Weishaupt WRSol 1.0 Manual page 61

Table of Contents

Advertisement

Change setting continued
Setting for amount of fluid throughput
Through
per impulse of the volume impulse
meter. The volume impulse meter must
put
be activated in options with Yes
( Ch 6.8).
0.25l/I
Value set or read at throughput limiter,
Volume
at 100% pump rating.
flow
Variation: 22...45, 50...84
1.5l/m
Value set or read at throughput limiter,
Volume
at 100% pump rating of second solar
pump.
flow2
Variation: 22...34, 50, 74
1.5l/m
The factor depends on the type and the
Heat
mixing ratio of heat exchanger fluid.
This factor is used for the energy yield
capacity
calculation.
kJ/lK
Variation: 1...45, 50...84
3.73
The solar pump switches on, when the
Frost
collector sensor value reaches the set
value.
protection
The pump switches off, when the
value set is exceeded by 3K
(hysteresis).
-50.0°C
Hysteresis: 3K (fixed cannot be altered)
Variation: 1...45, 50...84
Lowest limit value of modulation range
PWT
of PWT pump to plate heat exchanger.
Speed
Variation: 3, 8, 11, 63...65, 84
Minimum
30%
Temperature differential between
Tank
collector sensor (TKO) and tank sensor
(TSU) as switch on criteria of solar
diff.
pump.
On
Variation: 1...6, 8...11, 17...19,
7.0K
21...27, 32...38, 43...45,
50...59, 84
Variation:
1...8, 12...14, 17, 18, 20, 21, 35...37,
40, 41, 43, 44, 52...55, 57, 58, 60, 61,
63, 64, 72, 76...84
Setting range:
0.01...10.0 l/Impulse
Presetting:
0.25 l/Impulse
Setting range:
0.1...500.0 l/m (litres/minute)
Presetting:
1.5 l/m
Setting range:
0.1...500.0 l/m (litres/minute)
Presetting:
1.5 l/m
Setting range:
0.01...10.0 kJ/lK
Presetting:
3.73 kJ/lK (at 60°C)
Setting range:
–50°C...–41°C ; frost prot. deactivated
–40°C...+20°C ; frost prot. activated
Presetting:
–50°C
Attention: With variation 20, frost protection should not
be set below 5°C or frost protection should be
deactivated if using a suitable collector fluid
to protect the heat exchanger.
Note:
With sensor short circuit, the pump is driven
at PS Speed Minimum, if the frost protection
temperature > –40°C has been set.
Setting range:
10...100%
Presetting:
30%
Setting range:
0 K...40 K
Presetting:
7.0 K
6
61