Cod. +050003515 - rel. 1.4 - 29.09.2015
DPWL*: sensore rilevatore perdite gas refrigerante / refrigerant gas leak sensor
Semiconductor sensor R22-R134a-R404a-R407a-
Infrared sensor
R407c-R407f-R410a-R507a-R290-CO2 version
CO
P1
J5
J4
Infrared
J6
(IR-RS)
Delay
Alarm
Reset
Sensor
TP
PC board
Semiconductor
(Alarm)
Audible Alarm
(SC) Sensor
and Relay Set Point
Voltage Test Point
PC board
GREEN
RED
GREEN
LED
LED
LED
P4
P2
TP2 (Vs)
TP2
Sensor
4-20mA
Voltage
(Vs)
ADJ V
Test Point
P3
J7 J8 J9 J10
Board
Ground
SPAN
CN4
TP3 (0V)
Plane
TP3
Test Point
0
0
1
2
(0V)
AC Select
AC Select
J1
G
+
–
5
10
5
10
J1
Modbus
Volts
CN1
J3
CN1
CN2
CN3
DC
DC
Select
Select
0V V+
0V V+
J2
12-24 Vdc
GNX
V
I
J2
12-24 Vdc
Output Signal
Fig. 1
Legenda:
SW1 and SW2
J4 Reset Jumper
CN3 Relay Connector
Modbus Addressing
J3 Audible Alarm
Jumper
ON
ADDR
SW1
SW2
(Then
(DEC)
(LSB)
(MSB)
OFF
OFF)
Reserved
D00
0
0
J4
Address
D01
1
0
Normal
Reset
D02
0
1
Operation
:
:
:
Valid
D17
1
1
Addresses
:
:
:
247
7
7
CN3
248
8
F
Reserved
:
:
:
Addresses
255
F
F
J1 and J2 Power Supply
P1-P4 Adjustment Pots
J5 and J6 Delay Jumper
Selection Jumper
for Audible Alarm and Relay
AC Power
DC Power
Selected
Selected
Adjusts Alarm Setpoint
J5
P1
for Audible Alarm
J6
and Relay
ON
OFF
J5
Adjusts Zero Level Voltage
P2
J1
J1
for Output Signal
J6
OFF
ON
J2
J2
J5
P3
Adjusts Output Signal Span
J6
CN1
CN1
J5
Adjusts 4-20 mA
P4
Current Output
J6
12-24 Vac
0V V+
12-24 Vdc
CN4 Modbus Connector
J7-J10 Output Jumper
for CN2 Output Signal Connector
GNX
0 Volt, Ground
Ground
G
(Isolated from 0V)
0-5 V Output
Non-inverting
0-10 V Output
+
V
Modbus Signal
G
+ –
V I
GNX
TxD+/RxD+
1-5 V Output
2-10 V Output
Modbus
Output
Non-inverting
–
Modbus Signal
Signal
TxD–/RxD–
I
Current Output, 4-20 mA
La presente guida ha lo scopo di fornire le operazioni minime da eseguire per una veloce confi gurazione e messa in
funzione del sensore rivelatore di gas refrigerante DPWL alimentato con trasformatore 24Vac. Eseguire la confi gura-
zione delle operazioni riportate nell'elenco contraddistinte dal segno (quelle evidenziate con il segno – non sono
da fare) seguendo la colonna del "tipo di confi gurazione da eseguire" in accordo al controllo o tipo di collegamento.
Per maggiori informazioni consultare il foglio istruzioni +050003510 o manuale tecnico +0300035EN.
Conf. Elenco delle azioni da fare
Confi gura il tipo di alimentazione Vac
J1=PRESENTE - J2=NON PRESENTE
J1-J2
Confi gura il tipo di alimentazione Vdc
J1= NON PRESENTE - J2= PRESENTE
Confi gura il segnalatore acustico
J3
J3= PRESENTE = attivo
J3= NON PRESENTE = disattivo
version
Impostazione del ritardo allarme selezionando il
2
jumper seguendo la tabella sotto riportata. Se si ha
un collegamento seriale RS485 selezionare J5=Off
J5
P1
J4
J6
TX
e J6=Off , impostando il ritardo da parametro via
Delay
P2
+V
Alarm
seriale.
