Panel Front Control Board - DAB E-BOX 2G M Instruction For Installation And Maintenance

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 41

9. PANEL FRONT CONTROL BOARD

I ON
Ref.
1
White warning light indicating correct operation of the auxiliary circuits.
2
Red warning light indicating a general alarm.
3
Alarm RESET button.
Electropump P1
4
Green warning light: fixed light indicating pump running.
Green warning light: blinking light indicating pump not available.
5
Yellow warning light indicating pump P1 malfunction alarm
6
Button for manual control or deactivation of pump P1:
- if held down for more than 3 seconds, allows the pump to be switched on manually,
- if pressed quickly, allows deactivation of the respective pump or activation of automatic
operation.
Electropump P2
7
Green warning light: fixed light indicating pump running.
Green warning light: blinking light indicating pump not available.
8
Yellow warning light indicating pump P2 malfunction alarm
9
Button for manual control or deactivation of pump P2:
- if held down for more than 3 seconds, allows the pump to be switched on manually,
- if pressed quickly, allows deactivation of the respective pump or activation of automatic
operation.
ENGLISH
1
2
3
Function
43
4
7
5
8
6
9