HART Proline Promass P 300 Operating Instructions Manual
HART Proline Promass P 300 Operating Instructions Manual

HART Proline Promass P 300 Operating Instructions Manual

Coriolis flowmeter
Table of Contents

Advertisement

BA01489D/06/EN/01.16
71302795
Valid as of version
01.00.zz (Device firmware)
Products

Operating Instructions

Proline Promass P 300
HART
Coriolis flowmeter
Solutions
Services

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Proline Promass P 300 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for HART Proline Promass P 300

  • Page 1: Operating Instructions

    Products Solutions Services BA01489D/06/EN/01.16 71302795 Valid as of version 01.00.zz (Device firmware) Operating Instructions Proline Promass P 300 HART Coriolis flowmeter...
  • Page 2 • Make sure the document is stored in a safe place such that it is always available when working on or with the device. • To avoid danger to individuals or the facility, read the "Basic safety instructions" section carefully, as well as all other safety instructions in the document that are specific to working procedures.
  • Page 3: Table Of Contents

    Table of contents Table of contents Document information ....6 Installation ..... . . 22 Document function .
  • Page 4 Operating tools ....68 11.6.1 Function scope of the "Control Measured variables via HART protocol ..68 Totalizer" parameter ... . 127 Other settings .
  • Page 5 Table of contents Maintenance ....152 13.1 Maintenance tasks ....152 13.1.1 Exterior cleaning .
  • Page 6: Document Information

    Document information Proline Promass P 300 HART Document information Document function These Operating Instructions contain all the information that is required in various phases of the life cycle of the device: from product identification, incoming acceptance and storage, to mounting, connection, operation and commissioning through to troubleshooting, maintenance and disposal.
  • Page 7: Tool Symbols

    Proline Promass P 300 HART Document information Symbol Meaning Light emitting diode is off. Light emitting diode is on. Light emitting diode is flashing. 1.2.4 Tool symbols Symbol Meaning Flat blade screwdriver Allen key Open-ended wrench 1.2.5 Symbols for certain types of information...
  • Page 8: Documentation

    Document information Proline Promass P 300 HART Symbol Meaning Hazardous area Safe area (non-hazardous area) Flow direction Documentation For an overview of the scope of the associated Technical Documentation, refer to the following: • The W@M Device Viewer : Enter the serial number from the nameplate (www.endress.com/deviceviewer)
  • Page 9: Registered Trademarks

    Proline Promass P 300 HART Document information Registered trademarks HART ® Registered trademark of the FieldComm Group, Austin, Texas, USA TRI-CLAMP ® Registered trademark of Ladish & Co., Inc., Kenosha, USA Applicator ® , FieldCare ® , DeviceCare ® , Field Xpert , HistoROM ®...
  • Page 10: Basic Safety Instructions

    Basic safety instructions Proline Promass P 300 HART Basic safety instructions Requirements for personnel The personnel for installation, commissioning, diagnostics and maintenance must fulfill the following requirements: ‣ Trained, qualified specialists must have a relevant qualification for this specific function and task.
  • Page 11: Workplace Safety

    Proline Promass P 300 HART Basic safety instructions NOTICE Verification for borderline cases: ‣ For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of fluid-wetted materials, but does not accept any warranty or liability as minute changes in the temperature, concentration or level of contamination in the process can alter the corrosion resistance properties.
  • Page 12: It Security

    Basic safety instructions Proline Promass P 300 HART IT security We only provide a warranty if the device is installed and used as described in the Operating Instructions. The device is equipped with security mechanisms to protect it against any inadvertent changes to the device settings.
  • Page 13: Access Via Fieldbus

    Proline Promass P 300 HART Basic safety instructions General notes on the use of passwords • The access code and network key supplied with the device should be changed during commissioning. • Follow the general rules for generating a secure password when defining and managing the access code or network key.
  • Page 14: Product Description

    Product description Proline Promass P 300 HART Product description The device consists of a transmitter and a sensor. The device is available as a compact version: The transmitter and sensor form a mechanical unit. Product design N ic te r e rg ö...
  • Page 15: Incoming Acceptance And Product

    Proline Promass P 300 HART Incoming acceptance and product identification Incoming acceptance and product identification Incoming acceptance Are the order codes on the delivery note (1) and the product sticker (2) identical? A0028673 A0029314 A0029315 Are the goods undamaged? A0028673...
  • Page 16: Product Identification

