Advanced Settings Guide
1.6.4 Anti Short Cycle (ASC) Timer
The minimum off time is the number of seconds after a call and before a new
heating or cooling call can be initiated.
Options: 0 to 300 seconds
Default: 300 seconds
1.
Main Menu
2.
Advanced Settings
3.
Heating & Cooling
4.
Enter Professional Access Code "1886"
5.
Anti Short Cycle
Figure 49
1.6.5 Cycle Time
The minimum off time is the number of seconds after a call and before a new
heating or cooling call can be initiated.
Options: 60 to 300 seconds
Default: 180 seconds
1.
Main Menu
2.
Advanced Settings
3.
Heating & Cooling
4.
Enter Professional Access code "1886"
5.
Cycle Time
Figure 50
1 8 |
1.6.6 Zero Energy Band
This feature establishes the temperature diff erential at which a heating or cooling
call occurs. The room temperature will need to drop by this value from the heating
setpoint for a heating call to occur. For cooling, the room temperature will need to
be raised by this value.
Options: 0.5°F to 2°F
Default: 1 °F.
1.
Main Menu
2.
Advanced Settings
3.
Heating & Cooling
4.
Enter Professional Access code "1886"
5.
Zero Energy Band
Use the Up and Down keys to select the range.
Figure 51
Bosch Connected Control BCC100 Thermostat (01.2022)