Document information Proline Promag 400 HART Document information Document function The document is part of the Operating Instructions and serves as a reference for parameters, providing a detailed explanation of each individual parameter of the Expert operating menu. Target group The document is aimed at specialists who work with the device over the entire life cycle and perform specific configurations.
Page 5
Proline Promag 400 HART Document information Language Language Operation Parameter 1 Parameter n Submenu 1 Submenu n Device tag Setup Wizard 1/Parameter 1 Wizard n/Parameter n Advanced setup Parameter 1 Parameter n Submenu 1 Submenu n Diagnostics Parameter 1 Parameter n...
Document information Proline Promag 400 HART 1.3.2 Structure of a parameter description The individual parts of a parameter description are described in the following section: Complete parameter name Write-protected parameter = Navigation Navigation path to the parameter via the local display (direct access code) or Web browser...
Proline Promag 400 HART Document information 1.4.2 Symbols in graphics Symbol Meaning Symbol Meaning 1, 2, 3 ... Item numbers A, B, C, ... Views A-A, B-B, C-C, ... Sections Endress+Hauser...
Overview of the Expert operating menu Proline Promag 400 HART Overview of the Expert operating menu The following table provides an overview of the menu structure of the expert operating menu and its parameters. The page reference indicates where the associated description of the submenu or parameter can be found.
Page 9
Proline Promag 400 HART Overview of the Expert operating menu ‣ Communication → 103 ‣ HART input → 103 ‣ HART output → 108 ‣ Web server → 123 ‣ Diagnostic configuration → 126 ‣...
Description of device parameters Proline Promag 400 HART Description of device parameters In the following section, the parameters are listed according to the menu structure of the local display. Specific parameters for the operating tools are included at the appropriate points in the menu structure.
Page 11
Proline Promag 400 HART Description of device parameters Additional information User entry The direct access code consists of a 4-digit number and the channel number, which identifies the channel of a process variable: e.g. 0914-1 • The leading zeros in the direct access code do not have to be entered.
Page 12
Description of device parameters Proline Promag 400 HART Access status display Navigation Expert → Access stat.disp (0091) Prerequisite A local display is provided. Description Displays the access authorization to the parameters via the local display. User interface • Operator •...
Proline Promag 400 HART Description of device parameters Display Information on access authorization is provided in the "User roles and associated access authorization" and "Operating concept" sections of the Operations Instructions for the device. Enter access code Navigation Expert → Ent. access code (0003)
Page 14
Description of device parameters Proline Promag 400 HART Value 2 display (0108) → 19 Decimal places 2 (0117) → 20 Value 3 display (0110) → 20 0% bargraph value 3 (0124) → 21 100% bargraph value 3 (0126) →...
Page 15
Proline Promag 400 HART Description of device parameters • Portuguesa • Polski • русский язык (Russian) • Svenska • Türkçe • 中文 (Chinese) • 日本語 (Japanese) • 한국어 (Korean) • ( ا ل ْ ع َ ر َب ي ّةArabic) •...
Page 16
Description of device parameters Proline Promag 400 HART appears in the header of the display (). The reading of the Custody transfer counter parameter (→ 148) is displayed in alternation with the information of the totalizer. For detailed information on custody transfer mode, see the Special Documentation for the device.
Page 17
Proline Promag 400 HART Description of device parameters Value 1 display Navigation Expert → System → Display → Value 1 display (0107) Prerequisite A local display is provided. Description Use this function to select one of the measured values to be shown on the local display.
Page 18
Description of device parameters Proline Promag 400 HART Factory setting Country-specific: • 0 l/h • 0 gal/min (us) Additional information Description The Format display parameter (→ 15) is used to specify that the measured value is to be displayed as a bar graph.
Page 19
Proline Promag 400 HART Description of device parameters Additional information Description This setting does not affect the measuring or computational accuracy of the device. The arrow displayed between the measured value and the unit indicates that the device computes with more digits than are shown on the local display.
Page 20
Description of device parameters Proline Promag 400 HART Decimal places 2 Navigation Expert → System → Display → Decimal places 2 (0117) Prerequisite A measured value is specified in the Value 2 display parameter (→ 19). Description Use this function to select the number of decimal places for measured value 2.
Page 21
Proline Promag 400 HART Description of device parameters 0% bargraph value 3 Navigation Expert → System → Display → 0% bargraph 3 (0124) Prerequisite A selection has been made in the Value 3 display parameter (→ 20).
Page 22
Description of device parameters Proline Promag 400 HART Decimal places 3 Navigation Expert → System → Display → Decimal places 3 (0118) Prerequisite A measured value is specified in the Value 3 display parameter (→ 20). Description Use this function to select the number of decimal places for measured value 3.
Page 23
Proline Promag 400 HART Description of device parameters Decimal places 4 Navigation Expert → System → Display → Decimal places 4 (0119) Prerequisite A measured value is specified in the Value 4 display parameter (→ 22). Description Use this function to select the number of decimal places for measured value 4.
