HART Prosonic S FMU90 Operating Instructions Manual

HART Prosonic S FMU90 Operating Instructions Manual

Level measurement alternating pump control rake control
Table of Contents

Advertisement

Quick Links

BA00288F/00/EN/15.20
71494895
2020-08-17
Products
Operating Instructions
Prosonic S FMU90
HART
Level measurement
Alternating pump control
Rake control
Solutions
Services

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Prosonic S FMU90 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for HART Prosonic S FMU90

  • Page 1 Products Solutions Services BA00288F/00/EN/15.20 71494895 2020-08-17 Operating Instructions Prosonic S FMU90 HART Level measurement Alternating pump control Rake control...
  • Page 2 Prosonic S FMU90 HART Order code: XXXXX-XXXXXX Ser. no.: XXXXXXXXXXXX Ext. ord. cd.: XXX.XXXX.XX Serial number www.endress.com/deviceviewer Endress+Hauser Operations App A0023555 Endress+Hauser...
  • Page 3: Table Of Contents

    Prosonic S FMU90 HART Table of contents Table of contents Advanced settings ..... 56 Important document information ..4 Simulation .
  • Page 4: Important Document Information

    Important document information Prosonic S FMU90 HART Important document information Document function These Operating Instructions provide all of the information that is required in various phases of the life cycle of the device including: • Product identification • Incoming acceptance •...
  • Page 5 Prosonic S FMU90 HART Important document information The ground terminals are located on the interior and exterior of the device: • Interior ground terminal: protective earth is connected to the mains supply. • Exterior ground terminal: device is connected to the plant grounding system.
  • Page 6: Documentation

    Important document information Prosonic S FMU90 HART Documentation The following documentation types are available in the Downloads area of the Endress +Hauser website (www.endress.com/downloads): For an overview of the scope of the associated Technical Documentation, refer to the following: • W@M Device Viewer (www.endress.com/deviceviewer): Enter the serial number from nameplate •...
  • Page 7: Basic Safety Instructions

    Basic safety instructions Designated use Prosonic S FMU90 is a transmitter for ultrasonic sensors FDU90, FDU91, FDU91F, FDU92, FDU93 and FDU95. To support existing installations, the following sensors can also be connected: FDU80, FDU80F, FDU81, FDU81F, FDU82, FDU83, FDU84, FDU85, FDU86, FDU96.
  • Page 8: Product Description

    Product description Prosonic S FMU90 HART Product description Product layout: polycarbonate field housing Valid for: Order code 030 (housing, material) Option 1 (PC field mounting, IP66 NEMA4x) A0035266  1 Parts of the Prosonic S in the polycarbonate field housing...
  • Page 9: Product Layout: Din Rail Housing

    Prosonic S FMU90 HART Product description Product layout: DIN rail housing Valid for: Order code 030 (housing, material) Option 2 (DIN rail mounting PBT, IP20) A0035268  3 Parts of the Prosonic S in the DIN rail housing Display and operating module...
  • Page 10 Product description Prosonic S FMU90 HART A0035265  4 Parts of the Prosonic S with remote display and operating module DIN rail housing without display and operating module Remote display and operating module for mounting in a cabinet The cable (3m [9.8 ft]) is supplied One possible version of the DIN rail housing is illustrated in the graphic above.
  • Page 11: Incoming Acceptance And Product

    Prosonic S FMU90 HART Incoming acceptance and product identification Incoming acceptance and product identification Incoming acceptance Check the following during goods acceptance: • Are the order codes on the delivery note and the product label identical? • Are the goods undamaged? •...
  • Page 12: Storage, Transport

    Incoming acceptance and product identification Prosonic S FMU90 HART Storage, transport • Pack the device so that it is protected against impact for storage and transportation. The original packaging provides optimum protection. • Permitted storage temperature: –40 to +60 °C (–40 to 140 °F)
  • Page 13: Installation

    Prosonic S FMU90 HART Installation Installation Mounting the polycarbonate field housing Valid for: Order code 030 (housing, material) Option 1 (PC field mounting, IP66 NEMA4x) 5.1.1 Installation conditions Dimensions of polycarbonate field housing ø6.5 (0.26) ≥ ≥ 55 (2.17) 55 (2.17) A0034906 ...
  • Page 14 Installation Prosonic S FMU90 HART 5.1.2 Mounting the device Wall mounting • The housing bracket supplied can also be used as a drilling template. • Mount the housing bracket on a level surface so that it cannot become warped or bent.
  • Page 15: Mounting The Aluminum Field Housing