SIGNAL
TP1(Alarm)
–V
Zero
Delay jumper Sounder and Relay Delay
Addressing
RX
J5-J6
J5
J6
OFF
OFF
0 (no delay)
P4
RED
SW1
SW2
LED
ON
OFF
1 minute
4-20mA
OFF
ON
5 minutes
P3
Volts
ON
ON
10 minutes
0
0
1
2
SPAN
Legenda:
CN4
5
10
5
10
On=Presente
Off =Non Presente
G
+
–
J7 J8 J9 J10
Confi gura indirizzo seriale: SW1 seleziona gli indi-
Modbus
J3
CN2
CN3
rizzi da 1 a 15. SW2 moltiplica il valore impostato su
SW1-
SW1 per un valore 16. Vedi tabella 2
GNX
V
I
SW2
Output Signal
Formula: ID = SW1+(SW2 x 16)
Esempio: ID = 17 SW1=1; SW2=1
Fig. 2
Collegare il cavo seriale RS485 prestando attenzio-
CN4
ne ai collegamenti Defaul Baud rate 9600. Verifi care
che il software preveda la gestione del sensore.
Collegamenti uscita digitale N/O – COM
CN3
(max 1A/24V)
CN2 Collegare uscita corrente tra 0V e I (vedi Nota 3)
Alimentare il sensore con trasformatore esterno
12...24 Vac 3 VA (Se si alimenta solo sensore si
possono usare i seguenti trasformatori:
CN1
TRA12VDE00 – pannello,
TRADR4W012 – guida omega,
Normally
N/O
TRASP3E120 – a spina);
Open
COM
da fare
Common
Legenda
Note:
Usato con controllo IR33 Universale il valore espresso a display in ppm per la versione semiconduttore è x 10, per la
N/C
Normally
versione infrared x100; È possibile alimentare in DC anche prelevando l'alimentazione da pRACK dai terminali +VTerm e
Closed
GND (J24) In questo caso DPWL - J1 non presente, J2 presente; J7 – J8 – J9 – J10 si confi gurano solo se si desidera l'uscita in
tensione (vedi manuale tecnico).
Cambio del baud rate da 9600 (default) a 19.200
1. Posizionare i commutatori rotativi SW1=F e SW2=F;
2. Cortocircuitare per un breve attimo il jumper J4;
3. Rimpostare l'indirizzo desiderato di SW1 e SW2;
4. Per verifi care se è stato cambiato, togliere l'alimentazione e verifi care se alla riaccensione il led rosso esegue un lampeg-
0
0 Minutes
gio (conferma dell'avvenuto cambiamento del parametro);
(No Delay)
1
1 Minutes
Per cambiare il livello di soglia allarme ppm
Delay
1. Collegare il multimetro in volts DC tra TP3 (0V–GND) e TP1 (alarm).
2. Ruotare il trimmer P1 nella scala da 0 a 5Vdc selezionando il valore ( scala lineare). Per il calcolo applicare la seguente formula:
5
5 Minutes
Delay
ppm (set point desiderato) x 5V
V
=
(TP1-TP3)
max valore fondo scala ppm
10 Minutes
10
Delay
max valore fondo scala ppm: Semiconduttore = 1000; Infrared = 10000.
Se possibile, cambiare la soglia allarme da supervisore o parametri modbus.
Esempio selezione indirizzo ID (SW1-SW2)
Address SW1 SW2 Selection
0
0
0
Reserve
1
1
0
Address 1
2
2
0
Address 2
J7
J8
J9
J10
3
3
0
Address 3
4
4
0
Address 4
5
5
0
Address 5
6
6
0
Address 6
7
7
0
Address 7
8
8
0
Address 8
9
9
0
Address 9
10
A
0
Address 10
Tipo di confi gurazione da eseguire
pRACK /pCO3
pCO5/PVPRO/
IR33 Univ.
(collegamento
PWPRO (collega-
(collegamento
ingresso analogico
mento seriale
ingresso analogico)
4...20mA)
RS485 Modbus)
Vedi nota 1
-
-
-
-
-
-
-
-
-
Vedi nota 2
- non fare
500 x 5
Es. sensore ver. semiconduttore
V
=
(TP1-TP3)
con set point a 500 ppm
1000
Address SW1 SW2 Selection
Address SW1 SW2
11
B
0
Address 11
.........
.... ......
12
C
0
Address 12
246
6
F
13
D
0
Address 13
247
7
F
14
E
0
Address 14
248
8
F
15
F
0
Address 15
249
9
F
16
0
1
Address 16
250
A
F
17
1
1
Address 17
251
B
F
18
2
1
Address 18
252
C
F
19
3
1
Address 19
253
D
F
20
4
1
Address 20
254
E
F
21
5
1
Address 21
255
F
F
The purpose of this guide is to describe the minimum operations required for quick confi guration and setup of the
DPWL refrigerant gas sensor supplied with 24 Vac transformer. Perform the confi guration operations shown in the list
marked (those marked – should be skipped) under the "Type of confi guration required" column, depending on the
controller used or type of connection. For further information see instruction sheet +050003510 or technical manual
+0300035EN.