    Incoming acceptance and product identification Proline Promass P 300 HART Product identification The following options are available for identification of the measuring device: • Nameplate specifications • Order code with breakdown of the device features on the delivery note • Enter serial numbers from nameplates in W@M Device Viewer (www.endress.com/deviceviewer): All information about the measuring device is...
  • Page 17: Transmitter Nameplate

    Proline Promass P 300 HART Incoming acceptance and product identification 4.2.1 Transmitter nameplate 3 4 5 Order code: Ser. no.: Ext. ord. cd.: Date: A0029192  2 Example of a transmitter nameplate Manufacturing location Name of the transmitter Order code Serial number (ser.
  • Page 18: Sensor Nameplate

    Incoming acceptance and product identification Proline Promass P 300 HART 4.2.2 Sensor nameplate Order code: Ser. no.: Ext. ord. cd.: Date: A0029199  3 Example of a sensor nameplate Name of the sensor Manufacturing location Order code Serial number (ser. no.) Extended order code (Ext.
  • Page 19: Symbols On Measuring Device

    Proline Promass P 300 HART Incoming acceptance and product identification 4.2.3 Symbols on measuring device Symbol Meaning WARNING! This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious or fatal injury. Reference to documentation Refers to the corresponding device documentation.
  • Page 20: Storage And Transport

    Storage and transport Proline Promass P 300 HART Storage and transport Storage conditions Observe the following notes for storage: • Store in the original packaging to ensure protection from shock. • Do not remove protective covers or protective caps installed on process connections.
  • Page 21: Measuring Devices With Lifting Lugs

    Proline Promass P 300 HART Storage and transport 5.2.2 Measuring devices with lifting lugs CAUTION Special transportation instructions for devices with lifting lugs ‣ Only use the lifting lugs fitted on the device or flanges to transport the device. ‣...
  • Page 22: Installation

    Installation Proline Promass P 300 HART Installation Installation conditions No special measures such as supports are necessary. External forces are absorbed by the construction of the device. 6.1.1 Mounting position Mounting location A0028772 To prevent measuring errors arising from accumulation of gas bubbles in the measuring tube, avoid the following mounting locations in the pipe: •...
  • Page 23 Proline Promass P 300 HART Installation Ø orifice plate, pipe restriction [mm] [in] [mm] [in] ³⁄₈ 0.24 ½ 0.40 0.55 1½ 0.87 1.10 Orientation The direction of the arrow on the sensor nameplate helps you to install the sensor according to the flow direction (direction of medium flow through the piping).
  • Page 24: Requirements From Environment And Process

    Installation Proline Promass P 300 HART Inlet and outlet runs No special precautions need to be taken for fittings which create turbulence, such as valves, elbows or T-pieces, as long as no cavitation occurs →  24. A0029322 A0029323 Installation dimensions For the dimensions and installation lengths of the device, see the "Technical...
  • Page 25 Proline Promass P 300 HART Installation Thermal insulation In the case of some fluids, it is important that the heat radiated from the sensor to the transmitter is kept to a minimum. A wide range of materials can be used for the required insulation.
  • Page 26 Installation Proline Promass P 300 HART Maximum recommended insulation thickness at an ambient temperature of T = 40 °C (104 °F) (104) Maximum recommended insulation thickness at an ambient temperature of T = 60 °C (140 °F) (140) Maximum recommended insulation thickness for the extended temperature range or...
  • Page 27: Special Mounting Instructions

    Proline Promass P 300 HART Installation Using an electrical trace heating system If heating is regulated via phase angle control or pulse packages, magnetic fields can affect the measured values (= for values that are greater than the values permitted by the EN standard (sine 30 A/m)).
  • Page 28: Mounting The Measuring Device

    Installation Proline Promass P 300 HART A0030298 [mm] [in] [mm] [in] [mm] [in] [mm] [in] ³⁄₈ 11.73 ½ 15.83 21.34 1 ½ 25.91 36.5 1.44 30.39 44.1 1.74 2.95 Zero point adjustment All measuring devices are calibrated in accordance with state-of-the-art technology.
  • Page 29: Preparing The Measuring Device

    Proline Promass P 300 HART Installation 6.2.2 Preparing the measuring device 1. Remove all remaining transport packaging. 2. Remove any protective covers or protective caps present from the sensor. 3. Remove stick-on label on the electronics compartment cover. 6.2.3 Mounting the measuring device...
  • Page 30: Turning The Display Module

