3.1. Install of Smoke Detector
Smoke detectors should be installed in order to detect following place.
・The flow of smoke into position
・Fans forced to inhale position
This detector has suction of smoke by the built-in fan.
There may not be able to suck the smoke sufficiently in ambient wind speed is more than
1m /s. Please be careful.
Caution
Caution
Do not disassemble a detector. It causes trouble.
Do not remove a detector, Fire can not be detected.
Do not use detector which have impacted. And also do not paint or cover a
detector.
Do not wiring while power is on. It causes electric shock and detector troubles.
・The smoke detector detects a scattered light by smoke particles optically.
And that detects a large amount of dust and steam too.
Please install correct location.
・Do not use at the place where it exceeds environmental specification. It
causes trouble.
・Do not install wrong location. The smoke detector cannot detect a smoke.
・Be sure to install the detector away from sources of electrical noise such as
high voltage and high current switches.
[Isolation from electric noise source such as power line]
The signal conductor which is connected to the detector, please wires over 20cm
separating from the power line.
Case it is not possible, please pass in the metallic conduit which the power line is
grounded.