Page 24
Description of device parameters Proline Promag 400 HART Display damping Navigation Expert → System → Display → Display damping (0094) Prerequisite A local display is provided. Description Use this function to enter the reaction time of the local display to fluctuations in the measured value caused by process conditions.
Page 25
Proline Promag 400 HART Description of device parameters Header text Navigation Expert → System → Display → Header text (0112) Prerequisite The Free text option is selected in the Header parameter (→ 24). Description Use this function to enter a customer-specific text for the header of the local display.
Page 26
Description of device parameters Proline Promag 400 HART Description Use this function to enter a value to adapt the display contrast to the ambient conditions (e.g. the lighting or viewing angle). User entry 20 to 80 % Factory setting 50 %...
Proline Promag 400 HART Description of device parameters Display Information on access authorization is provided in the "User roles and associated access authorization" and "Operating concept" sections of the Operations Instructions for the device. 3.1.2 "Diagnostic handling" submenu Navigation Expert → System → Diagn. handling ‣...
Page 28
Description of device parameters Proline Promag 400 HART "Diagnostic behavior" submenu For a list of all the diagnostic events, see the Operating Instructions for the device. Modifying the diagnostic behavior of a diagnostic event. Each diagnostic event is assigned a certain diagnostic behavior at the factory. The user can change this assignment for certain diagnostics events.
Proline Promag 400 HART Description of device parameters Assign behavior of diagnostic no. 441 (Current output 1) Navigation Expert → System → Diagn. handling → Diagn. behavior → Diagnostic no. 441 (0657) Description Use this function to change the diagnostic behavior of the diagnostic message 441 Current output 1.
Proline Promag 400 HART Description of device parameters Selection • Off • Alarm • Warning • Logbook entry only Factory setting Warning Additional information For a detailed description of the options available, see → 28 Assign behavior of diagnostic no. 862 (Empty pipe) ...
Description of device parameters Proline Promag 400 HART Assign behavior of diagnostic no. 302 (Device verification active) Navigation Expert → System → Diagn. handling → Diagn. behavior → Diagnostic no. 302 (0739) Description Use this function to change the diagnostic behavior of the diagnostic message 302 Device verification active.
Page 33
Proline Promag 400 HART Description of device parameters Define access code Navigation Expert → System → Administration → Def. access code → Def. access code Description Use this function to enter a user-specific release code to restrict write-access to the parameters.
Page 34
Description of device parameters Proline Promag 400 HART Additional parameters in the "Administration" submenu Define access code Navigation Expert → System → Administration → Def. access code Description Use this function to enter a user-specific release code to restrict write-access to the parameters.
Page 35
Proline Promag 400 HART Description of device parameters "Restart device" option The restart resets every parameter whose data are in the volatile memory (RAM) to the factory setting (e.g. measured value data). The device configuration remains unchanged. Activate SW option ...
"Extended HistoROM" option Order code for "Application package", option EA "Extended HistoROM" "PFS output 2 + status input" option Order code for "Output; input", option I "4-20mA HART, 2x pul./freq./switch output; status input" "Certified pulse output" option Only available for Promag W.
Page 38
Description of device parameters Proline Promag 400 HART Additional information Dependency The unit is taken from the Mass flow unit parameter (→ 47) Conductivity Navigation Expert → Sensor → Measured val. → Process variab. → Conductivity (1850) Prerequisite In the Conductivity measurement parameter (→...
Page 39
Proline Promag 400 HART Description of device parameters Additional information Description As it is only possible to display a maximum of 7 digits, the current counter value is the sum of the totalizer value and the overflow value from the Totalizer overflow 1 to 3 parameter if the display range is exceeded.
Page 40
Expert → Sensor → Measured val. → Input values → Val. status inp. (1353) Prerequisite For the following order code: • "Output; input", option I "4-20mA HART, 2x pul./freq./switch output; status input" • "Output; input", option J "4-20mA HART, certified pulse output, switch output; status input" Description Displays the current input signal level.
Page 41
Proline Promag 400 HART Description of device parameters Output current 1 Navigation Expert → Sensor → Measured val. → Output values → Output curr. 1 (0361–1) Description Displays the current value currently calculated for the current output. User interface 0 to 22.5 mA...
Page 42
Description of device parameters Proline Promag 400 HART A0025816-EN Non-conductive Conductive NC Normally closed NO Normally opened The output behavior can be reversed via the Invert output signal parameter (→ 102) i.e. the transistor does not conduct for the duration of the pulse.
Proline Promag 400 HART Description of device parameters Additional information Selection • Open The switch output is not conductive. • Closed The switch output is conductive. 3.2.2 "System units" submenu Navigation Expert → Sensor → System units ‣ System units Volume flow unit (0553) →...
Page 44
Description of device parameters Proline Promag 400 HART Selection SI units US units Imperial units • cm³/s • af/s • gal/s (imp) • cm³/min • af/min • gal/min (imp) • cm³/h • af/h • gal/h (imp) • cm³/d • af/d •...