    Installation Proline Promass P 300 HART 6.2.5 Turning the display module The display module can be turned to optimize display readability and operability. – – – 3 mm A0030035 1. Loosen the securing clamp of the connection compartment cover. 2. Unscrew the connection compartment cover.
  • Page 31: Electrical Connection

    Minimum requirement: cable temperature range ≥ ambient temperature +20 K Power supply cable Standard installation cable is sufficient. Signal cable Current output 4 to 20 mA HART A shielded cable is recommended. Observe grounding concept of the plant. Current output 0/4 to 20 mA Standard installation cable is sufficient.
  • Page 32 Electrical connection Proline Promass P 300 HART Current input 0/4 to 20 mA Standard installation cable is sufficient. Status input Standard installation cable is sufficient. Cable diameter • Cable glands supplied: M20 × 1.5 with cable ⌀ 6 to 12 mm (0.24 to 0.47 in) •...
  • Page 33: Terminal Assignment

    Proline Promass P 300 HART Electrical connection 7.1.3 Terminal assignment Transmitter: supply voltage, input/outputs The terminal assignment of the inputs and outputs depends on the individual order version of the device. The device-specific terminal assignment is documented on an adhesive label in the terminal cover.
  • Page 34 Electrical connection Proline Promass P 300 HART – – – 3 mm A0029813 1. Loosen the securing clamp of the connection compartment cover. 2. Unscrew the connection compartment cover. 3. Squeeze the tabs of the display module holder together. 4. Remove the display module holder.
  • Page 35 Proline Promass P 300 HART Electrical connection 22 mm 24 mm – A0029816 10. Connect the cable in accordance with the terminal assignment .  Signal cable terminal assignment: The device-specific terminal assignment is documented on an adhesive label in the terminal cover.
  • Page 36: Connecting Remote Display And Operating Module Dkx001

    Electrical connection Proline Promass P 300 HART 7.2.2 Connecting remote display and operating module DKX001 NOTICE If ordered subsequently: only one display or operation unit may be connected to the transmitter at any one time. The remote display and operating module DKX001 cannot be connected at the same time as the existing display or operation unit.
  • Page 37: Special Connection Instructions

    Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable specifications Connection for HART operating devices →  62 Resistor for HART communication (≥ 250 Ω): observe maximum load →  161 Analog display unit: observe maximum load →  161 Transmitter 4...20 mA...
  • Page 38 4...20 mA A0028763  10 Connection example for HART input with a common negative (passive) Automation system with HART output (e.g. PLC) Active barrier for power supply (e.g. RN221N) Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable...
  • Page 39 Proline Promass P 300 HART Electrical connection Pulse/frequency output 12345 A0028761  13 Connection example for pulse/frequency output (passive) Automation system with pulse/frequency input (e.g. PLC) Power supply Transmitter: Observe input values →  161 Switch output A0028760  14 Connection example for switch output (passive) Automation system with switch input (e.g.
  • Page 40 Electrical connection Proline Promass P 300 HART A0029279  16 Connection example for double pulse output (passive) Automation system with double pulse input (e.g. PLC) Power supply Transmitter: Observe input values →  163 Double pulse output Double pulse output (slave), phase-shifted...
  • Page 41: Ensuring The Degree Of Protection

    Proline Promass P 300 HART Electrical connection Status input A0028764  19 Connection example for status input Automation system with status output (e.g. PLC) Power supply Transmitter: Observe input values Ensuring the degree of protection The measuring device fulfills all the requirements for the IP66/67 degree of protection, Type 4X enclosure.
  • Page 42: Operation Options

    Operation options Proline Promass P 300 HART Operation options Overview of operation options A0029295 Local operation via display module Computer with Web browser (e.g. Internet Explorer) or with operating tool (e.g. FieldCare, DeviceCare, AMS Device Manager, SIMATIC PDM) Field Xpert SFX350 or SFX370...
  • Page 43: Structure And Function Of The Operating Menu

    Proline Promass P 300 HART Operation options Structure and function of the operating menu 8.2.1 Structure of the operating menu For an overview of the operating menu for experts: "Description of Device Parameters" document supplied with the device→  185...
  • Page 44: Operating Philosophy

    Operation options Proline Promass P 300 HART 8.2.2 Operating philosophy The individual parts of the operating menu are assigned to certain user roles (operator, maintenance etc.). Each user role contains typical tasks within the device lifecycle. Menu/parameter User role and tasks...
  • Page 45: Display