    Prosonic S FMU90 HART Installation Mounting the aluminum field housing Valid for: Order code 030 (housing, material) Option 3 (aluminum field mounting, IP66 NEMA4x) 5.2.1 Installation conditions Dimensions of the aluminum field housing 180 (7.09) 7 (0.28) 11 (0.43) ≥55 (2.17) ≥55 (2.17)
  • Page 16: Mounting The Din Rail Housing

    Installation Prosonic S FMU90 HART 5.2.2 Mounting the device P ro O rd > A0033331  10 Wall-mounted aluminum field housing Mounting the DIN rail housing Valid for: Order code 030 (housing, material) Option 2 (DIN rail mounting PBT, IP20) WARNING The DIN rail housing meets protection class IP06.
  • Page 17 Prosonic S FMU90 HART Installation 5.3.1 Installation conditions Dimensions Σ = 0 Σ = 1...3 EN 60715 EN 60715 TH 35x7.5/15 TH 35x7.5/15 (1.4x0.3/0.6) (1.4x0.3/0.6) Σ = 4 EN 60715 TH 35x7.5/15 (1.4x0.3/0.6) A0035915  11 Dimensions of Prosonic S with DIN rail housing; Σ: number of additional connection modules. Unit of...
  • Page 18: Installation Of The Remote Display And Operating Module

    Installation Prosonic S FMU90 HART 5.3.2 Mounting the device EN 60715 TH 35x7.5/15 (1.4x0.3/0.6) A0032559  12 Mounting/disassembling the DIN rail housing. Unit of measurement mm (in) Installation Disassembly Installation of the remote display and operating module Valid for: Order code 040 (operation) Option E (illuminated display + keypad, 96x96, panel mounting, IP65 at front) 5.4.1...
  • Page 19 Prosonic S FMU90 HART Installation A0032562  14 Mounting in remote display of FMU860/861/862 Remote display of Prosonic S with adapter plate Opening of remote display of the FMU860/861/862 5.4.2 Mounting the device Scope of delivery • Display and operating module 96 x 96 mm (3.78 x 3.78 in) •...
  • Page 20: Mounting The Sensors

    Installation Prosonic S FMU90 HART Mounting the sensors Further information and the documentation currently available can be found on the Endress+Hauser website: www.endress.com → Downloads. Sensor documentation: • TI01469F (FDU90) • TI01470F (FDU91) • TI01471F (FDU91F) • TI01472F (FDU92) • TI01473F (FDU93) •...
  • Page 21: Electrical Connection

    Prosonic S FMU90 HART Electrical connection Electrical connection Connection conditions 6.1.1 Cable specification • Conductor cross-section: 0.2 to 2.5 mm (26 to 14 AWG) • Wire sleeve cross-section: 0.25 to 2.5 mm (24 to 14 AWG) • Min. stripping length: 10 mm (0.39 in) Connecting the device 6.2.1...
  • Page 22 Electrical connection Prosonic S FMU90 HART Cable entries Precut openings on the bottom of the housing for the following cable entries: • M20x1.5 (10 openings) • M16x1.5 (5 openings) • M25x1.5 (1 opening) Use a suitable tool to cut out the openings.
  • Page 23 Prosonic S FMU90 HART Electrical connection Access to terminal compartment A0034897  19 Access to terminal compartment: single DIN rail housing unit A0034898  20 Access to terminal compartment: several DIN rail housing units mounted side by side 6.2.4 Terminal assignment Terminal type Prosonic S has plug-in spring terminals.
  • Page 24 Electrical connection Prosonic S FMU90 HART Terminal areas • Basic terminal area (A) Found on all device versions • Terminal area for additional inputs and outputs (B) Found on the following device versions: • FMU90 - *****2****** • FMU90 - *******2**** •...
  • Page 25 Prosonic S FMU90 HART Electrical connection Terminals for analog outputs Terminal area A Terminals 4, 5: analog output 1 (0/4 to 20mA, HART) Terminal area B Terminals 41, 42: analog output 2 (0/4 to 20mA) Terminals for relays Terminal area A...
  • Page 26: Special Connection Instructions