Page 45
Proline Promag 400 HART Description of device parameters Customer-specific units The unit for the customer-specific volume is specified in the User volume text parameter (→ 50). Volume unit Navigation Expert → Sensor → System units → Volume unit (0563) Description Use this function to select the unit for the volume.
Page 46
Description of device parameters Proline Promag 400 HART Selection SI units • nS/cm • µS/cm • µS/m • µS/mm • mS/m • mS/cm • S/cm • S/m • kS/m • MS/m Factory setting µS/cm Additional information Result The selected unit applies for: Conductivity parameter (→...
Page 47
Proline Promag 400 HART Description of device parameters Mass flow unit Navigation Expert → Sensor → System units → Mass flow unit (0554) Description Use this function to select the unit for the mass flow. Selection SI units US units •...
Page 48
Description of device parameters Proline Promag 400 HART Selection SI units US units • g • oz • kg • lb • t • STon Custom-specific units User mass Factory setting Country-specific: • kg • lb Additional information Selection For an explanation of the abbreviated units: → 170...
Page 49
Proline Promag 400 HART Description of device parameters Selection • SD = specific density The specific density is the ratio of the density of the fluid to the density of water at a water temperature of +4 °C (+39 °F), +15 °C (+59 °F), +20 °C (+68 °F).
Description of device parameters Proline Promag 400 HART User volume text Navigation Expert → Sensor → System units → User-spec. units → Volume text (0567) Description Use this function to enter a text for the user-specific unit of volume and volume flow. The corresponding time units (s, min, h, d) for volume flow are generated automatically.
Proline Promag 400 HART Description of device parameters Factory setting User mass text Navigation Expert → Sensor → System units → User-spec. units → Mass text (0560) Description Use this function to enter a text for the user-specific unit of mass and mass flow. The corresponding time units (s, min, h, d) for mass flow are generated automatically.
Description of device parameters Proline Promag 400 HART User mass factor Navigation Expert → Sensor → System units → User-spec. units → Mass factor (0561) Description Use this function to enter a quantity factor (without time) for the user-specific mass and mass flow unit.
Page 53
Proline Promag 400 HART Description of device parameters Factory setting Standard CIP off Additional information Description The user can choose from a range of filter combinations which can optimize the measurement result depending on the application. Each change in the filter setting affects the output signal of the measuring device.
Page 54
Description of device parameters Proline Promag 400 HART Flow damping Navigation Expert → Sensor → Process param. → Flow damping (6661) Description Use this function to enter flow damping. Reduction of the variability of the flow measured value (in relation to interference). For this purpose, the depth of the flow filter is adjusted: when the filter setting increases, the reaction time of the device also increases.
Page 55
Proline Promag 400 HART Description of device parameters Conductivity damping Navigation Expert → Sensor → Process param. → Conduct. damping (1803) Prerequisite In the Conductivity measurement parameter (→ 55), the On option is selected. Description Use this function to enter the time constant for conductivity damping.
Page 56
Description of device parameters Proline Promag 400 HART Assign process variable Navigation Expert → Sensor → Process param. → Low flow cut off → Assign variable (1837) Description Use this function to select the process variable for low flow cutoff detection.
Page 57
Proline Promag 400 HART Description of device parameters Additional information Example A0012887 Flow Time Hysteresis Low flow cut off active Low flow cut off is activated Low flow cut off is deactivated On value entered Off value entered Pressure shock suppression ...
Page 58
Description of device parameters Proline Promag 400 HART A0012888 Flow Time Drip Pressure shock Pressure shock suppression active as specified by the time entered Pressure shock suppression inactive Valve closes Flow falls below the on-value of the low flow cut off: pressure shock suppression is activated...
Page 59
Proline Promag 400 HART Description of device parameters Empty pipe detection Navigation Expert → Sensor → Process param. → Empty pipe det. → Empty pipe det. (1860) Description Use this function to switch empty pipe detection on and off.
Page 60
Description of device parameters Proline Promag 400 HART Description Displays the adjustment value when the measuring pipe is empty. User interface Positive floating-point number Full pipe adjust value Navigation Expert → Sensor → Process param. → Empty pipe det. → Full pipe value (6548) Prerequisite •...
Page 61
Proline Promag 400 HART Description of device parameters New adjustment Navigation Expert → Sensor → Process param. → Empty pipe det. → Empty pipe adj. → New adjustment (6560) Prerequisite The On option is selected in the Empty pipe detection parameter (→ 59).
Page 62
Description of device parameters Proline Promag 400 HART Electrode cleaning circuit Navigation Expert → Sensor → Process param. → ECC → ECC (6528) Prerequisite For the following order code: "Application package", option EC "ECC electrode cleaning" Description Use this function to enable and disable cyclic electrode cleaning.
Proline Promag 400 HART Description of device parameters ECC cleaning cycle Navigation Expert → Sensor → Process param. → ECC → ECC clean. cycle (6557) Prerequisite For the following order code: "Application package", option EC "ECC electrode cleaning"...
