Variation 32: Calorifier with internal tank for DHW and collector cascade
The WRSol 2.0 determines the temperature differential
between the collector sensors (TKO or TK2) and the
reference sensor (TPU or TSU).
As soon as the temperature differential is greater than the
increase (... Diff. On ) set, the relevant solar pump
(PS or PS2) is activated.
Once the increase ( ... Diff. Off ) or the maximum
calorifier temperature has been reached the solar pump is
switched off. TSU or TPU is selected as reference sensor.
Depending on the average pump speed and the minimum
storage tank temperature, the external heat exchanger can
be blocked via the potential free Multi-funct. Output
(MFA).
In addition an 18 hour block can be activated.
The DHW function (Ch. 7.14) can also influence the MFA
output.
Possible settings MFA output:
0, 1, 2, 5, 6, 7, 8, 9, 10, 11, 12
Variation 33: Calorifier with internal tank for DHW and collector cascade/bypass
The WRSol 2.0 determines the temperature differential
between the collector sensors (TKO or TK2) and the
reference sensor (TPU or TSU).
As soon as the temperature differential is greater than the
increase (... Diff. On ) set, the relevant solar pump
(PS or PS2) is activated.
Once the increase ( ... Diff. Off ) or the maximum
calorifier temperature has been reached the solar pump is
switched off. TSU or TPU is selected as reference sensor.
The three way valve (VBY) is switched over depending on
the collector temperature (TKO or TK2) and the reference
sensor (TBY).
Depending on the average pump speed and the minimum
storage tank temperature, the external heat exchanger can
be blocked via the potential free Multi-funct. Output
(MFA).
In addition an 18 hour block can be activated.
The DHW function (Ch. 7.14) can also influence the MFA
output.
Possible settings MFA output:
0, 1, 2, 5, 6, 7, 8, 9, 10, 11, 12
28
TSU
PWL*
TPU
X2:
eBus
1
2
TKO
3
4
TK2
5
6
TSU
7
8
9
10
11
TPU
12
13
14
15
16
17
18
* optional
TSU
PWL*
B
TPU
AB
M
VBY
A
X2:
1
eBus
2
TKO
3
4
TK2
5
6
TSU
7
8
9
10
TPU
11
12
TBY
13
14
15
16
17
18
* optional
TKO
TK2
PS
PWL*
MFA
TKO
TK2
PS
TBY
PWL*
MFA
PS2
X1:
N
PS
1
N
PS2
2
N
3
N
4
5
6
PS2
X1:
N
PS
1
N
PS2
2
N
3
N
VBY
L
4
5
6

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wrsol 2.0

Table of Contents