Relays (outputs)

Output controllers are used to expand the number of relays (outputs) on a DGP or control panel. Each output controller expands the
outputs by eight. A DGP can have two output controllers connected, increasing the outputs to a maximum of 16 per DGP. An Alliance
System can have up to 32 output controllers, which allows a system maximum of 255 outputs.
If there are more than two output controllers connected to the main control panel, resulting in more than 16 outputs, the output numbers are
duplicated on DGP 1. When this is done, one of two options can be used:
1. The outputs on DGP 1 are not used.
or
2. Both outputs are activated together.
Example:
If the main control panel has three output controllers and DGP 1 has one output controller, when output 17 is
active, the first output on the third output controller connected to the control panel and the first output on the
output controller that is connected to DGP 1 are both activated.
Output numbers are always the same as the first 16 zone numbers on the DGP they are connected to. If a DGP address does not exist
because the previous DGP has an expanded number of zones, the output numbers of that DGP address cannot be used. The output numbers
can be used if output controllers are connected to the control panel that corresponds to those output numbers.
Example:
DGP 1 has 32 zones:
DGP 1 outputs (max 16):
(DGP 2 outputs 33-48 are not used)
DGP 3 has 32 zones:
DGP 3 outputs:
(DGP 4 outputs 65-80 are not used)
Strobe and siren outputs
The internal strobe output is always treated as output 2. The internal siren speaker output on the control panel is always treated as output
15 and the external siren speaker output on the control panel is always treated as output 16. On DGPs with siren speaker outputs, the last of
the 16 output numbers associated with that DGP address is the siren output. For example, on DGP 3 the siren speader output is output 64.
DGP
Siren output number
DGP 1
32
DGP 2
48
DGP 3
64
DGP 4
80
DGP 5
96
DGP 6
112
DGP 7
128
DGP 8
144
To enable the siren speaker output, the output number representing the siren output must be assigned to the required siren event flag
number. The siren event flag numbers are programmed in installer programming option 2 (Area database).
Output control groups
Output control group numbers identify a group of eight outputs controlled by the control panel, a DGP, or a RAS. When an output control
group is assigned to a RAS, the open collector output (OUT) terminal follows the first output of the output control group.
Programming steps
1.
Press MENU, enter 1278, and press ENTER to access system programming.
2.
Enter 19 and press ENTER to access installer programming. Press MENU (advanced menu).
3.
Enter 16 and press ENTER to access event to output programming.
4.
Enter the output number to be programmed and press ENTER.
5.
Enter the event flag number needed to trigger the output and press ENTER.
6.
Enter the time zone assigned to the output and press ENTER.
7.
Press MENU to toggle between Output active or Inactive during time zone and press ENTER.
8.
Press MENU to toggle between Output is inverted or Noninverted and press ENTER.
16
17-48
17-32
49-80
49-64
DGP
Siren output number
DGP 9
160
DGP 10
176
DGP 11
192
DGP 12
208
DGP 13
224
DGP 14
240
DGP 15
-
AL-2017/AL-3017 Installation Manual