Page 64
Description of device parameters Proline Promag 400 HART External value Navigation Expert → Sensor → External comp. → External value (6707) Description Use this function to select the process variable which is taken from an external device. Selection •...
Page 66
Description of device parameters Proline Promag 400 HART User interface 50 to 1 000 ms "Process variable adjustment" submenu Navigation Expert → Sensor → Sensor adjustm. → Variable adjust ‣ Process variable adjustment Volume flow offset (1831) → 66 →...
Page 67
Proline Promag 400 HART Description of device parameters Factory setting 0 m³/s Additional information Description Corrected value = (factor × value) + offset Mass flow factor Navigation Expert → Sensor → Sensor adjustm. → Variable adjust → Mass flow factor (1846) Description Use this function to enter a quantity factor (without time) for the mass flow.
Description of device parameters Proline Promag 400 HART Factory setting 0 S/m Additional information Description Corrected value = (factor × value) + offset Conductivity factor Navigation Expert → Sensor → Sensor adjustm. → Variable adjust → Conduct. factor (1849) Prerequisite In the Conductivity measurement parameter (→...
Page 69
Proline Promag 400 HART Description of device parameters Factory setting Depends on the size of the sensor Additional information Description The value is also specified on the sensor nameplate. Calibration factor Navigation Expert → Sensor → Calibration → Cal. factor (6522) Description Displays the current calibration factor for the sensor.
Description of device parameters Proline Promag 400 HART "Input" submenu Navigation Expert → Input ‣ Input ‣ Status input → 70 3.3.1 "Status input" submenu Navigation Expert → Input → Status input ‣ Status input Assign status input (1352) →...
Page 71
Expert → Input → Status input → Val. status inp. (1353) Prerequisite For the following order code: • "Output; input", option I "4-20mA HART, 2x pul./freq./switch output; status input" • "Output; input", option J "4-20mA HART, certified pulse output, switch output; status input" Description Displays the current input signal level.
Page 73
Proline Promag 400 HART Description of device parameters Selection • Volume flow • Mass flow • Flow velocity • Conductivity • Electronic temperature Factory setting Volume flow Current span Navigation Expert → Output → Curr.output 1 → Current span (0353–1)
Page 74
User entry 0 to 22.5 mA Factory setting 22.5 mA Additional information Example This setting can be used for HART multidrop, for example. 0/4 mA value Navigation Expert → Output → Curr.output 1 → 0/4 mA value (0367–1) Prerequisite One of the following options is selected in the Current span parameter (→...
Page 75
Proline Promag 400 HART Description of device parameters Dependency The unit depends on the process variable selected in the Assign current output parameter (→ 72). Current output behavior The current output behaves differently depending on the settings configured in the following parameters: •...
Page 76
Description of device parameters Proline Promag 400 HART The current output signal is independent of the direction of flow (absolute amount of the measured variable). The values for the 0/4 mA value parameter (→ 74) and 20 mA value parameter (→ 76) must have the same sign. The value for the 20 mA value parameter (→...
Page 77
Proline Promag 400 HART Description of device parameters Measuring mode Navigation Expert → Output → Curr.output 1 → Measuring mode (0351–1) Prerequisite One of the following options is selected in the Assign current output parameter (→ 72): •...
Page 78
Description of device parameters Proline Promag 400 HART • The current output signal is independent of the direction of flow (absolute amount of the measured variable). The values for the 0/4 mA value parameter (→ 74) and 20 mA value parameter (→...
Page 79
Proline Promag 400 HART Description of device parameters I [mA] A0028092 Current Time With Forward/Reverse flow option The current output signal is independent of the direction of flow. I [mA] A0028093 Current Time With Reverse flow compensation option flow components outside of the measuring range are buffered, balanced and output after a maximum delay of 60 s.
Page 80
Description of device parameters Proline Promag 400 HART A0028098 Flow Time Lower range value (value assigned to 0/4 mA current) Upper range value (value assigned to 20 mA current) With Forward flow option • a (—): The flow components outside the scaled measuring range cannot be taken into account for signal output.
Page 81
Proline Promag 400 HART Description of device parameters Damping output Navigation Expert → Output → Curr.output 1 → Damping out. (0363–1) Prerequisite One of the following options is selected in the Assign current output parameter (→ 72): •...
Page 82
Description of device parameters Proline Promag 400 HART Description Displays the response time. This specifies how quickly the current output reaches the measured value change of 63 % of 100 % of the measured value change. User interface Positive floating-point number...
Page 83
Proline Promag 400 HART Description of device parameters "Max." option The current output adopts the value of the upper level for signal on alarm. The signal on alarm level is defined via the Current span parameter (→ 73). "Last valid value" option The current output adopts the last measured value that was valid before the device alarm occurred.