    Electrical connection Prosonic S FMU90 HART Other elements on the terminal areas Terminal area A • Display Connection of the display or the remote display and operating module • Service Service interface; for connection of a PC/notebook via Commubox FXA291 •...
  • Page 27 Prosonic S FMU90 HART Electrical connection Connection of the power supply in the aluminum field housing Valid for: Order code 030 (housing, material) Option 3 (aluminum field mounting, IP66 NEMA4x) WARNING Shock Hazard and Explosion Hazard ‣ Connect the aluminum field housing to the potential earth (PE) and/or the local ground potential (PML) via the protective ground terminal.
  • Page 28 Electrical connection Prosonic S FMU90 HART Sync Service Fuse Display HART 0/4…20mA FDU- Sensor Relay 90 … 253 VAC 10.5 … 32 VDC A0035932  24 Connection of the power supply in the DIN rail housing Metal DIN rail in cabinet...
  • Page 29 Prosonic S FMU90 HART Electrical connection NOTICE The evaluation electronics and their direct connections (display/service connector, service interface etc.) are galvanically isolated from the power supply and the communication signals, and are connected to the potential of the sensor electronics.
  • Page 30 Electrical connection Prosonic S FMU90 HART Connection diagram for FDU9x → FMU90 FDU90/91/92 FDU90/91 ≤30 m (98 ft) BN BU ≤300 m (984 ft) YE BK RD YE BK RD 24 VDC FMU90/95 FMU90/95 FDU91F/93/95 FDU91F/93/95 ≤30 m (98 ft)
  • Page 31 Prosonic S FMU90 HART Electrical connection Valid for the following sensors • FDU91F • FDU93 • FDU95 These sensors are no longer available but can be connected to the Prosonic S in existing installations. • FDU96 • FDU83 • FDU84 •...
  • Page 32 Electrical connection Prosonic S FMU90 HART Sync Service Fuse Display HART 0/4…20mA FDU- Sensor Relay FDU91F/93/95/96 (FDU83/84/85/86) 90 … 253 VAC 10 5 … 32 VDC A0033333  27 Potential equalization of metallic sensors in aluminum field housing Potential equalization in the field housing; wired on delivery...
  • Page 33 Prosonic S FMU90 HART Electrical connection Sync Service Fuse Display HART 0/4…20mA FDU- Sensor Relay GNYE FDU91F/93/95/96 (FDU83/84/85/86) PE PE 90 … 253 VAC 10.5 … 32 VDC A0032584  28 Potential equalization of metallic sensors in DIN rail housing...
  • Page 34 Electrical connection Prosonic S FMU90 HART 6.3.4 Shortening the sensor cable NOTICE Damaged wires or no return conductor may cause malfunctions ‣ Do not damage the wires when removing the insulation. ‣ After shortening the cable, twist the shielding metal braiding and connect it to the "BK"...
  • Page 35 Prosonic S FMU90 HART Electrical connection Technical data for sensor heater • Supply voltage 24 V ±10 % • Residual ripple < 100 mV • Current consumption 250 mA per sensor Temperature compensation with sensor heater If the sensor heater is used, connect an external temperature sensor to correct the sound time-of-flight and assign this temperature sensor to the sensor.
  • Page 36 Electrical connection Prosonic S FMU90 HART WARNING Explosion Hazard ‣ Install the power supply unit outside the hazardous area. ‣ Use a cable that meets the requirements of the zone in which the aluminum field housing is installed. ‣ Connect the sensor heater inside the aluminum field housing (or another explosion- proof housing) to the power supply.
  • Page 37 Prosonic S FMU90 HART Electrical connection FMU90 Sync Service Fuse Display HART 0/4…20mA FDU- Sensor Relay FDU90 FDU91 24 VDC A0032575  32 Connection of the sensor heater via a metal DIN rail in the cabinet External power supply unit...
  • Page 38 Electrical connection Prosonic S FMU90 HART Cable specification for synchronization • Max. length 10 m (33 ft) between the individual transmitters • Cross-section 2 x 0.75 to 2.5 mm (18 to 14 AWG) • Cable shield Required for cables > 1 m (3.3 ft); ground the shield.
  • Page 39 Prosonic S FMU90 HART Electrical connection FMU90 FMU90 FMU90 (24 V) (24 V) (24 V) 24 V A0034904  35 Connection of external switches Liquiphant connection Connection of external switches (passive) Connection of external switches (active) Inputs for external switches •...
  • Page 40 Electrical connection Prosonic S FMU90 HART 84 85 FMU90 Pt100 Pt100 A0034905  36 Connection of a Pt100 temperature sensor Pt100 with 3-wire connection Pt100 with 4-wire connection (one connector is not used) The use of a 2-wire connection is not permitted due to insufficient measuring accuracy.
  • Page 41 Prosonic S FMU90 HART Electrical connection Connection of the Omnigrad S TR61 temperature sensor in hazardous areas FMU90 83 84 FMU90 83 84 ↑↑ ↑↑ A0033403  38 Connection of the Omnigrad S TR61 in hazardous areas Temperature sensor in hazardous area...
  • Page 42 Electrical connection Prosonic S FMU90 HART Sync Service Fuse Display HART 0/4…20mA FDU- Sensor Relay A0034903  39 Connection of the remote display and operating module Pre-terminated connecting cable 3 m (9.8 ft) with display plug (supplied) Minimum diameter for cable entry 20 mm (0.79 in)
  • Page 43: Operating Options