    Proline Promass P 300 HART Operation options Access to the operating menu via the local display 8.3.1 Operational display X X X X X X X 1120.50 kg/h A0029348 Operational display Device tag Status area Display area for measured values (4-line) Operating elements→...
  • Page 46: Navigation View

    Operation options Proline Promass P 300 HART • Density • Reference density Temperature Totalizer  The measurement channel number indicates which of the three totalizers is displayed. Output  The measurement channel number indicates which of the outputs is displayed.
  • Page 47 Proline Promass P 300 HART Operation options • In the submenu: Omission symbol for Name of current Display symbol for menu operating menu levels in • Submenu • In the wizard: between • Wizard Display symbol for wizard • Parameters ↓...
  • Page 48: Editing View

    Operation options Proline Promass P 300 HART Locking Symbol Meaning Parameter locked When displayed in front of a parameter name, indicates that the parameter is locked. • By a user-specific access code • By the hardware write protection switch Wizard operation...
  • Page 49 Proline Promass P 300 HART Operation options Exits the input without applying the changes. Clears all entered characters. Text editor Symbol Meaning Toggle • Between upper-case and lower-case letters • For entering numbers • For entering special characters Selection of letters from A to Z.
  • Page 50: Operating Elements

    Operation options Proline Promass P 300 HART 8.3.4 Operating elements Meaning Minus key In a menu, submenu Moves the selection bar upwards in a choose list. With a Wizard Confirms the parameter value and goes to the previous parameter. With a text and numeric editor In the input mask, moves the selection bar to the left (backwards).
  • Page 51 Proline Promass P 300 HART Operation options • Setup • Data backup • Simulation Calling up and closing the context menu The user is in the operational display. 1. Press  for 2 s.  The context menu opens. XXXXXXXXXX 20.50...
  • Page 52: Navigating And Selecting From List

    Operation options Proline Promass P 300 HART 8.3.6 Navigating and selecting from list Different operating elements are used to navigate through the operating menu. The navigation path is displayed on the left in the header. Icons are displayed in front of the individual menus.
  • Page 53: Calling Up Help Text

    Proline Promass P 300 HART Operation options The direct access code consists of a 4-digit number and the channel number, which identifies the channel of a process variable: e.g. 0914-1. In the navigation view, this appears on the right-hand side in the header of the selected parameter.
  • Page 54: Changing The Parameters

    Operation options Proline Promass P 300 HART 8.3.9 Changing the parameters For a description of the editing display - consisting of text editor and numeric editor - with symbols →  48, for a description of the operating elements →  50 Example: Changing the tag name in the "Tag description"...
  • Page 55: User Roles And Related Access Authorization

    Proline Promass P 300 HART Operation options Ent. access code Invalid or out of range input value Min:0 Max:9999 A0014049-EN 8.3.10 User roles and related access authorization The two user roles "Operator" and "Maintenance" have different write access to the parameters if the customer defines a user-specific access code.
  • Page 56: Access To The Operating Menu Via The Web Browser

    Operation options Proline Promass P 300 HART Local operation with touch control The keypad lock is switched on and off via the context menu. Switching on the keypad lock The keypad lock is switched on automatically: • Each time the device is restarted.
  • Page 57 Proline Promass P 300 HART Operation options Computer software Software Interface CDI-RJ45 WLAN Recommended operating • Microsoft Windows 7 or higher. systems • Mobile operating systems: – iOS – Android  Microsoft Windows XP is supported. Web browsers supported • Microsoft Internet Explorer 8 or higher •...
  • Page 58: Establishing A Connection

    Operation options Proline Promass P 300 HART 8.4.3 Establishing a connection Via service interface (CDI-RJ45) Configuring the Internet protocol of the computer The following information refers to the default Ethernet settings of the device. IP address of the device: 192.168.1.212 (factory setting) 1.
  • Page 59: Logging On

    Proline Promass P 300 HART Operation options Starting the Web browser 1. Start the Web browser on the computer. 2. Enter the IP address of the Web server in the address line of the Web browser: 192.168.1.212  The login page appears.
  • Page 60: User Interface

    Operation options Proline Promass P 300 HART 8.4.5 User interface A0029418 Function row Operating language Navigation area Header The following information appears in the header: • Device tag • Device status with status signal →  138 • Current measured values...
  • Page 61: Disabling The Web Server

