Function description
Control functions
When the screed drying function is acti-
vated, the heating circuit pump of the
mixer circuit is switched ON and the flow
temperature will be held at the selected
profile. After completion (30 days), the
mixer circuit will again be regulated auto-
matically via the set parameters.
Observe EN 1264. The report to be pro-
vided by the heating contractor must
contain the following heat-up details:
■ Heat-up data with respective flow tem-
peratures
■ Max. flow temperature achieved
■ Operating condition and outside tem-
perature during handover
Temperature profile 1: (EN 1264-4) code "F1:1"
50
40
30
20
10
1
5
Temperature profile 2: (ZV parquet and flooring technology) code "F1:2"
50
40
30
20
10
1
5
100
(cont.)
10
15
20
10
15
20
The various temperature profiles are
adjustable via coding address "F1".
The function continues after power fail-
ure or after the control unit has been
switched OFF. "Heating and DHW" will
be started after the screed drying func-
tion has been terminated or if code
"F1:0" is manually adjusted.
25
30
Days
25
30
Days