Display Elements; Profibus Interfaces; Rs485 Interface - Profichip VPC3+ Manual

Evaluation kit
Table of Contents

Advertisement

3.5

Display Elements

The evaluation board has two LEDs on board. The green LED D2 indicates
correct power supply. The green LED D2 is connected to the DATA_EX-
output of the VPC3+ and lights up each time the VPC3+/C is in data ex-
change mode.
3.6

PROFIBUS Interfaces

PROFIBUS uses a screened twisted pair cable connected to an RS485 in-
terface or a full-duplex fiber-optic link as communication medium. The
Evaluation Board offers both possibilities.

3.6.1 RS485 Interface

The RS485 interface uses differential voltages. It is for this reason that this
interface is less susceptible to interference than a plain voltage or current
based interface. The network may be configured as a daisy-chain or in a
tree configuration.
The VPC3+ evaluation board PROFIBUS coupler carries a 9-pin socket.
This socket is used to connect the PROFIBUS coupler to the PROFIBUS
network as a slave.
Each segment can support a maximum of 32 devices. Individual segments
are linked by means of repeaters. The maximum length for a segment is
determined by the transmission rate. In a PROFIBUS-DP network the
transmission rate is adjusted automatically and ranges from 9.6 Kbit/s to 12
Mbit/s. Slaves adapt their communication rate automatically. All devices
connected to the network communicate at the same transmission rate
(baudrate).
Due to the bus structure of the network any station may be connected or
disconnected without interruptions and a system can be commissioned in
different stages. Extensions to the system do not affect stations that have
already been commissioned. Any failures of stations or new devices are
detected automatically.
VPC3+ Evaluation Kit
Copyright © profichip GmbH, 2005
VPC3+/C Extension Board 3
Revision 2.00
19

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pa006300

Table of Contents