Change setting continued
Setting for amount of fluid throughput
Through
per impulse of the volume impulse
meter. The volume impulse meter must
put
be activated in options with Yes
( Ch 6.8).
0.25l/I
Value set or read at throughput limiter,
Volume
at 100% pump rating.
flow
Variation: 22...45, 50...84
1.5l/m
Value set or read at throughput limiter,
Volume
at 100% pump rating of second solar
pump.
flow2
Variation: 22...34, 50, 74
1.5l/m
The factor depends on the type and the
Heat
mixing ratio of heat exchanger fluid.
This factor is used for the energy yield
capacity
calculation.
kJ/lK
Variation: 1...45, 50...84
3.73
The solar pump switches on, when the
Frost
collector sensor value reaches the set
value.
protection
The pump switches off, when the
value set is exceeded by 3K
(hysteresis).
-50.0°C
Hysteresis: 3K (fixed cannot be altered)
Variation: 1...45, 50...84
Lowest limit value of modulation range
PWT
of PWT pump to plate heat exchanger.
Speed
Variation: 3, 8, 11, 63...65, 84
Minimum
30%
Temperature differential between
Tank
collector sensor (TKO) and tank sensor
(TSU) as switch on criteria of solar
diff.
pump.
On
Variation: 1...6, 8...11, 17...19,
7.0K
21...27, 32...38, 43...45,
50...59, 84
Variation:
1...8, 12...14, 17, 18, 20, 21, 35...37,
40, 41, 43, 44, 52...55, 57, 58, 60, 61,
63, 64, 72, 76...84
Setting range:
0.01...10.0 l/Impulse
Presetting:
0.25 l/Impulse
Setting range:
0.1...500.0 l/m (litres/minute)
Presetting:
1.5 l/m
Setting range:
0.1...500.0 l/m (litres/minute)
Presetting:
1.5 l/m
Setting range:
0.01...10.0 kJ/lK
Presetting:
3.73 kJ/lK (at 60°C)
Setting range:
–50°C...–41°C ; frost prot. deactivated
–40°C...+20°C ; frost prot. activated
Presetting:
–50°C
Attention: With variation 20, frost protection should not
be set below 5°C or frost protection should be
deactivated if using a suitable collector fluid
to protect the heat exchanger.
Note:
With sensor short circuit, the pump is driven
at PS Speed Minimum, if the frost protection
temperature > –40°C has been set.
Setting range:
10...100%
Presetting:
30%
Setting range:
0 K...40 K
Presetting:
7.0 K
6
61