    Prosonic S FMU90 HART Operating options Operating options Structure and function of the operating menu 7.1.1 Submenus and parameter sets Parameters that belong together are grouped into one parameter set in the operating menu. Each parameter set is identified by a five-digit code.
  • Page 44: Access To The Operating Menu Via The Local Display

    Operating options Prosonic S FMU90 HART Access to the operating menu via the local display 7.2.1 Display and operating elements Elements of the display and operating module A0034921 Soft key symbols Keys Light emitting diodes to indicate the relay switching states...
  • Page 45 Prosonic S FMU90 HART Operating options Scroll symbols Scroll list available Is displayed if the picklist contains more options than can be shown on the display. All the options in the list can be displayed by pressing repeatedly. Navigation in the envelope curve display (select the "Cyclic" display format) •...
  • Page 46 Operating options Prosonic S FMU90 HART • • Opens the list of errors which are currently detected. • If a warning is present, the symbol flashes. • If an alarm is present, the symbol is displayed permanently. • Displays the next page of measured values (only available if several pages of measured values have been defined;...
  • Page 47 Prosonic S FMU90 HART Operating options 7.2.2 Calling the operating menu from a standard screen (measured value display) • Left button ("Info") : shortcut menu Provides fast access to the most important parameters: • Daily counter • Tag marking • Envelope curve •...
  • Page 48: System Integration

    System integration Prosonic S FMU90 HART System integration Ω I : 4...20 mA + HART A0034891  45 HART system integration PLC, API Commubox FXA195 (USB), HART protocol DeviceCare/FieldCare Commubox FXA291 (service interface) Display and operating module on Prosonic S (if available)
  • Page 49: Commissioning

    Prosonic S FMU90 HART Commissioning Commissioning Preparatory steps 9.1.1 Resetting to factory settings (Reset) NOTICE A reset may negatively impact the measurement. ‣ Perform a new basic setup after resetting the device. Using the reset function It is always advisable to reset the device if you want to use a device with an unknown history.
  • Page 50: Configuring The Measuring Device

    Commissioning Prosonic S FMU90 HART Configuring the measuring device 9.3.1 Parameter set "LVL N sensor sel." Navigation Level → Level (LVL) N → Basic setup → LVL N sensor sel. Parameter • Input Assign a sensor to the channel. • Sensor selection Specify the sensor type.
  • Page 51 Prosonic S FMU90 HART Commissioning 9.3.3 Parameter set "LVL N empty cal." 100% A0034882  47 Empty and full calibration for level measurement FDU9x sensor FMU90/FMU95 transmitter BD Blocking distance Distance between sensor membrane and product surface Empty E Full F...
  • Page 52 Commissioning Prosonic S FMU90 HART Parameter • Unit level Select the level unit. The level is output in this unit if linearization is not performed. • Level N Displays the level F currently measured (from the zero point to the surface of the product) in the selected unit.
  • Page 53 Prosonic S FMU90 HART Commissioning 9.3.6 Parameter set "LVL N Linearisat." 100% 100% 100% 100% 100% A0021476  48 Types of linearization None Table Pyramid bottom Conical bottom Angled bottom Sphere Horizontal cylindrical Intermediate height Navigation Level → Level (LVL) N → Basic setup → LVL N Linearisat.
  • Page 54 Commissioning Prosonic S FMU90 HART • Edit Only displayed if Type = Table. Opens the Edit parameter set to enter the linearization table. • Status table Activates or deactivates the linearization table. • Mode Specifies whether the linearization refers to the level or the ullage.
  • Page 55 Prosonic S FMU90 HART Commissioning 9.3.8 Parameter set "Check value" • This parameter set starts inference echo suppression (mapping). • To record all the interference echoes, perform mapping at the minimum level possible (ideally with an empty vessel). • If it is not possible to empty the vessel during commissioning, record preliminary mapping when the vessel is partially filled.
  • Page 56: Advanced Settings