Proline Promag 400 HART Description of device parameters Switch output function (0481–1 to 2) → 96 Assign diagnostic behavior → 96 (0482–1 to 2) → 97 Assign limit (0483–1 to 2) Switch-on value (0466–1 to 2) → 99 Switch-off value (0464–1 to 2)
Page 86
Description of device parameters Proline Promag 400 HART U[V] B < P A0026883 7 Quantity-proportional pulse (pulse value) with pulse width to be configured Pulse width entered Pauses between the individual pulses "Frequency" option Flow-proportional frequency output with 1:1 on/off ratio An output frequency is output that is proportional to the value of a process variable, such as mass flow, volume flow, flow velocity, conductivity or electronic temperature.
Description of device parameters Proline Promag 400 HART Factory setting 100 ms Additional information Description • Define how long a pulse is (duration). • The maximum pulse rate is defined by f = 1 / (2 × pulse width). • The interval between two pulses lasts at least as long as the set pulse width.
Proline Promag 400 HART Description of device parameters Additional information Selection • Forward flow Positive flow is output, negative flow is not output. • Forward/Reverse flow Positive and negative flow are output (absolute value), but a distinction is not made between positive and negative flow.
Proline Promag 400 HART Description of device parameters Selection • Off • Volume flow • Mass flow • Flow velocity • Conductivity • Electronic temperature Factory setting Minimum frequency value Navigation Expert → Output → PFS output 1 to 2 → Min. freq. value (0453–1 to 2) Prerequisite The Frequency option is selected in the Operating mode parameter (→...
Description of device parameters Proline Promag 400 HART Measuring value at minimum frequency Navigation Expert → Output → PFS output 1 to 2 → Val. at min.freq (0476–1 to 2) Prerequisite The Frequency option is selected in the Operating mode parameter (→ 85) and one of the following options is selected in the Assign frequency output parameter (→...
Proline Promag 400 HART Description of device parameters Measuring mode Navigation Expert → Output → PFS output 1 to 2 → Measuring mode (0479–1 to 2) Prerequisite The Frequency option is selected in the Operating mode parameter (→ 85) and one of the following options is selected in the Assign frequency output parameter (→...
Description of device parameters Proline Promag 400 HART Additional information Description Use this function to enter a time constant (PT1 element) for frequency output damping. The frequency output is subject to separate damping that is independent of all preceding time constants.
Proline Promag 400 HART Description of device parameters Factory setting 0 Hz Additional information Selection • Actual value In the event of a device alarm, the frequency output continues on the basis of the current flow measurement. The device alarm is ignored.
Page 96
Description of device parameters Proline Promag 400 HART Switch output function Navigation Expert → Output → PFS output 1 to 2 → Switch out funct (0481–1 to 2) Prerequisite In the Operating mode parameter (→ 85) the Switch option is selected.
Page 97
Proline Promag 400 HART Description of device parameters Additional information Description If no diagnostic event is pending, the switch output is closed and conductive. Options • Alarm The switch output signals only diagnostic events in the alarm category. • Alarm or warning The switch output signals diagnostic events in the alarm and warning category.
Page 98
Description of device parameters Proline Promag 400 HART A0026891 Switch-on value Switch-off value Conductive Non-conductive Process variable Status output Behavior of status output when Switch-on value < Switch-off value: • Process variable < Switch-on value: transistor is conductive • Process variable > Switch-off value: transistor is non-conductive...
Page 99
Proline Promag 400 HART Description of device parameters A0026893 Switch-on value = Switch-off value Conductive Non-conductive Process variable Status output Switch-on value Navigation Expert → Output → PFS output 1 to 2 → Switch-on value (0466–1 to 2) Prerequisite •...
Page 100
Description of device parameters Proline Promag 400 HART Description Use this function to enter the measured value for the switch-off point. User entry Signed floating-point number Factory setting Country-specific: • 0 l/h • 0 gal/min (us) Additional information Description Use this function to enter the limit value for the switch-off value (process variable <...
Page 101
Proline Promag 400 HART Description of device parameters Additional information Options If empty pipe detection or low flow cut off are enabled, the output is conductive. Otherwise, the switch output is non-conductive. Switch-on delay Navigation Expert → Output → PFS output 1 to 2 → Switch-on delay (0467–1 to 2) Prerequisite •...
Page 102
Description of device parameters Proline Promag 400 HART Additional information Options • Actual status In the event of a device alarm, faults are ignored and the current behavior of the input value is output by the switch output. The Actual status option behaves in the same way as the current input value.
Page 104
Expert → Communication → HART input → Configuration → Device ID (7007) Prerequisite The Master network option is selected in the Capture mode parameter (→ 104). Description Use this function to enter the device ID of the HART slave device whose data are to be recorded. User entry 6-digit value: •...
Page 105
Prerequisite The Master network option is selected in the Capture mode parameter (→ 104). Description Use this function to enter the device type of the HART slave device whose data are to be recorded. User entry 4-digit hexadecimal number...
Page 106
Use this function to capture the dynamic HART variables and the current. • Command 9 Use this function to capture the dynamic HART variables including the associated status. • Command 33 Use this function to capture the dynamic HART variables including the associated unit.
