Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A York International Corporation, 5005 6150258-UIM-A-1021 York Drive, Norman, OK 73069 A-1021 www.johnsoncontrols.com 2021-05-26 Johnson Controls Ducted Systems...
Page 2
Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Post start checklist..........75 RPM selection............ 55 Gas heat start-up............76 Indoor blower specifications......56 Pre-start checklist............76 Smart Equipment™ unit control board...59 Operating instructions........... 76 Operation............... 64 Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 4
Start up for units equipped for fan energy rating..81 Direct drive..............81 Troubleshooting..............82 Charging tables..............87 Smart Equipment™ Control board navigation components................89 Start-Up sheet................ 90 Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Refer to this manual for assistance or for additional information, consult a qualified contractor, installer or service agency. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 6
Fuel Gas Code, ANSI Z223.1/NFPA 54, and/or the installed National Gas and Propane Installation Code, CSA B149.1. Horizontal flow dry bulb economizer field installed Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 7
CAUTION This system uses R-410A Refrigerant which operates at higher pressures than R-22. No other refrigerant may be used in this system. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
A fire or explosion may result causing property damage, personal Attach the cover to the unit with the four screws provided. injury or loss of life. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 10
See Figure 3 for the factory SAT sensor location and Figure 5 for the sensor relocation. Figure 3: Supply air temperature sensor Item Description Filter rack and filters RAT sensor Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Local plumbing and waste water codes, and Controller • Other applicable local codes. Wire tie See to unit application data found in this document. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 12
SCCR (kVA) Unit limitations (ton) Applied voltage Outdoor DB temp Minimum Maximum Maximum (°F) 208/230-1-60 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Gas Code, ANSI Z223.1 – Latest Edition (in U.S.A.), or Sections 7.2, 7.3, or 7.4 of Gas Installation Codes, CSA-B149.1 (in Canada) - Latest Edition, and/or applicable provisions of the local building Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
4 point load location (lb) 6 point load location (lb) (ton) Shipping Operating 04 (3) 05 (4) 06 (5) 04 (3) 05 (4) 06 (5) Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 15
Flue extension kit (1FE0414) Flue extension kit (1FE0415) Flue extension kit (1FE0416) Curb rigid 14 in. small footprint Curb rigid 24 in. small footprint Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 16
Figure 11: ZL04 unit dimensions Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 17
Figure 12: ZL05-06 unit dimensions Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 18
1TB0401 - through the base electrical and through the curb gas 1TB0403 - through the base electrical and gas Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
When fastening ductwork to side duct flanges on unit, insert screws through duct flanges only. DO NOT insert screws through casing. Outdoor ductwork must be insulated and water-proofed. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
R-410A compressor lubricants are known to cause long term damage to some synthetic roofing materials. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Voltage tolerances which must be maintained at the supplied disconnect switch. compressor terminals during starting and running conditions are indicated on the unit rating plate and Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 22
A or L1 and C or L3 only. Note: The maximum length is measured from the unit to the thermostat and back to the unit. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Typical field power and control wiring Typical power wiring Figure 19: Typical Smart Equipment™ Control wiring Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
17.3 11146 11.5 1 13.8 24.9 25.6 11446 16.8 28.7 29.3 575-3-60 None 13.4 13.8 11058 17.1 17.6 11458 13.8 1 13.3 22.6 23.1 Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 25
Non-fused disconnect, verify on the unit nameplate that the disconnect is properly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
14.1 10646 14.6 11146 11.5 1 13.8 22.3 22.9 11446 16.8 26.6 575-3-60 None 11.6 11058 14.9 15.4 11458 13.8 1 13.3 20.4 20.9 Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 27
Non-fused disconnect, verify on the unit nameplate that the disconnect is properly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
16.8 11146 11.5 1 13.8 24.4 25.1 11446 16.8 28.2 28.8 575-3-60 None 12.8 13.2 11058 16.4 16.9 11458 13.8 1 13.3 21.9 22.4 Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 29
Non-fused disconnect, verify on the unit nameplate that the disconnect is properly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
14.1 11146 11.5 1 13.8 21.8 22.4 11446 16.8 25.5 26.1 575-3-60 None 11.1 11.5 11058 14.3 14.8 11458 13.8 1 13.3 19.8 20.3 Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 31
