Supply piping
Pipe connections
➔ Installation of a pipe union in the gas line is recommended to
simplify burner removal.
➔ Use of flexible pipe is optional.
note: Flexible pipe causes higher pressure drops than standard
pipe. Consider this when sizing your gas lines.
Bracket
Schelle
Soporte
支座
Pipe union
Rohrverschraubung
联管节
Unión roscada de tubo
Pipe connections
Piping support
➔ Use brackets or hangers to support the gas piping.
➔ If you have questions, consult your local gas company.
Control motor
➔ Install a control motor to modulate the air butterfly valve if not
factory installed on the burner.
note: Be sure the control motor shaft and air butterfly valve shaft
are aligned properly.
Set
screws
BV
shaft
Coupling
Control motor
B
Main gas
shut-off
valve train
A
Motor
shaft
Control
motor

CHeCKLIst AFteR InstALLAtIon

To verify proper system installation, do the following:
1 Make sure that there are no leaks in the gas and air lines.
2 Make sure all the components of the flame monitoring control
system are properly installed. This includes verifying that all switch-
es are installed in correct locations and all wiring, pressure and
impulse lines are properly connected.
3 Make sure components of spark ignition system are installed and
functioning properly.
4 Make sure that the blower rotates in the correct direction. If in-
correct, have a qualified electrician rewire the blower to reverse
its rotation.
5 Make sure all valves are installed in the proper location and cor-
rectly oriented relative to the gas or air flow direction.
InstALL AIR PRe-MIX LIne WItH ReMote BLoW-
eR (WX0850 onLY)
When using a remote blower instead of the packaged blower on
the WX0850, the low fire air pre-mix line must be installed to the
combustion air line. 1/4" diameter braided hose is recommended,
located as shown in figure "Air pre-mix line".
note: A 24" length of 1/4" diameter braided hose is included with
the burner.
Remote
blower
pre-mix
air line
Fuel
inlet
Air pre-mix line
EN-5
Remote
blower
Combustion air
modulation valve