Page 107
F410 Data transfer. Failure mode Navigation Expert → Communication → HART input → Configuration → Failure mode (7011) Prerequisite In the Capture mode parameter (→ 104), the Burst network option or Master network option is selected. Description Use this function to select the device behavior if no data are recorded within the maximum permitted interval.
Signed floating-point number Status Navigation Expert → Communication → HART input → Input → Status (7004) Description Displays the value of the device variable recorded by the HART input in accordance with the HART specification. User interface • Manual/Fixed • Good •...
Page 109
→ 110 HART short tag Navigation Expert → Communication → HART output → Configuration → HART short tag (0220) Description Use this function to enter a brief description for the measuring point. This can be edited and displayed via HART protocol or using the local display.
Page 110
Navigation Expert → Communication → HART output → Configuration → HART address (0219) Description Use this function to enter the address via which the data exchange takes place via HART protocol. User entry 0 to 63 Factory setting No.
Page 111
Burst mode 1 to 3 Navigation Expert → Communication → HART output → Burst config. → Burst config. 1 to 3 → Burst mode 1 to 3 (2032–1 to 3) Description Use this function to select whether to activate the HART burst mode for burst message X.
Page 112
Burst variable 0 Navigation Expert → Communication → HART output → Burst config. → Burst config. 1 to 3 → Burst variable 0 (2033–1 to 3) Description For HART command 9 and 33: select the HART device variable or the process variable.
Page 113
Burst variable 1 Navigation Expert → Communication → HART output → Burst config. → Burst config. 1 to 3 → Burst variable 1 (2034–1 to 3) Description For HART command 9 and 33: select the HART device variable or the process variable.
Page 114
Burst variable 3 Navigation Expert → Communication → HART output → Burst config. → Burst config. 1 to 3 → Burst variable 3 (2036–1 to 3) Description For HART command 9 and 33: select the HART device variable or the process variable.
Page 115
Burst variable 7 Navigation Expert → Communication → HART output → Burst config. → Burst config. 1 to 3 → Burst variable 7 (2040–1 to 3) Description For HART command 33: select the HART device variable or the process variable.
Page 116
X. Min. update period Navigation Expert → Communication → HART output → Burst config. → Burst config. 1 to 3 → Min. upd. per. (2042–1 to 3) Description Use this function to enter the minimum time span between two burst commands of burst message X.
Page 117
Device ID Navigation Expert → Communication → HART output → Information → Device ID (0221) Description Use this function to view the device ID for identifying the measuring device in a HART network. User interface 6-digit hexadecimal number Additional information...
Page 118
Device type Navigation Expert → Communication → HART output → Information → Device type (0209) Description Displays the device type with which the measuring device is registered with the HART Communication Foundation. User interface 2-digit hexadecimal number Factory setting...
Page 119
Navigation Expert → Communication → HART output → Information → HART message (0216) Description Use this function to enter a HART message which is sent via the HART protocol when requested by the master. User entry Max. 32 characters such as letters, numbers or special characters (e.g. @, %, /)
Page 120
Assign PV Navigation Expert → Communication → HART output → Output → Assign PV (0234) Description Use this function to select a measured variable (HART device variable) for the primary dynamic variable (PV). Selection • Off • Volume flow •...
Page 121
Proline Promag 400 HART Description of device parameters Primary variable (PV) Navigation Expert → Communication → HART output → Output → Primary var (PV) (0201) Description Displays the current measured value of the primary dynamic variable (PV). User interface...
Page 122
Navigation Expert → Communication → HART output → Output → Assign TV (0236) Description Use this function to select a measured variable (HART device variable) for the tertiary (third) dynamic variable (TV). Selection • Volume flow • Mass flow •...
• Totalizer 1 • Totalizer 2 • Totalizer 3 Quaternary variable (QV) Navigation Expert → Communication → HART output → Output → Quaterna.var(QV) (0203) Description Displays the current measured value of the quaternary dynamic variable (QV). User interface Signed floating-point number...
Page 124
Description of device parameters Proline Promag 400 HART Web server language Navigation Expert → Communication → Web server → Webserv.language (7221) Description Use this function to select the web server language setting. Selection • English • Deutsch • Français •...
Page 125
Proline Promag 400 HART Description of device parameters IP address Navigation Expert → Communication → Web server → IP address (7209) Description Displays the IP address of the Web server of the measuring device. User interface 4 octet: 0 to 255 (in the particular octet) Factory setting 192.168.1.212...
Description of device parameters Proline Promag 400 HART Additional information Selection • Off – The Web server is completely disabled. – Port 80 is blocked. • On – The complete Web server functionality is available. – JavaScript is used. – The password is transmitted as an encrypted password.
Page 127
Proline Promag 400 HART Description of device parameters Event category 862 (0214) → 129 Event category 937 (0260) → 130 Event category 004 (Sensor) Navigation Expert → Communication → Diag. config. → Event category 004 (0238) Description Use this function to select the category assigned to diagnostic message 004 Sensor.
