Install; Installation Place - Fenwal F11-Y1 Series Operation & Instruction Manual

Table of Contents

Advertisement

3. Install

! ! ! ! Warning

3-1. Installation place

Smoke detectors should be installed in order to detect following place.
・The flow of smoke into position
・Fans forced to inhale position
When you use smoke detector in a fast wind speed, it is necessary that the smoke is ongoing around
detector. Please be careful.
Address number should be placed below or sideways
Caution
! ! ! !
Caution
! ! ! !
F11-Y1
・Do not disassemble and repair and remodel a detector. It causes trouble
・Do not remove a detector, Fire can not be detected.
・Do not use a detector which has impacted. And also do not paint or cover a
detector.
・Do not wiring while power is on. It causes electric shock and detector
troubles.
・The smoke detector detects a scattered light by smoke particles optically.
And that detects a large amount of dust and steam too.
Please install correct location.
・Do not use at the place where it exceeds environmental specification. It
causes trouble.
・Do not install wrong location. The smoke detector cannot detect a smoke.
・Be sure to install the detector away from sources of electrical noise such as
high voltage and high current switches.
[Isolation from electric noise source such as power line]
The signal conductor which is connected to the detector, please wires over
20cm separating from the power line.
Case it is not possible, please pass in the metallic conduit which the power line
is grounded.
over 20cm
over
20cm
F11-Y1
ES1103
730110 K0
7