Non-fused disconnect, verify on the unit nameplate that the disconnect is properly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Non-fused disconnect, verify on the unit nameplate that the disconnect is properly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Non-fused disconnect, verify on the unit nameplate that the disconnect is properly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 34
Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
55-78 45-75 Gas limit setting (ºF) Gas piping connection (in.) Dimensions (in.) Length 74.1 74.1 Width 48.9 48.9 Height 32.5 32.5 Operating weight (lb) Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 37
2 - (16 x 25 x 2) 2 - (16 x 25 x 2) 2 in. throwaway, standard, MERV 4 (Minimum Efficiency Reporting Value). Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 38
44-73 49-77 Gas limit setting (ºF) Gas piping connection (in.) Dimensions (in.) Length 74.1 74.1 Width 48.9 48.9 Height 40.6 40.6 Operating weight (lb) Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 39
4 - (16 x 16 x 2) 4 - (16 x 16 x 2) 2 in. throwaway, standard, MERV 4 (Minimum Efficiency Reporting Value). Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 40
35-58 43-72 Gas limit setting (ºF) Gas piping connection (in.) Dimensions (in.) Length 74.1 74.1 Width 48.9 48.9 Height 40.6 40.6 Operating weight (lb) Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Refer to Table 16. The heating value of the gas may differ with Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 42
Units require either a 1/2 in. or 3/4 in. pipe connection at the entrance fitting. Line should not be sized smaller than the entrance fitting size. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 43
Venting slots in the heating compartment access panel remove the need for a combustion air hood. The gas heat flue exhaust is routed from the Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
If factory installed, refer to the instructions included with the outdoor air hood to complete the assembly. Field installed economizer accessories include complete instructions for installation. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 45
Table 18: Supply air limitations Model (ton) Supply air (CFM) Minimum Maximum ZL04 (3) 1500 ZL05 (4) 1200 2000 ZL06 (5) 1500 2500 Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 46
As the altitude or temperature increases, density correction factors are shown in Table 19 and the density of air decreases. In order to use the Figure 24. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 47
BHP requirement. Solution: As in the example above, no temperature information is given so 70°F is assumed. The 1.4 in. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 48
Review the RPM range for the motor options available. Select the appropriate drive if multiple drives are available for the chosen motor. Determine turns open to obtain the required operation point. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Blower performance includes gas heat exchangers and 2 in. filters. See static resistance table for additional applications. Note: See rpm selection table to determine required motor sheave setting and to determine the maximum continuous BHP. kW = 0.929 x BHP Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 51
Blower performance includes gas heat exchangers and 2 in. filters. See static resistance table for additional applications. Note: See RPM selection table to determine required motor sheave setting and to determine the maximum continuous BHP. kW = 0.857 x Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Note: 24 V wires 261/orange, 267/red, 238/white can be moved up to different taps depending on the airflow and static requirements of the application. See the relevant unit's wiring diagram. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Blower performance includes gas heat exchangers and 2 in. filters. See static resistance table for additional applications. Note: See RPM selection table to determine required motor sheave setting and to determine the maximum continuous BHP. kW = 0.929 x Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 54
Blower performance includes gas heat exchangers and 2 in. filters. See static resistance table for additional applications. Note: See RPM selection table to determine required motor sheave setting and to determine the maximum continuous BHP. kW = 0.857 x Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
06 (5) Std. Direct drive Med. 1750 0.87 1.15 56HZ 1.9 - 2.9 1VL34 AK46 H. static 1750 0.87 1.15 2.8 - 3.8 1VL44 AK46 Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 57
Verify proper sheave alignment; tighten blower pulley and motor sheave set screws after these adjustments. Re-checking set screws and belt tension after 10-12 hrs. run time is recommended. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 58
The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
SD-24 and R 24 VAC common for thermostat power Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 60
10KΩ at 77°F, type III negative temperature VDC reading EC2+ to EC2– with open circuit. Used in suction line temperature safety. coefficient thermistor Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 61