Page 128
Description of device parameters Proline Promag 400 HART Description Use this function to select a category for the diagnostic message 442 Frequency output 1 to 2. Selection • Failure (F) • Function check (C) • Out of specification (S) • Maintenance required (M) •...
Page 129
Proline Promag 400 HART Description of device parameters Event category 832 (Electronic temperature too high) Navigation Expert → Communication → Diag. config. → Event category 832 (0218) Description Use this function to select the category assigned to diagnostic message 832 Electronic temperature too high.
Description of device parameters Proline Promag 400 HART Additional information For a detailed description of the options available for selection: → 126 Event category 937 (EMC interference) Navigation Expert → Communication → Diag. config. → Event category 937 (0260)
Proline Promag 400 HART Description of device parameters Additional information Selection • Cancel No action is executed and the user exits the parameter. • Reset + totalize All totalizers are reset to 0 and the totaling process is restarted. 3.6.1 "Totalizer 1 to 3"...
Page 132
Description of device parameters Proline Promag 400 HART Unit totalizer Navigation Expert → Application → Totalizer 1 to 3 → Unit totalizer (0915–1 to 3) Prerequisite One of the following options is selected in the Assign process variable parameter (→...
Page 133
Proline Promag 400 HART Description of device parameters Totalizer operation mode Navigation Expert → Application → Totalizer 1 to 3 → Operation mode (0908–1 to 3) Prerequisite One of the following options is selected in the Assign process variable parameter (→...
Page 134
Description of device parameters Proline Promag 400 HART Additional information Selection • Totalize The totalizer is started or continues totalizing with the current counter reading. • Reset + hold The totaling process is stopped and the totalizer is reset to 0.
Proline Promag 400 HART Description of device parameters Selection • Stop • Actual value • Last valid value Factory setting Stop Additional information Description This setting does not affect the failsafe mode of other totalizers and the outputs. This is specified in separate parameters.
Page 136
Description of device parameters Proline Promag 400 HART Actual diagnostics Navigation Expert → Diagnostics → Actual diagnos. (0691) Prerequisite A diagnostic event has occurred. Description Displays the current diagnostic message. If two or more messages occur simultaneously, the message with the highest priority is shown on the display.
Page 137
Proline Promag 400 HART Description of device parameters Additional information Display Via the local display: the time stamp and corrective measures referring to the cause of the diagnostic message can be accessed via the key. Example For the display format: F271 Main electronic failure...
Description of device parameters Proline Promag 400 HART Additional information User interface The maximum number of days is 9999, which is equivalent to 27 years. 3.7.1 "Diagnostic list" submenu Navigation Expert → Diagnostics → Diagnostic list ‣ Diagnostic list Diagnostics 1 (0692) →...
Page 139
Proline Promag 400 HART Description of device parameters User interface Days (d), hours (h), minutes (m) and seconds (s) Additional information Display The diagnostic message can be viewed via the Diagnostics 1 parameter (→ 138). Example For the display format:...
Page 140
Description of device parameters Proline Promag 400 HART Diagnostics 3 Navigation Expert → Diagnostics → Diagnostic list → Diagnostics 3 (0694) Description Displays the current diagnostics message with the third-highest priority. User interface Symbol for diagnostic behavior, diagnostic code and short message.
Page 141
Proline Promag 400 HART Description of device parameters Examples For the display format: • S442 Frequency output • F276 I/O module failure Timestamp Navigation Expert → Diagnostics → Diagnostic list → Timestamp Description Displays the operating time when the diagnostic message with the fourth-highest priority occurred.
Description of device parameters Proline Promag 400 HART User interface Days (d), hours (h), minutes (m) and seconds (s) Additional information Display The diagnostic message can be viewed via the Diagnostics 5 parameter (→ 141). Example For the display format: 24d12h13m00s 3.7.2...
Page 143
Proline Promag 400 HART Description of device parameters "Event list" submenu The Event list submenu is only displayed if operating via the local display. If operating via the FieldCare operating tool, the event list can be read out with a separate FieldCare module.
Description of device parameters Proline Promag 400 HART 3.7.3 "Device information" submenu Navigation Expert → Diagnostics → Device info ‣ Device information Device tag (0011) → 144 Serial number (0009) → 145 → 145 Firmware version (0010) Device name (0013) →...
Page 145
Proline Promag 400 HART Description of device parameters Factory setting Promag 400 Additional information User interface XXXXXXXXX A0013375 11 Header text The number of characters displayed depends on the characters used. Serial number Navigation Expert → Diagnostics → Device info → Serial number (0009) Description Displays the serial number of the measuring device.
Page 146
Description of device parameters Proline Promag 400 HART Device name Navigation Expert → Diagnostics → Device info → Device name (0013) Description Displays the name of the transmitter. It can also be found on the nameplate of the transmitter.
Page 147
Proline Promag 400 HART Description of device parameters Extended order code 2 Navigation Expert → Diagnostics → Device info → Ext. order cd. 2 (0021) Description For displaying the second part of the extended order code. User interface...