    Commissioning Prosonic S FMU90 HART 9.3.9 Parameter set "LVL N dist. map." Navigation Level → Level (LVL) N → Basic setup → LVL N dist. map. Parameter • Actual distance Displays the distance D currently measured between the sensor membrane and the surface of the product.
  • Page 57 Prosonic S FMU90 HART Commissioning FMU90 A0035948  50 Use of the flooding protection tube for FDU90 Blocking distance FDU90: 70 mm (2.8 in) Safety distance to be entered: 40 mm (1.6 in) Enter 40 mm (1.6 in). With this setting, the safety distance ends just below the flooding protection tube.
  • Page 58 Commissioning Prosonic S FMU90 HART A0036766  53 "Type" = "value max size". The different values are displayed cyclically in maximum size. A0036767  54 "Type" = "alter.3x2 val.". Up to six values can be displayed. These values are spread over three pages with two values on each.
  • Page 59 Prosonic S FMU90 HART Commissioning 2. Specify the time after which the onsite display returns to home (measured value display). 9.4.3 Configuring the limit value relay Limit type = "Standard" or "Tendency/speed" A0036325  55 Parameters for "Limit type" = "Standard" or "Tendency/speed"...
  • Page 60 Commissioning Prosonic S FMU90 HART Limit type = "Inband" or "Out of band" A0036324  56 Parameters for "Limit type" = "Inband" or "Out of band" "Limit type" = "Inband" "Limit type" = "Out of band" Upper switchpt. Lower switchpt.
  • Page 61 Prosonic S FMU90 HART Commissioning 12. In the Switch delay parameter, specify the switch delay for the relay.  The relay only switches when the limit value has been exceeded for the length of time specified here. 13. In the Invert parameter, specify whether the switching direction of the relay is to be inverted in relation to the defined behavior.
  • Page 62 Commissioning Prosonic S FMU90 HART A0036679  57 Switch-on point and switch-off point for limit control Pump empties a vessel: switch-on point > switch-off point Pump fills a vessel: switch-off point > switch-on point Switch-on point Switch-off point Set the Switch-on point and Switch-off point parameters according to the diagram above.
  • Page 63 Prosonic S FMU90 HART Commissioning A0036678  58 Effect of "Backlash interval" and "Backlash time" Switch-on point Switch-off point Pump on Pump off Backlash interval Backlash time If, for example, you want to empty a pump chamber at regular intervals for a period...
  • Page 64 Commissioning Prosonic S FMU90 HART Configuration of the pump control system (function: Pump rate control) P1+P2 A0036677  59 Operating principle of pump rate control Switch-on point Switch-off point Pump on Pump off Hook up interval Switch on border Min. pump rate/min 1.
  • Page 65 Prosonic S FMU90 HART Commissioning 8. In the Switch on border parameter, specify the limit level for switching on an additional pump.  If the distance between the current level and the switch-off point is smaller than the switch-on border, no additional pumps are switched on even if the desired pump rate has not yet been reached.
  • Page 66 Commissioning Prosonic S FMU90 HART 16. In the Relay K → Function parameter, select the Pump M/control N option.  Pump M is now controlled via relay K. 17. In the Invert parameter, specify whether the switching direction of the relay should be inverted in relation to the defined behavior.
  • Page 67 Prosonic S FMU90 HART Commissioning A0036679  61 Switch-on point and switch-off point for limit control Pump empties a vessel: switch-on point > switch-off point Pump fills a vessel: switch-off point > switch-on point Switch-on point Switch-off point Set the Switch-on point and Switch-off point parameters according to the diagram above.
  • Page 68 Commissioning Prosonic S FMU90 HART A0036678  62 Effect of "Backlash interval" and "Backlash time" Switch-on point Switch-off point Pump on Pump off Backlash interval Backlash time If, for example, you want to empty a pump chamber at regular intervals for a period...
  • Page 69 Prosonic S FMU90 HART Commissioning Configuration of the pump control system (function: Pump rate control) P1+P2 A0036677  63 Operating principle of pump rate control Switch-on point Switch-off point Pump on Pump off Hook up interval Switch on border Min. pump rate/min 1.
  • Page 70 Commissioning Prosonic S FMU90 HART 8. In the Switch-on point and Switch-off point parameters, specify the switch points for pump rate control. 9. In the Min. pump rate parameter, specify the desired minimum pump rate. (Positive values: filling, negative values: emptying).
  • Page 71 Prosonic S FMU90 HART Commissioning A0036678  64 Effect of "Backlash interval" and "Backlash time" Switch-on point Switch-off point Pump on Pump off Backlash interval Backlash time If, for example, you want to empty a pump chamber at regular intervals for a period...
  • Page 72 Commissioning Prosonic S FMU90 HART 9.4.7 Configuring rake control Operating principle of the rake control function A0036428  65 Operating principle of the rake control function • The rake control function uses two levels, namely L and L . If the downstream level L...
  • Page 73 In the Current span parameter, select the current range to which the measured value (0 % to 100 %) will be mapped. If the Fix. current option is selected, the measured value is only transmitted via the HART signal. 3. For Current span = Fix. current HART: In the mA value parameter, specify the value of the fixed current.
  • Page 74 9.4.9 Configuring the HART signal This section only applies to current output 1. The first HART variable (PV) always corresponds to the measured value which is also assigned to the current. The other HART variables can be defined in the HART settings submenu.
  • Page 75: Simulation