Not effective for one stage compressor UCBs. If demand is present and permissions 24 VAC hot output for compressor 2 allow compressor 2 operation; output with compressor cooling, comfort ventilation cooling or heat pump heating demands Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 62
Button for display menu acknowledgment and navigation Button for display menu navigation and zeroing of active compressor CANCEL ASCD timer 4-way Joystick for display menu navigation Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 63
Be sure the cable you use fits the modular jack housing. The preassembled cables that are available from Anixter (Part No. CBL-NETWORKxxx) use 24 gauge wire. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
30 seconds. Additionally, the indoor for the compressor has been completed. After the blower has a minimum off delay of 10 seconds. compressor de-energizes, the blower is stopped Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 65
Should a high-pressure switch open three times 45°F (default). When the OAT Sensor senses a within two hours of operation, the UCB will lock- Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 66
(opens at 625 ± 25 psig). lockouts. A low-pressure switch to protect against loss of refrigerant charge, (opens at 50 ± 5 psig). Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
0.25 V lower than +) SA BUS communication circuit to the UCB. Through the unit wiring harness, may continue on to the 4-stage board and/or fault detection and diagnostics board Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 68
24 V~ 24 VAC hot supplied for the air monitoring station sensor Connects through circuit trace to 24 V~ IN pin HOT Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 69
When wiring unit and other devices using the SA Bus and FC Bus, see Table "Cable for FC Buses and SA Buses in Order of Preference". Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
LIMIT input 3 times in 1 hour, an alarm appears and the FAN output is energized. The heating H1 and H2 outputs are de-energized until the alarm is cleared. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
The ICB energizes the main gas valve, second stage gas valve and spark outputs for a 10 second ignition Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
6 on the LED. When the high temperature switch closes, the control will restart the ignition sequence beginning with pre-purge. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
You must turn off the power to the unit and gas valve opens to supply gas to the burner after turn on the power to the unit again to reset the ICB. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Note: This feature must only be used by a qualified service technician. To retrieve error codes: Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
First stage compressors will energize after the built-in time delay (five minutes). Post start checklist Verify correct system pressures. Measure the temperature drop across the evaporator coil. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Check for gas leaks in the unit piping as well as the supply piping. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
1 cubic foot dial to make a stage. revolution with a 200,000 Btuh furnace run- ning. To determine rotations per minute, divide 60 by 19 = 3.16. To calculate rotations Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
"LO" marking on the valve (see Figure and Figure ). Manifold pressure adjustment procedure. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 79
Med, NOx High, NOx High Low, ULN High, ULN ZL06 (5) Low, NOx three phase Med, NOx High, NOx High Low, ULN High, ULN Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Remove the heat shield on top of the manifold supports. Burners are now accessible for inspection and/or replacement. Note: Reverse the above procedure to replace the assemblies. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
• A red heating lead Figure 30: 3 ton through 5 ton, 1/2 in. two stage gas valve Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Caution should be used at all times as the supply air blower may energize regardless of the room thermostat fan switch position. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 83
Verify that there are no conditioned air leaks or heat exchanger breaches to interfere with ignition or the burners. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 84
ICB error history has been cleared None required - normal operation steady on green LED Normal operation with a call for None required - normal operation heating operation Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 85
If it is open, the switch must be reset before operation can resume. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Page 86
This includes the occurrence of repeated fault codes during a call for heat. During a hard lockout, cycle high-voltage power to the the unit will respond to calls for cooling or fan operation, but ignores calls for heat. ICB. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...
Equipment™ Quick Start Guide. Note: For more in-depth sequence of operation of the Smart Equipment™ control, refer to the Smart Equipment™ Controls Sequence of Operation Overview LIT-12011950. Installation Manual ZL Series 3 ton to 5 ton 60 Hz R-410A Johnson Controls Ducted Systems...