IBC SFC 99 Quick Start Manual page 2

Fuel conversion to natural gas - p-805

Advertisement

Combustion Test Target Ranges
Figure:
Gas valve and fan
The Low Fire (zero-offset) valve adjustment cap on the gas valve has been factory set. Do not adjust this screw in 
the field unless indicated   i n these instructions. 
After converting the appliance to natural gas, a combustion (CO
using properly functioning and calibrated combustion analyzing equipment and the results compared to the values 
in Table 1.
Natural Gas
Max. CO
 value
2
Min. CO
 value
2
Table 1
- CO
values at High and Low Fire
2
2 |
High Fire with front cover open
10.1%
9.1%
) reading must be taken by a qualified technician 
2
Low Fire with front cover
Actual Value at High Fire 
open
9.1%

Advertisement

loading

This manual is also suitable for:

Sfb 99