    For addresses 1 - 15, the output current is constant. The measured value is then only output via the HART signal. 3. In the No. of preambles parameter, specify the number of preambles for the HART protocol. 4. In the Measured value N parameter (N = 2 - 4), specify which measured value is output via the HART variable.
  • Page 76 Commissioning Prosonic S FMU90 HART 9.6.2 Keypad lock Locking ‣ Press all three keys simultaneously.  The device is locked; no entries can be made. The symbol appears on the display. Unlocking ‣ If an attempt is made to change a parameter, the device jumps to Password/reset.
  • Page 77 Prosonic S FMU90 HART Commissioning Display options • Unlocked All parameters (apart from Service parameters) can be edited. • Code locked The device has been locked via the operating menu. It can only be unlocked again by entering the access code in the Device settings → Password/reset → Code parameter.
  • Page 78: Diagnostics And Troubleshooting

    Diagnostics and troubleshooting Prosonic S FMU90 HART Diagnostics and troubleshooting 10.1 General troubleshooting 10.1.1 Calibration error Measured value incorrect Check the Actual distance parameter. • The Actual distance is incorrect: • For measurements in a bypass or ultrasound guide pipe: Set the appropriate option in the LVL N appl.
  • Page 79 Prosonic S FMU90 HART Diagnostics and troubleshooting 3. Select which type of curve is to be displayed: envelope curve, floating average curve (FAC), mapping curve. 4. Select the display format: single curve or cyclic.  The envelope curve display now appears: A0036421 ...
  • Page 80 Diagnostics and troubleshooting Prosonic S FMU90 HART Envelope curve display in FieldCare/DeviceCare A0036420 1. Click F (functions) on the menu bar. 2. Select the sensor whose envelope curve is to be displayed. 3. To display a single curve, click the Read curve button.
  • Page 81: Overview Of Diagnostic Information