    Proline Promass P 300 HART Operation options Working area Depending on the selected function and the related submenus, various actions can be performed in this area: • Configuring parameters • Reading measured values • Calling up help text • Starting an upload/download 8.4.6...
  • Page 62: Connecting The Operating Tool

    Proline Promass P 300 HART 8.5.1 Connecting the operating tool Via HART protocol This communication interface is available in device versions with a HART output. A0028747  22 Options for remote operation via HART protocol (active) Control system (e.g. PLC) Field Communicator 475 Computer with Web browser (e.g.
  • Page 63 Proline Promass P 300 HART Operation options Service interface Via service interface (CDI-RJ45) A0027563  24 Connection via service interface (CDI-RJ45) Computer with Web browser (e.g. Microsoft Internet Explorer, Microsoft Edge) for accessing the integrated device Web server or with "FieldCare", "DeviceCare" operating tool with COM DTM "CDI Communication TCP/IP"...
  • Page 64: Field Xpert Sfx350, Sfx370

    Function scope Field Xpert SFX350 and Field Xpert SFX370 are mobile computers for commissioning and maintenance. They enable efficient device configuration and diagnostics for HART and FOUNDATION fieldbus devices in the non-Ex area (SFX350, SFX370) and the Ex area (SFX370).
  • Page 65: Fieldcare

    Proline Promass P 300 HART Operation options 8.5.3 FieldCare Function scope FDT-based plant asset management tool from Endress+Hauser. It can configure all smart field devices in a system and helps you manage them. By using the status information, it is also a simple but effective way of checking their status and condition.
  • Page 66: Devicecare

    Operation options Proline Promass P 300 HART User interface Xxxxxx/…/…/ Device name: Xxxxxxx kg/h Mass flow: 12.34 Device tag: Xxxxxxx Volume flow: 12.34 m /h ³ Status: Good Xxxxxx Mass flow unit: kg/h Access status tooling Maintenance Volume flow unit: m /h ³...
  • Page 67: Simatic Pdm

    Source for device description files See data →  68 8.5.7 Field Communicator 475 Function scope Industrial handheld terminal from Emerson Process Management for remote configuration and measured value display via HART protocol. Source for device description files See data →  68 Endress+Hauser...
  • Page 68: System Integration

    SIMATIC PDM www.endress.com → Download Area (Siemens) Field Communicator 475 Use update function of handheld terminal (Emerson Process Management) Measured variables via HART protocol The following measured variables (HART device variables) are assigned to the dynamic variables at the factory: Endress+Hauser...
  • Page 69 • Expert → Communication → HART output → Output → Assign PV • Expert → Communication → HART output → Output → Assign SV • Expert → Communication → HART output → Output → Assign TV •...
  • Page 70: Other Settings

    • 15 = concentration Other settings 9.3.1 Burst mode functionality in accordance with HART 7 Specification Navigation "Expert" menu → Communication → HART output → Burst configuration → Burst configuration 1 to n ‣ Burst configuration ‣ Burst configuration 1 to n Burst mode 1 to n →...
  • Page 71 Activate the HART burst mode for burst • Off message X. • On Burst command 1 to n Select the HART command that is sent to the • Command 1 Command 2 HART master. • Command 2 • Command 3 •...
  • Page 72 System integration Proline Promass P 300 HART Parameter Description Selection / User entry Factory setting Min. update period Enter the minimum time span between two Positive integer 1 000 ms burst responses of one burst message. Max. update period Enter the maximum time span between two...
  • Page 73: Commissioning

    Proline Promass P 300 HART Commissioning Commissioning 10.1 Function check Before commissioning the measuring device: ‣ Make sure that the post-installation and post-connection checks have been performed. • "Post-installation check" checklist →  30 • "Post-connection check" checklist →  41 10.2...
  • Page 74 Commissioning Proline Promass P 300 HART X X X X X X X 20.50 0104-1 Main menu Display language English Display/operat. Setup Main menu Display/operat. Setup Diagnostic / ../Setup Status input XXXXXXXXX XXXXXXXXX A0029700-EN  26 Taking the example of the local display Depending on the device version, not all submenus and parameters are available in every device.
  • Page 75: Defining The Tag Name

