Checking Outputs (Relay Test) - Viessmann VITODENS 200-W Service Instructions Manual

Table of Contents

Advertisement

Temperatures, boiler coding card and brief...
Brief scan
E
0: no exter-
nal
demand
1: external
demand
3
0
A
0
4
0
5
0
b
0
C
0
c
0
d
0

Checking outputs (relay test)

Weather-compensated control unit
Press the following keys:
1. K + d simultaneously for approx.
2 s
The following relay outputs can be controlled subject to system design:
Display screen
Base load
Full load
Int. pump on
Display screen
0: no exter-
External 0 to 10 V hook-up
nal blocking
Display in %
1: external
0: no external hook-up
blocking
0
Set boiler water temperature
0
Highest demand temperature
Burner control unit type
0
Set cylinder temperature
0
Max. output in %
Boiler coding card (hexadecimal)
Version
Device
0
0
2. a/b
3. d
Explanation
Burner modulation base load
Burner modulation full load
Int. output 20
Service scans
(cont.)
Appliance type
Version
Burner control unit
Variable
Software
speed
version
pump
variable
0 w/o
speed pump
1 Wilo
0: no varia-
2 Grundfos
ble speed
pump
for the required relay out-
put
relay test is completed
67