    Prosonic S FMU90 HART Diagnostics and troubleshooting 10.2 Overview of diagnostic information 10.2.1 Error signal Displaying errors that occur during commissioning or operation: • Onsite display: • Error symbol • Error code • Error description • Current output, depends on the Output on alarm → Output N parameter: •...
  • Page 82 Diagnostics and troubleshooting Prosonic S FMU90 HART List of error codes • A 00 100 Software version does not suit hardware version. • A 00 101 Checksum error → Total reset and recalibration • A 00 102 Checksum error → Total reset and recalibration • W 00 103 Initializing - please wait →...
  • Page 83 Prosonic S FMU90 HART Diagnostics and troubleshooting • A 00 250 Faulty external temperature sensor → Check temperature sensor. • A 0x 281 Temperature readings sensor 01 or 02 defect - check connection → Check that the sensor is connected correctly. • W 0x 501 No sensor selected for input 01 or 02 →...
  • Page 84: Firmware History

    Diagnostics and troubleshooting Prosonic S FMU90 HART • W 0x 70y Operating hours alarm pump y PST x → Reset operating hours (Op.hour alarm submenu). • W 0x 71y Failure pump y PST x → Check pump 1. After rectifying the pump error, reset the pump controller or switch the device off and on again.
  • Page 85 Prosonic S FMU90 HART Diagnostics and troubleshooting • V01.02.03 (05.2011) Improved temperature plausibility; flow counter limit; troubleshooting BA00288F/00/en/07.09 • V01.02.05 (08.2014) Continuous improvement BA00288F/00/en/13.12 • V01.02.06 (04.2016) Continuous improvement BA00288F/00/en/14.17 Endress+Hauser...
  • Page 86: Maintenance

    Maintenance Prosonic S FMU90 HART Maintenance No special maintenance work is required. 11.1 Exterior cleaning When cleaning the exterior, always use cleaning agents that do not corrode the surface of the housing and the seals. Endress+Hauser...
  • Page 87: Repair

    Prosonic S FMU90 HART Repair Repair 12.1 General information 12.1.1 The Endress+Hauser repair concept Under the Endress+Hauser repair concept, the measuring devices have a modular design and customers are able to undertake repairs themselves. For more information on service and spare parts, please contact your Endress+Hauser sales representative.
  • Page 88: Disposal

    Repair Prosonic S FMU90 HART 2. Return the device if repairs or a factory calibration are required, or if the wrong device was ordered or delivered. 12.4 Disposal Observe the following notes during disposal: • Observe valid federal/national regulations. • Ensure proper separation and reuse of the device components.
  • Page 89: Accessories

    Accessories 13.1 Communication-specific accessories 13.1.1 Commubox FXA195 HART • For intrinsically safe HART communication with FieldCare or DeviceCare via the USB interface • Additional information: Technical Information TI00404F 13.1.2 Commubox FXA291 • Connects the CDI interface (Common Data Interface) of Endress+Hauser devices with the USB port of a computer.
  • Page 90 Accessories Prosonic S FMU90 HART 13.2.2 Mounting plate for polycarbonate field housing A0034923  73 Mounting plate for polycarbonate field housing • Compatible with the Prosonic S housing bracket • Pipe diameter: 25 to 50 mm (1 to 2 in) •...
  • Page 91 Prosonic S FMU90 HART Accessories Material 316L (1.4404) Order number 71452327 Mounting frame, long 3.2 (0.13) 60 (2.36) ø33.7 (1.3) 4 (0.16) 20 (0.8) 55 (2.17) 109 (4.29) (3.94) 130 (5.12) 150 (5.91) A0037800  75 Dimensions of mounting frame, long. Unit of measurement mm (in) Weight: 4.9 kg (10.08 lb)
  • Page 92 Accessories Prosonic S FMU90 HART 13.2.3 Adapter plate for remote display A0035916  76 Use of adapter plate Remote display of Prosonic S FMU9x with adapter plate Installation opening of the remote display of the FMU86x predecessor transmitter To mount the remote display of the Prosonic S FMU9x in the housing of the larger remote display of the FMU86x predecessor •...
  • Page 93 Prosonic S FMU90 HART Accessories FDU95 • Cable type: Li2G2G 2x(0.75)D+1x0.75 • Material: silicone • Ambient temperature:–40 to +150 °C (–40 to +302 °F) • Order number: 71027745 13.2.6 Temperature sensor Omnigrad S TR61 125 (4.92) 28 (1.1) 78 (3.01) A0035035 ...
  • Page 94: Operating Menu