    Proline Promass P 300 HART Commissioning ‣ Partially filled pipe detection →  101 ‣ Advanced setup →  102 10.4.1 Defining the tag name To enable fast identification of the measuring point within the system, you can enter a unique designation using the Device tag parameter and thus change the factory setting.
  • Page 76 Commissioning Proline Promass P 300 HART Corrected volume flow unit →  76 Corrected volume unit →  76 Density unit →  76 Reference density unit →  76 Temperature unit →  77 →  77 Pressure unit...
  • Page 77 Proline Promass P 300 HART Commissioning Parameter Description Selection Factory setting Temperature unit Select temperature unit. Unit choose list Country-specific: • °C Result • °F The selected unit applies for: • Electronic temperature parameter (6053) • Maximum value parameter (6051) •...
  • Page 78: Selecting And Setting The Medium

    Commissioning Proline Promass P 300 HART 10.4.3 Selecting and setting the medium The Select medium wizard submenu contains parameters that must be configured in order to select and set the medium. Navigation "Setup" menu → Select medium ‣ Medium selection →...
  • Page 79: Displaying The I/O Configuration

    Proline Promass P 300 HART Commissioning Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting entry / User interface Select medium – Select medium type. • Liquid Liquid • Gas Select gas type The Gas option is selected in Select measured gas type.
  • Page 80: Configuring The Current Input

    Commissioning Proline Promass P 300 HART Navigation "Setup" menu → I/O configuration ‣ I/O configuration →  80 I/O module 1 to n terminal numbers →  80 I/O module 1 to n information I/O module 1 to n type →...
  • Page 81: Configuring The Status Input

    Proline Promass P 300 HART Commissioning Signal mode →  81 0/4 mA value →  81 20 mA value →  81 Current span →  81 Failure mode →  81 →  81 Failure value Parameter overview with brief description...
  • Page 82: Configuring The Current Output

    Commissioning Proline Promass P 300 HART Terminal number →  82 Active level →  82 Terminal number →  82 Response time status input →  82 Terminal number →  82 Parameter overview with brief description Parameter Description User interface / Selection / ...
  • Page 83 Proline Promass P 300 HART Commissioning Fixed current →  84 Failure mode →  84 Failure current →  84 Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting interface / User entry Assign current output 1 to n –...
  • Page 84 Commissioning Proline Promass P 300 HART Parameter Prerequisite Description Selection / User Factory setting interface / User entry 20 mA value One of the following options is Enter 20 mA value. Signed floating-point Depends on country selected in the Current span number and nominal parameter (→...
  • Page 85: Configuring The Pulse/Frequency

    Proline Promass P 300 HART Commissioning 10.4.8 Configuring the pulse/frequency/switch output The Pulse/frequency/switch output wizard guides you systematically through all the parameters that can be set for configuring the selected output type. Navigation "Setup" menu → Advanced setup → Pulse/frequency/switch output ‣...
  • Page 86 Commissioning Proline Promass P 300 HART Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting interface / User entry Operating mode – Define the output as a pulse, • Pulse Pulse frequency or switch output. • Frequency • Switch Terminal number –...
  • Page 87 Proline Promass P 300 HART Commissioning Configuring the frequency output Navigation "Setup" menu → Pulse/frequency/switch output ‣ Pulse/frequency/switch output 1 to n Operating mode →  87 Terminal number →  87 Signal mode →  87 →  88...
  • Page 88 Commissioning Proline Promass P 300 HART Parameter Prerequisite Description Selection / User Factory setting interface / User entry Assign frequency output In the Operating mode Select process variable for • Off parameter (→  85), the frequency output. • Mass flow Frequency option is selected.
  • Page 89 Proline Promass P 300 HART Commissioning Parameter Prerequisite Description Selection / User Factory setting interface / User entry Maximum frequency value In the Operating mode Enter maximum frequency. 0.0 to 10 000.0 Hz 10 000.0 Hz parameter, the Frequency option is selected and one of...
  • Page 90 Commissioning Proline Promass P 300 HART Parameter Prerequisite Description Selection / User Factory setting interface / User entry Measuring value at maximum In the Operating mode Enter measured value for Signed floating-point Depends on country frequency parameter, the Frequency maximum frequency. number and nominal...
  • Page 91 Proline Promass P 300 HART Commissioning Parameter Prerequisite Description Selection / User Factory setting interface / User entry Failure frequency In the Operating mode Enter frequency output value 0.0 to 12 500.0 Hz 0.0 Hz parameter, the Frequency in alarm condition. option is selected and one of...
  • Page 92 Commissioning Proline Promass P 300 HART Configuring the switch output Navigation "Setup" menu → Pulse/frequency/switch output ‣ Pulse/frequency/switch output 1 to n Operating mode →  92 Terminal number →  92 Signal mode →  92 →  93...
  • Page 93 Proline Promass P 300 HART Commissioning Parameter Prerequisite Description Selection / User Factory setting interface / User entry Switch output function In the Operating mode Select function for switch • Off parameter the Switch option is output. • On selected. • Diagnostic behavior • Limit •...
  • Page 94: Configuring The Relay Output

