Communication Protocol Manual
Table 7:
Default Class assignment for analog input data
Point index
Name/description
See the point list manual.

Analog data scaling

The four scaling options associated with analog input data reporting are None, Ratio,
Multiplicative and Divisor. The selection None means that no scaling is performed
on the source IEC 61850 value. The value is reported as such to DNP.
Ratio, multiplicative and divisor scaling methods
The PCM600 tool contains four value arguments related to the scaling methods:
sourceMinVal, sourceMaxVal, destMinVal and destMaxVal. The use of these
arguments differs depending on the scaling method.
The ratio, multiplicative and divisor scaling methods use the first two arguments,
souceMinVal and sourceMaxVal, to define the source value range inside which the
object is to be used. The complete value range of the object is usually wanted even
though the user could freely define the source range.
Arguments three and four, destMinVal and destMaxVal, define the destination value
range. In ratio scaling, arguments destMinVal and destMaxVal define the
corresponding range of the scaled, reported DNP value.
=
DNPvalue
(
sourceValue sourceMinVal
GUID-9F985816-2268-412A-AE24-ED90EAC44AD7 V1 EN
In multiplicative scaling, argument four destMaxVal becomes a scale constant and
argument three destMinVal becomes an offset.
(
=
DNPvalue
sourceValue destMaxVal
GUID-4CB1987F-BDD8-48A2-9389-20B0B2EB271F V1 EN
In divisor scaling, argument four destMaxVal becomes a scale constant and argument
three destMinVal becomes an offset.
sourceValue
=
DNPvalue
destMaxVal
GUID-01F26415-274B-4844-B861-DB7D6E56D91B V1 EN

Fault record timestamp

When a new fault occurs, the fault number (LD0.FLTMSTA1.OpCnt.stVal)
increments, and it is stored in the DNP AI event buffer. Other points associated with
Vendor-specific implementation
Default deadband
Configurable IED setting
(
destMaxVal destMinVal
)
×
(
sourceMinVal sourceMaxVal
)
×
+
destMinVal
+
destMinVal
Section 3
Default change event
assigned class (1, 2, 3 or
none)
2
) )
+
destMinVal
)
(Equation 1)
(Equation 2)
(Equation 3)
17