Connecting The Ebus Connector; Volt Connection; Connecting Humidity Sensor; Externalbus Connection - Wolf CWL-2-400 Installation And Operating Instructions Manual

Table of Contents

Advertisement

Installation
5.5.3

Connecting the eBus connector

For connecting an eBus connector, the 2-pole detachable (green) connector X17 is located at the rear of
the display cap (® Exploded view of appliance page 9). The eBus protocol may for instance be used to
connect the Bedienmodul BM-2 (® Connecting Bedienmodul BM-2 page 39). Because of polarity
sensitivity, always connect contacts correctly; the appliance will not work if these contacts have been
interchanged! The optional CO
connected onto the eBus connector.
5.5.4

24 volt connection

On the X16 & X18 connector of the basic pcb, 24 volt is available.
Connector X-16 is for 24 volt connection of the optional Plus pcb.
For position connection (black) connector X16 & X18 (® Electrical diagram page 33). Maximum current
reduction at plug X16 and X18 is 5 VA per connection.
5.5.5

Connecting humidity sensor

The optional humidity sensor has to be connected onto the the X07 connection of the basic pcb. For this,
use the cable supplied with the humidity sensor. In order to connect the humidity sensor, the plastic cover
above the control has to be taken off, after which the X07 connection is accessible.
For connecting the humidity sensor, see ® Connecting humidity sensor page 40.
5.5.6

externalBus Connection

The Modbus/ externalbus (red) connector X15 can for example be used for coupling appliances (®
Coupling appliances using externalBus page 17).
The function of this connector can be adjusted using step number 14.1 to 14.4 in the settings menu.
If the appliance is fitted with a Plus pcb, then this red connector X15 is also in use for connecting the Plus
pcb; several cables then have to be connected onto this connector X15.
5.5.7

Connecting "signal output" connector

The blue 2-pole screw connector X19. This connection is used to give a filter message or fault message.
If a filter or fault message is given in the appliance a contact is closed at connection X19. The operation
of this is set by following step number 16.1.
5.5.8

ModBus Connection

The appliance can be connected with a ModBus system such as a building management system.Using
the (red) 3-pole connector X15 (or with the Plus version the red connector X06 on the UWA2-E pcb) a
connection can be made between the appliance and the ModBus system; (®) for the right connection.
For the correct setting of the jumpers X12, X121 & X122 see the explanation given with electrical diagram
(®); for more information and the correct modBus settings see the separate Modbus manual on the
website!
i
Note
Note: When ModBus is active, the ventilation mode cannot be changed using the display or, if
applicable, the connected multiple switch! Also any connected humidity sensor will not function.
16 | WOLF GmbH
sensor(s) or an extra eBus preheater or postheater (®) can also be
2
xxxx
7100833_202010