Viessmann VITODENS 200-W Service Instructions Manual page 81

Table of Contents

Advertisement

Fault codes
(cont.)
Fault
Const.
code on
the dis-
play
F2
X
F3
X
F4
X
F7
X
F8
X
weath.-
System char-
comp.
acteristics
X
Burner in a fault
state
X
Burner in a fault
state
X
Burner in a fault
state
X
Burner blocked Short circuit
X
Burner in a fault
state
Troubleshooting
Cause
Measures
The tempera-
Check the heating
ture limiter
system fill level.
has respon-
Check the circula-
ded
tion pump. Check
the temperature
limiter and con-
necting cables.
Vent the system.
Press "E RESET"
Flame signal
Check the ionisa-
is already
tion electrode and
present at
connecting cable.
burner start
Press "E RESET"
No flame sig-
Check the ionisa-
nal
tion electrode and
cable, measure the
ionisation current,
check the gas
pressure, check
the gas train, igni-
tion, ignition mod-
ule, ignition elec-
trodes and the con-
densate drain.
Press "E RESET"
Check the water
or water pres-
pressure sensor
sure sensor
and the connecting
lead broken
cable
The fuel valve
Check the gas
closes too
train. Check both
late
control paths.
Press "E RESET"
81