Electrical Data - Carrier AquaForce 30XW-V Installation, Operation And Maintenance Instructions

Variable-speed water-cooled liquid chillers/ variable-speed water-to-water heat pumps
Table of Contents

Advertisement

4 - PHYSICAL AND ELECTRICAL DATA

4.2 - Electrical data

30XW-V/30XWHV
Power circuit
Nominal power supply
Voltage range
Control circuit
Start-up current
(1)
Maximum power factor
(2)
Cosine phi
Harmonic distortion rate
(3)
Maximum power input
(4)
Circuit A
Circuit B
With option 81
Eurovent current draw
Circuit A
Circuit B
With option 81
Maximum current draw (Un)
(4)
Circuit A
Circuit B
With option 81
Maximum current draw (Un -10%)
Circuit A
Circuit B
With option 81
Maximum power input with option 150B
Circuit A
Circuit B
With option 81
Maximum current draw (Un) with option 150B
Circuit A
Circuit B
With option 81
Dissipated power
(3)
(1) Instantaneous start-up current.
(2) May vary, based on the short-circuit current/max. current draw ratio of the system transformer. Values obtained at operation with maximum unit power input.
(3) Values obtained at operation with maximum unit power input.
(4) Values obtained at operation with maximum unit power input. Values given on the unit name plate.
Eurovent unit operating conditions: evaporator entering/leaving water temperature = 12°C/7°C, condenser entering/leaving water temperature = 30°C/35°C.
Gross performances, not in accordance with EN14511-3:2013. These performances do not take into account the correction for the proportional heating capacity and
power input generated by the water pump to overcome the internal pressure drop in the heat exchanger.
580
V-ph-Hz
V
A
0,91-
0,93
> 0,98
> 0,98
%
35-45
35-45
kW
155
kW
-
kW
-
A
175
A
-
A
-
A
245
A
-
A
-
(3)
A
270
A
-
A
-
(4)
kW
141
kW
-
kW
-
(4)
A
222
A
-
A
-
W
3000
630
810
880
400-3-50
360-440
24 V via the built-in transformer
Negligible (lower than maximum current drawn)
0,91-
0,91-
0,91-
0,93
0,93
0,93
> 0,98
> 0,98
35-45
35-45
193
222
246
-
-
-
-
-
-
200
240
265
-
-
-
-
-
-
300
346
383
-
-
-
-
-
-
330
380
421
-
-
-
-
-
-
173
199
221
-
-
-
-
-
-
272
314
348
-
-
-
-
-
-
4200
4700
5300
1150
1280
1470
0,91-
0,91-
0,91-
0,93
0,93
0,93
> 0,98
> 0,98
> 0,98
35-45
35-45
35-45
155
193
222
155
193
193
310
386
415
175
200
240
175
200
200
350
400
440
245
300
346
245
300
300
490
600
646
270
330
380
270
330
330
540
660
710
141
173
199
141
173
173
282
346
372
222
272
314
222
272
272
444
544
586
6000
8400
8900
1570
1710
0,91-
0,91-
0,93
0,93
> 0,98
> 0,98
35-45
35-45
222
246
222
246
444
492
240
265
240
265
480
530
346
383
346
383
692
766
380
421
380
421
760
842
199
221
199
221
398
442
314
348
314
348
628
696
9400
10600
13