FCP-PA-701-NF
Table 6: System configuration settings
Menu item
Description
21
System type
22
2-pipe FCU with aux heat available
(available only if system type = 2FCU)
23
Available modes
25
Remote sensor location
26
Remote sensor type
27
Pipe sensor type
28
Pipe state – calendar
29
Heat to cool day
(unavailable if pipe state – calendar = OFF)
30
Cool to heat day
(unavailable if pipe state – calendar = OFF)
31
Pipe state
(unavailable if system type ≠ 2FCU or if pipe
sensor = true or if pipe state – calendar = ON)
32
Heat to cool threshold
(unavailable if system type ≠ 2FCU or if pipe
sensor = false)
33
Cool to heat threshold
(unavailable if system type ≠ 2FC or if pipe sensor
= false)
34
Purge frequency
(unavailable if system type ≠ 2FC or if pipe sensor
= false)
Setting options
2FCU: 2-pipe fan coil unit without fan
4FCU: 4-pipe fan coil unit without fan
H-C: conventional without fan
Yes
No
2FCU without aux heat:
04: Heat and cool without auto
2FCU with aux heat:
03: Heat and cool with auto
04: Heat and cool without auto
4FCU or H-C:
01: Heat only
02: Cool only
03: Heat and cool with auto
04 : Heat and cool without auto
0: in room
1: in duct
0: type II
1: type III
0: type II
1: type III
ON
OFF
1-Mar to 31-May
1-Sep to 30-Nov
0: Heat
1: Cool
50°F - 72°F (10°C - 22°C)
55°F - 90°F (13°C - 32°C)
0: Never
1: 2 hours
2: 24 hours
7
Default
4FCU
No
2FCU without aux: 04
2FCU with aux: 03
4FCU, HP, or H-C: 03
0
0
0
OFF
15-Apr
15-Oct
0
60°F (16°C)
80°F (27°C)
0
LIT-12013797