Specification - Fenwal F1H-Q-RYW1K Operation & Instruction Manual

Table of Contents

Advertisement

4.

Specification

(1)
Name
(2)
Type
4.1.
Electrical Specification
(1)
Rated Current
(2)
Range
Operating Voltage
(3)
Sensitivity
(4)
State
LED
(5)
Output
: Photoelectric Smoke Detector
: F1H-Q-RYW1K- xx xx x
①Sensitivity
②Type of Output
③Length of cable
Standard setting F1H-Q-RYW1K-R5BB2
Sensitivity 0.5%/m, Alarm Output B, Trouble Output B, Cable length 2m.
①Sensitivity:0.5%/m~5%/m (Value = R5~05)
②Type of Output:Type of Alarm & Trouble Output
③Length of cable:Cable Length 0=None,2=2m,5=5m。
: DC 20mA
: DC21.6V~DC26.4V(DC24V±10%)
of
Acceptable ripple voltage 300mVp-p
Power supply with connector cable.(See bellow(6))
: Depend on Type of Product. 0.5%/m (Nominal)
: RED LED
Indication
Normal mode
Alarm mode
Trouble mode
Alarm will override trouble.
: Alarm, Trouble Relay Output
Capacity of Relay DC24V,0.5A Resistance loading
State depends on Type of relay.
Type
AA
AB
BA
BB
(
Standard
・State of output will be normal about a second after power supply.
・Output relay is PhotoMOS relay.
・On resistance Max.0.7Ω.Off state leakage current 1μA.
・Insulation Test under DC24V between Relay and Relay, Relay and
Power supply.
Standard Setting is 0.5%/m.(Value=R5)
Standard Setting is Alarm=B,Trouble=B.
(Value = BB)
Standard Setting is 2m. (Value = 2)
State of LED
10 seconds interval
1 seconds interval
Off (not blinking)
Normal
Contact
mode
Alarm
Open
Trouble
Open
Alarm
Open
Trouble
Close
Alarm
Close
Trouble
Open
Alarm
Close
)
Trouble
Close
Page
Alarm
Trouble
Power
mode
mode
Close
Open
Open
Open
Close
Open
Close
Open
Open
Close
Open
Open
Open
Close
Open
Open
Close
Open
Open
Close
Open
Close
Open
Open
ES1613
730110 K0