Funz.
Conf. List of operations
autonomo
Set the type of power supply Vac
J1=PRESENT - J2=NOT PRESENT
J1-J2
Set the type of power supply Vdc
J1= PRESENT - J2= NOT PRESENT
Enable audible signal
J3
J3= PRESENT = enabled
J3= NOT PRESENT = disabled
Set the alarm delay by setting the jumpers shown
in the table below. If an RS485 serial connection is
used, select J5=Off and J6=Off , setting the delay by
parameter via the serial connection.
Delay jumper Sounder and Relay Delay
J5
J6
J5-J6
OFF
OFF
0 (no delay)
ON
OFF
1 minute
OFF
ON
5 minutes
ON
ON
10 minutes
Key:
On=Present
Off =Not present
Set serial address: SW1 selects addresses from 1 to
15. SW2 multiplies the value set on SW1 by value
SW1-
16. See table 2
SW2
-
Formula: ID = SW1+(SW2 x 16)
Example: ID = 17 SW1=1; SW2=1
Carefully connect the RS485 serial cable. Default
CN4
baud rate 9600. Make sure the software allows
-
management of the sensor.
N/O – COM digital output connections
CN3
(max 1A/24V)
Connect current output between
CN2
-
0V and I (see Note 3)
Power up the sensor with 12-24 Vac 3 VA external
transformer (if only powering the sensor the
following transformers can be used:
CN1
TRA12VDE00 – panel,
TRADR4W012 – DIN rail,
TRASP3E120 – plug-in);
Tab. 1
to do
Key
- not to do
Note:
When used with the IR33 Universal controller the value on the display in ppm for the semiconductor version is x 10, for the
infrared version is x100; DC power is also available from the pRack via the +VTerm and GND (J24) terminals. In this case,
DPWL - J1 is not present, J2 is present; J7 – J8 – J9 – J10 are only confi gured for voltage output (see the technical manual).
Changing the baud rate from 9600 (default) to 19200
1. Switch rotary selectors SW1=F and SW2=F;
2. Jumper terminal J4 for a brief moment;
3. Reset the desired address on SW1 and SW2;
4. To make sure that the setting has been changed, power down and when restarting check that the red LED fl ashes (confi r-
ming the parameter has been changed);
Changing the alarm threshold in ppm
1. Connect the multimeter with DC voltage setting between TP3 (0V–GND) and TP1 (alarm).
2. Turn trimmer P1 on the scale from 0 to 5 Vdc to select the value (linear scale). For the calculation apply the following formula:
ppm (set point desiderato) x 5V
V
=
(TP1-TP3)
max valore fondo scala ppm
= 2,5 V
max. full scale ppm value: Semiconduttore = 1000; Infrared = 10000.
It is possible change the threshold alarm by supervisor or modbus parameter.
Example address ID settings (SW1-SW2)
Selection
Address SW1 SW2 Selection
Address SW1 SW2 Selection
.............
0
0
0
Reserve
11
Address 246
1
1
0
Address 1
12
Address 247
2
2
0
Address 2
13
Reserve
3
3
0
Address 3
14
Reserve
4
4
0
Address 4
15
Reserve
5
5
0
Address 5
16
Reserve
6
6
0
Address 6
17
Reserve
7
7
0
Address 7
18
Reserve
8
8
0
Address 8
19
9600 Baud rate
9
9
0
Address 9
20
19200 Baud rate
10
A
0
Address 10
21
Tab. 2
Type of confi guration required
pRack /pCO3
pCO5/PVPRO /
IR33 Univ. (analogue
(4 to 20 mA
PWPRO (RS485
Stand-alone
input connection)
analogue input
Modbus serial
operation
See note 1
connection)
connection)
-
-
-
-
-
-
-
-
-
-
-
-
See note 2
Tab. 1
500 x 5
E.g. semiconductor ver. sensor
V
=
= 2,5 V
(TP1-TP3)
with set point 500 ppm
1000
Address SW1 SW2
Selection
B
0
Address 11
.........
.... ......
.............
C
0
Address 12
246
6
F
Address 246
D
0
Address 13
247
7
F
Address 247
E
0
Address 14
248
8
F
Reserve
F
0
Address 15
249
9
F
Reserve
0
1
Address 16
250
A
F
Reserve
1
1
Address 17
251
B
F
Reserve
2
1
Address 18
252
C
F
Reserve
3
1
Address 19
253
D
F
Reserve
4
1
Address 20
254
E
F
9600 Baud rate
5
1
Address 21
255
F
F
19200 Baud rate
Tab. 2
Need help?
Do you have a question about the DPWL Series and is the answer not in the manual?
Questions and answers