FCP-PA-701-NF
Table 2: Preset configuration profiles (part 2 of 2)
Profile #
Remote
Pipe
sensor
sensor
16
Yes
No
17
No
No
18
No
No
19
Yes
No
20
No
No
Button combinations
The following table describes the button combinations that you can use to access menus or functions. The table also indicates the
modes in which these button combinations are applicable.
Table 3: Button combinations
Menu or function
Advance Settings menu
Access Programming menu
Pipe State (Heat/Cool) Selection
Ex-Factory Reset
Toggle Keypad lock/unlock
Enable/Disable unoccupied mode manually HEAT and COOL mode
Control mode
FCP has four control modes: OFF, HEAT, COOL, AUTO. The available control modes depend on the selected system type and available
mode in the advanced menu setting, see Table 6.
Table 4: FCP available modes
System type
2-pipe
FCU with
aux heat
2-pipe FCU
No
2-pipe FCU
No
2-pipe FCU
Yes
2-pipe FCU
Yes
2-pipe FCU
No
2-pipe FCU
No
2-pipe FCU
Yes
2-pipe FCU
Yes
4-pipe FCU
n/a
PTAC conventional
n/a
Press Mode to access the control mode menu. Press Mode again to select the required control mode, OFF, HEAT, COOL, or AUTO. Do
not press any button for 2 seconds to confirm a change.
Note: AUTO mode is only available when both heating and cooling are available.
System
2-pipe
Available modes:
type
FCU with
1: heat only
aux heat
2: cool only
3: heat and cool with Auto
4: heat and cool without Auto
4-pipe FCU
-
4
4-pipe FCU
-
3
H-C
-
1
H-C
-
1
H-C
-
3
Applicable in mode
OFF mode
OFF mode, when programming
is enabled in Advanced Settings
OFF mode and system type =
2-pipe FCU
OFF mode
HEAT and COOL mode
Fan
Pipe
control
sensor
installed
No
No
No
No
No
Yes
Yes
Yes
Yes
n/a
n/a
Button combination
Mode + Back for 5 seconds
Mode + Up for 5 seconds
Back + Up for 5 seconds
Mode + Back + Up for 5 seconds
Mode + Up + Down for 10 seconds
Mode for 5 seconds
Control modes when thermostat operates
Pipe sensor state
Heat only Cool only Off
Heat, manual
Yes
selection
Cool, manual
No
selection
Heat, manual
Yes
selection
Cool, manual
Yes
selection
Heat, auto selection
Yes
Cool, auto selection
No
Heat, auto selection
Yes
Cool, auto selection
Yes
n/a
Yes
n/a
Yes
5
Pipe state
Pipe state:
Purge
- calendar
frequency:
0: heat
0: Never
1: cool
1: 2 hours
2: 24 hours
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
No
Yes
No
Yes
Yes
No
Yes
No
Yes
Yes
Yes
LIT-12013797
Auto
No
No
No
Yes
No
No
No
Yes
Yes
Yes