Page 2
On Manual Reset Units, if the control is in low water On Manual Reset Units, if the control is in low water condition (water is off the probe) and there is a sudden condition (water is off the probe) and there is a sudden power interruption, the control will remain in low water power interruption, the control will remain in low water condition (Burner Off) even if the power is restored.
Page 6
Terminal connection "PROBE" on PCB. Terminal connection "PROBE" on PCB. Terminal connection "GND" on PCB. Terminal connection "GND" on PCB. Connect a wire from Terminal 5 to the next safety Connect a wire from Terminal 5 to the next safety device of the Burner's safety circuit, such as device of the Burner's safety circuit, such as thermostat, gas valve, limits, etc.
Page 7
STEP 5 - Testing and Diagnostic Procedures Series 750 LWCO with Green Power On LED and Red Low Water LED Start-Up a. Before filling the system, turn on the electric power to the boiler. Auto reset units: simultaneously 4 times. 1.