Section 1 Description

1-3-2 Response time

The response time of OSSD outputs are as follows:
F3SN-A
F3SN-A
F3SN-A
F3SN-A
Response time for series connected types is calculated as follows:
For 2 sets:
Response time (ON to OFF): Response time of Light curtain 1 + Response time of Light curtain 2 + 3 ms
Response time (OFF to ON): Response time of Light curtain 1 + Response time of Light curtain 2 + 12 ms
For 3 sets:
Response time (ON to OFF): Response time of Light curtain 1 + Response time of Light curtain 2
Response time (OFF to ON): Response time of Light curtain 1 + Response time of Light curtain 2
Response time of F3SP-B1P is 10 ms, operation time is 100 ms.
[Note]:
B-10
Downloaded from
Elcodis.com
electronic components distributor
Protective
height(mm)
180 to 450
P14 series
459 to 765
774 to 1080
1089 to 1125
Protective
height(mm)
217 to 772
P25 series
787 to 1297
1312 to 1822
Protective
height(mm)
217 to 757
P40 series
787 to 1297
1327 to 1807
Protective
height(mm)
277 to 757
P70 series
817 to 1297
1357 to 1777
+ Response time of Light curtain 3 + 4 ms
+ Response time of Light curtain 3 +16 ms
If the controller is included in the set, calculate safety distance by adding the controller response
time to the F3SN response time.
No. of beams
Response time
(ON to OFF)
20 to 50
10.0
51 to 85
12.5
86 to 120
15.0
121 to 125
15.5
No. of beams
Response time
(ON to OFF)
13 to 50
10.0
51 to 85
12.5
86 to 120
15.0
No. of beams
Response time
(ON to OFF)
7 to 25
10.0
26 to 43
12.5
44 to 60
15.0
No. of beams
Response time
(ON to OFF)
5 to 13
10.0
14 to 22
12.5
23 to 30
15.0
Response time
(OFF to ON)
40
50
60
62
Response time
(OFF to ON)
40
50
60
Response time
(OFF to ON)
40
50
60
Response time
(OFF to ON)
40
50
60