Page 148
Description of device parameters Proline Promag 400 HART Custody transfer counter Navigation Expert → Diagnostics → Device info → Cust.trans.count (14402) Description Displays the number of times custody transfer mode has been enabled so far. User interface 0 to 65 535...
Page 151
Proline Promag 400 HART Description of device parameters Description Options for the assignment of a process variable to the data logging channel. Selection Picklist, see Assign channel 1 parameter (→ 150) Factory setting Assign channel 3 Navigation Expert → Diagnostics → Data logging → Assign chan. 3 (0853) Prerequisite The Extended HistoROM application package is available.
Page 152
Description of device parameters Proline Promag 400 HART Factory setting 10.0 s Additional information Description This defines the interval between the individual data points in the data log, and thus the maximum loggable process time T • If 1 logging channel is used: T = 1000 ×...
Page 154
Description of device parameters Proline Promag 400 HART Display channel 2 Navigation Expert → Diagnostics → Data logging → Displ.channel 2 Prerequisite A process variable is defined in the Assign channel 2 parameter. Description See the Display channel 1 parameter → 153 "Display channel 3"...
Description of device parameters Proline Promag 400 HART User interface Signed floating-point number Additional information Dependency The unit is taken from the Temperature unit parameter (→ 46) Maximum value Navigation Expert → Diagnostics → Min/max val. → Main elect.temp. → Maximum value...
Page 157
Proline Promag 400 HART Description of device parameters Value process variable (1811) → 158 Simulation status input (1355) → 158 Input signal level (1356) → 159 Simulation current output 1 (0354–1) → 159 Value current output 1 (0355–1) →...
Page 158
Prerequisite For the following order code: • "Output; input", option I "4-20mA HART, 2x pul./freq./switch output; status input" • "Output; input", option J "4-20mA HART, certified pulse output, switch output; status input" Description Use this function to switch simulation of the status input on and off. The display alternates between the measured value and a diagnostic message of the "Function check"...
Page 159
Proline Promag 400 HART Description of device parameters Selection • Off Simulation for the status input is switched off. The device is in normal measuring mode or another process variable is being simulated. • On Simulation for the status input is active.
Page 160
Description of device parameters Proline Promag 400 HART Value current output 1 Navigation Expert → Diagnostics → Simulation → Value curr.out 1 (0355–1) Prerequisite In the Simulation current output 1 parameter, the On option is selected. Description Use this function to enter a current value for the simulation. In this way, users can verify the correct adjustment of the current output and the correct function of downstream switching units.
Page 161
Proline Promag 400 HART Description of device parameters Description Use this function to enter a frequency value for the simulation. In this way, users can verify the correct adjustment of the frequency output and the correct function of downstream switching units.
Page 162
Description of device parameters Proline Promag 400 HART Switch output simulation 1 to 2 Navigation Expert → Diagnostics → Simulation → Switch sim. 1 to 2 (0462–1 to 2) Prerequisite In the Operating mode parameter (→ 85), the Switch option is selected.
Page 163
Proline Promag 400 HART Description of device parameters Simulation device alarm Navigation Expert → Diagnostics → Simulation → Sim. alarm (0654) Description Use this function to switch the device alarm on and off. Selection • Off • On...
Country-specific factory settings Proline Promag 400 HART Country-specific factory settings SI units Not valid for USA and Canada. 4.1.1 System units Volume flow Volume m³ Conductivity µS/cm Temperature °C Mass flow kg/h Mass Density kg/l 4.1.2 Full scale values The factory settings applie to the following parameters: •...
Country-specific factory settings Proline Promag 400 HART Nominal diameter ( 2 pulse/s) [mm] [dm³] 1 400 1 600 2.5 m 1 800 2 000 3.5 m 2 200 4.5 m 2 400 5.5 m 4.1.5 On value low flow cut off The switch-on point depends on the type of medium and the nominal diameter.
Proline Promag 400 HART Country-specific factory settings US units Only valid for USA and Canada. 4.2.1 System units Volume flow gal/min (us) Volume gal (us) Temperature °F Mass flow lb/min Mass Density lb/ft³ 4.2.2 Full scale values The factory settings applie to the following parameters: •...
Proline Promag 400 HART Country-specific factory settings Nominal diameter ( 2 pulse/s) [in] [gal] 0.0011 Mgal 0.0013 Mgal 4.2.5 On value low flow cut off The switch-on point depends on the type of medium and the nominal diameter. Nominal diameter (v ~ 0.04 m/s)
Explanation of abbreviated units Proline Promag 400 HART Explanation of abbreviated units SI units Process variable Units Explanation Density g/cm³, g/m³ Gram/volume unit kg/dm³, kg/l, kg/m³ Kilogram/volume unit SD4°C, SD15°C, SD20°C Specific density: The specific density is the ratio of the density of the fluid to the density of water at a water temperature of 4 °C (39 °F), 15 °C (59 °F), 20 °C (68 °F).