    Commissioning Proline Promass P 300 HART Parameter Prerequisite Description Selection / User Factory setting interface / User entry Switch-off delay • The Switch option is Define delay for the switch-off 0.0 to 100.0 s 0.0 s selected in the Operating of status output. mode parameter.
  • Page 95 Proline Promass P 300 HART Commissioning Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting interface / User entry Relay output function – Select the function for the • Closed Closed relay output. • Open • Diagnostic behavior • Limit •...
  • Page 96: 10.4.10 Configuring The Double Pulse Output

    Commissioning Proline Promass P 300 HART 10.4.10 Configuring the double pulse output The Double pulse output submenu guides the user systematically through all the parameters that have to be set for configuring the double pulse output. Navigation "Setup" menu → Double pulse output ‣...
  • Page 97: 10.4.11 Configuring The Local Display

    Proline Promass P 300 HART Commissioning Parameter Description Selection / User interface /  Factory setting User entry Failure mode Define output behavior in alarm condition. • Actual value No pulses • No pulses Invert output signal Invert the output signal. • No • Yes Visibility depends on order options or device settings 10.4.11 Configuring the local display...
  • Page 98 Commissioning Proline Promass P 300 HART Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting entry Format display A local display is provided. Select how measured values • 1 value, max. size 1 value, max. size are shown on the display.
  • Page 99 Proline Promass P 300 HART Commissioning Parameter Prerequisite Description Selection / User Factory setting entry Value 2 display A local display is provided. Select the measured value that • None None is shown on the local display. • Mass flow • Volume flow •...
  • Page 100: 10.4.12 Configuring The Low Flow Cut Off

    Commissioning Proline Promass P 300 HART 10.4.12 Configuring the low flow cut off The Low flow cut off wizard systematically guides the user through all the parameters that must be set to configure low flow cut off. Navigation "Setup" menu → Low flow cut off ‣...
  • Page 101: 10.4.13 Configuring The Partial Filled Pipe Detection

    Proline Promass P 300 HART Commissioning 10.4.13 Configuring the partial filled pipe detection The Partial filled pipe detection wizard guides you systematically through all parameters that have to be set for configuring the monitoring of the pipe filling. Navigation "Setup" menu → Partially filled pipe detection ‣...
  • Page 102: Advanced Settings

    Commissioning Proline Promass P 300 HART 10.5 Advanced settings The Advanced setup submenu together with its submenus contains parameters for specific settings. Navigation to the "Advanced setup" submenu X X X X X X X 20.50 0104-1 Main menu Language English Display/operat.
  • Page 103: Using The Parameter To Enter The Access Code

    Proline Promass P 300 HART Commissioning ‣ Deactivate SIL ‣ Display →  107 ‣ WLAN settings →  110 ‣ Concentration ‣ Heartbeat setup ‣ →  111 Configuration backup ‣ Administration →  113 10.5.1 Using the parameter to enter the access code Navigation "Setup"...
  • Page 104: Carrying Out A Sensor Adjustment

    Commissioning Proline Promass P 300 HART Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting interface / User entry Corrected volume flow calculation – Select reference density for • Fixed reference Calculated reference calculating the corrected density density volume flow.
  • Page 105: Configuring The Totalizer

    Proline Promass P 300 HART Commissioning Parameter overview with brief description Parameter Description Selection Factory setting Installation direction Set sign of flow direction to match the • Flow in arrow direction Flow in arrow direction direction of the arrow on the sensor.
  • Page 106 Commissioning Proline Promass P 300 HART Parameter overview with brief description Parameter Prerequisite Description Selection Factory setting Assign process variable – Select process variable for • Off Mass flow totalizer. • Volume flow • Mass flow • Corrected volume flow •...
  • Page 107: Carrying Out Additional Display Configurations