    Operating menu Prosonic S FMU90 HART Operating menu 14.1 Menu "Level → Level (LVL N)" 14.1.1 Submenu "Basic setup" Parameter set L1003 "LVL N sensor sel." • Input • Sensor selection • Detected Parameter set L1004 "LVL N appl. param."...
  • Page 95: Menu "Safety Settings

    Prosonic S FMU90 HART Operating menu Parameter set L1017 "LVL N check value" Correction Parameter set L1018 "LVL N correction" Offset Parameter set L1020 "LVL N blocking distance" Blocking distance Parameter set L1019 "LVL N limitation" • Limitation • Upper limit •...
  • Page 96: Menu "Relay/Controls

    Operating menu Prosonic S FMU90 HART 14.3 Menu "Relay/controls" 14.3.1 Submenu "Pump control N" (standard - limit control) Valid for: • FMU90-*1********** • FMU90-*2********** Parameter set R1300 "Pump control N" • Reference • Number of pumps Parameter set R1301 "Pump control N"...
  • Page 97 Prosonic S FMU90 HART Operating menu Parameter set R13A6 "Relay allocation → Relay K" • Function • Invert 14.3.3 Submenu "Pump control N → Basic setup" (extended - limit control) Valid for: • FMU90-*3********** • FMU90-*4********** Navigation to the submenu: Relay/controls →...
  • Page 98 Operating menu Prosonic S FMU90 HART Parameter set R1401 "Pump control N" • Reference • Number of pumps • Standby pump • Reset Parameter set R1402 "Pump control N" • Function = Pump rat. contr. • Load control Parameter set R1504 "Pump control N"...
  • Page 99 Prosonic S FMU90 HART Operating menu Parameter set R1602 "Function test N" • Function test • Max. downtime • Max. test time • Switch-on point • Switch-off point 14.3.7 Submenu "Pump control N → Flush control" Valid for: • FMU90-*3********** •...
  • Page 100 Operating menu Prosonic S FMU90 HART • Backlash starts • Reset backlstart • Last run time 14.3.10 Submenu "Pump control N → Op. hours alarm" Valid for: • FMU90-*3********** • FMU90-*4********** Navigation to the submenu: Relay/controls → Pump control N → Op. hours alarm Parameter set R1612 "Op.
  • Page 101 Prosonic S FMU90 HART Operating menu 14.3.13 Submenu "Relay configurat. → Relay N" (function: limit) Parameter set R1203 "Relay N" • Function → Limit → Limit XXX • Limit type • Switch-on point • Switch-off point • Switch on/min. • Switch off/min.
  • Page 102: Menu "Output/Calculat. → Current Output N

    Only for current output 1 Parameter set O1203 "HART settings" • HART address • No. of preambles • Short TAG HART Parameter set O2205/O3206/O4207 "Add. HART value M" • Measured value M • Output damping M 14.4.4 Submenu "Simulation" Parameter set O1204 "Current output N"...
  • Page 103: Menu "System Informat

    Prosonic S FMU90 HART Operating menu 14.5.2 Submenu "Tag marking" Parameter set D1102 "Tag marking" • Output N • Device marking 14.5.3 Submenu "Language" Parameter set D1103 "Language" Language 14.5.4 Submenu "Password/reset" Parameter set D1104 "Password/reset" • Reset • Code •...
  • Page 104 Operating menu Prosonic S FMU90 HART 14.6.3 Submenu "Trend display → Trend output N" Parameter set IX10F Trend output N Time interval 14.6.4 Submenu "Min/max values" Parameter set IX302 "Level → Level (LVL) N" • Max. value • Min. Value •...
  • Page 105: Menu "Display

    Prosonic S FMU90 HART Operating menu 14.7 Menu "Display" Parameter set DX202 "Display" • Type • Value N • Customized text N Parameter set DX201 "Display format" • Format • No. of decimals • Sep. character • Customized text Parameter set DX200 "Back to home"...
  • Page 106: Menu "Sensor Management

    Operating menu Prosonic S FMU90 HART 14.8 Menu "Sensor management" 14.8.1 Submenu "Sensor management → FDU sensor → Sensor management" Parameter set D1019 "Input" FDU sensor N Parameter set D1106 "US sensor N" • Sensor operation • Sensor priority • Detected •...
  • Page 108 *71494895* 71494895 www.addresses.endress.com...