connections
Burned-out heat anticipator in thermostat.
Broken thermostat wires.
Inadequate heating.
Dirty air filter.
Gas input to unit too low.
Unit undersized for application.
Restricted airflow.
Blower speed too low.
Limit switch cycles main burners.
Too much outdoor air.
Poor flame
Incomplete combustion (lack of combustion air)
characteristics.
results in:
Aldehyde odors, CO, sooting flame, or floating flame.
Burners will not
Unit is locked into Heating mode for a one minute
turn off.
minimum.
AHA
— Adjustable Heat Anticipator
BR
— Burner Relay
C
— Contactor, Compressor
CAP
— Capacitor
CB
— Circuit Breaker
CC
— Cooling Compensator
COMP — Compressor Motor
CR
— Control Relay
D
— Diode
EC
— Enthalpy Control
EPS
— Economizer Pressure Switch
EQUIP — Equipment
FPT
— Freeze-Protection
Thermostat
GND
— Ground
GVR
— Gas Valve Relay
HPS
— High-Pressure Switch
HS
— Hall Effect Sensor
I
— Ignitor
IDM
— Induced-Draft Motor
IFC
— Indoor (Evaporator) Fan
Contactor
NOTES:
1. If any of the original wire furnished must be replaced, it must be
replaced with type 90 C wire or its equivalent.
2. Three-phase motors are protected under primary single phasing
conditions.
3. Thermostat: HH07AT170, 172, 174 and P272-2783
Subbase: HH93AZ176, 178 and P272-1882, 1883
4. Set heat anticipator for first stage at 0.14 amp, second stage at
0.2 amp.
Table 21 — Heating Service Troubleshooting
CAUSE
LEGEND AND NOTES FOR FIG. 48
IMPORTANT: Refer to unit wiring label for actual unit
wiring information.
IFM
— Indoor (Evaporator) Fan Motor
IGC
— Integrated Gas Unit
Controller
LED
— Light Emitting Diode
LPS
— Low-Pressure/Loss-of-Charge
Switch
LS
— Limit Switch
MGV
— Main Gas Valve
MTR
— Motor
OAT
— Outdoor Air Thermostat
OFM
— Outdoor-Fan Motor
PL
— Plug Assembly
QT
— Quadruple Terminal
R
— Relay
RS
— Rollout Switch
SAT
— Supply Air Thermostat
SEN
— Sensor
TC
— Thermostat-Cooling
TH
— Thermostat-Heating
TRAN — Transformer
Check flame ignition and sensor electrode positioning.
Adjust as needed.
Check gas line for air purge as necessary. After purging
gas line of air, allow gas to dissipate for at least 5 min-
utes before attempting to relight unit.
Check gas valve.
Drain water and install drip leg to trap water.
Check power supply, fuses, wiring, and circuit breaker.
Check transformer. Transformers with internal overcur-
rent protection require a cool down period before
resetting.
Check all wiring and wirenut connections.
Replace thermostat.
Run continuity check. Replace wires, if necessary.
Clean or replace filter as necessary.
Check gas pressure at manifold. Clock gas meter for
input. If too low, increase manifold pressure, or replace
with correct orifices.
Replace with proper unit or add additional unit.
Clean filter, replace filter, or remove any restrictions.
Use high speed tap, increase fan speed, or install op-
tional blower, as suitable for individual units.
Check rotation of blower, thermostat heat anticipator set-
tings, and temperature rise of unit. Adjust as needed.
Adjust minimum position.
Check economizer operation.
Check all screws around flue outlets and burner com-
partment. Tighten as necessary.
Cracked heat exchanger.
Overfired unit — reduce input, change orifices, or adjust
gas line or manifold pressure.
Check vent for restriction. Clean as necessary.
Check orifice to burner alignment.
Wait until mandatory one minute time period has
elapsed or power to unit.
5. Use copper conductors only.
6. TRAN is wired for 230 v unit. If unit is to be run with 208 v power
supply, disconnect BLK wire from 230 v tap (RED) and connect to
200 v tap (BLU). Insulate end of 230 v tap.
7. When economizer assembly is installed move GRA wire from con-
nection board (Y1) to GRA wire from PL6,5; move ORN wire from
connection board (Y2) to ORN wire from PL6,9, on economizer
assembly.
35
REMEDY
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To indicate common potential
only, not to represent wiring