    Proline Promass P 300 HART Commissioning 10.5.5 Carrying out additional display configurations In the Display submenu you can set all the parameters associated with the configuration of the local display. Navigation "Setup" menu → Advanced setup → Display ‣ Display Format display →...
  • Page 108 Commissioning Proline Promass P 300 HART Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting entry Format display A local display is provided. Select how measured values • 1 value, max. size 1 value, max. size are shown on the display.
  • Page 109 Proline Promass P 300 HART Commissioning Parameter Prerequisite Description Selection / User Factory setting entry Value 2 display A local display is provided. Select the measured value that • None None is shown on the local display. • Mass flow • Volume flow •...
  • Page 110: Wlan Configuration

    Commissioning Proline Promass P 300 HART Parameter Prerequisite Description Selection / User Factory setting entry Display language A local display is provided. Set display language. • English English • Deutsch (alternatively, the • Français ordered language is • Español preset in the device) •...
  • Page 111: Configuration Management

    Proline Promass P 300 HART Commissioning Navigation "Setup" menu → Advanced setup → WLAN Settings ‣ WLAN settings →  111 WLAN IP address →  111 Security type WLAN passphrase →  111 Assign SSID name →  111 SSID name →...
  • Page 112 Commissioning Proline Promass P 300 HART Navigation "Setup" menu → Advanced setup → Configuration backup ‣ Configuration backup →  112 Operating time →  112 Last backup Configuration management →  112 Backup state →  112 Comparison result →...
  • Page 113: Using Parameters For Device Administration

    Proline Promass P 300 HART Commissioning Options Description Compare The device configuration saved in the device memory is compared with the current device configuration of the integrated HistoROM. Clear backup data The backup copy of the device configuration is deleted from the memory of the device.
  • Page 114: Simulation

    Commissioning Proline Promass P 300 HART Using the parameter to reset the access code Navigation "Setup" menu → Advanced setup → Administration → Reset access code ‣ Reset access code Operating time →  114 Reset access code →  114...
  • Page 115 Proline Promass P 300 HART Commissioning Process variable value →  116 Status input simulation →  116 Input signal level →  116 Current input 1 to n simulation →  116 Value current input 1 to n →  116 Current output 1 to n simulation →...
  • Page 116 Commissioning Proline Promass P 300 HART Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting entry / User interface Assign simulation process variable – Select a process variable for • Off the simulation process that is • Mass flow activated.
  • Page 117: Protecting Settings From Unauthorized

    Proline Promass P 300 HART Commissioning Parameter Prerequisite Description Selection / User Factory setting entry / User interface Switch output simulation 1 to n In the Operating mode Switch the simulation of the • Off parameter, the Switch option switch output on and off.
  • Page 118 Commissioning Proline Promass P 300 HART Defining the access code via local display 1. Navigate to the Define access code parameter (→  113). 2. Define a max. 16-digit character string comprising numbers, letters and special characters as the access code.
  • Page 119: Write Protection Via Write Protection

    Proline Promass P 300 HART Commissioning Via Web browser, FieldCare, DeviceCare (via CDI-RJ45 service interface), fieldbus For a reset code, contact your Endress+Hauser service organization. 1. Navigate to the Reset access code parameter (→  114). 2. Enter the reset code.
  • Page 120: Operation

    Operation Proline Promass P 300 HART Operation 11.1 Reading the device locking status Device active write protection: Locking status parameter Operation → Locking status Function scope of the "Locking status" parameter Options Description None The access status displayed in the Access status parameter applies →  55. Only appears on local display.
  • Page 121: Measured Variables" Submenu

    Proline Promass P 300 HART Operation 11.4.1 "Measured variables" submenu The Measured variables submenu contains all the parameters needed to display the current measured values for each process variable. Navigation "Diagnostics" menu → Measured values → Measured variables ‣ Measured variables →...
  • Page 122: Totalizer" Submenu

    Operation Proline Promass P 300 HART Parameter Prerequisite Description User interface Reference density – Displays the reference density currently Signed floating-point calculated. number Dependency The unit is taken from the Reference density unit parameter (→  76). Temperature – Shows the medium temperature Signed floating-point currently measured.
  • Page 123: Input Values" Submenu

    Proline Promass P 300 HART Operation Parameter overview with brief description Parameter Prerequisite Description User interface Totalizer value 1 to n A process variable is selected in the Displays the current totalizer counter Signed floating-point Assign process variable parameter value.
  • Page 124: Output Values

    Operation Proline Promass P 300 HART Navigation "Diagnostics" menu → Measured values → Input values → Status input 1 to n ‣ Status input 1 to n →  124 Value status input Parameter overview with brief description Parameter Description...
  • Page 125 Proline Promass P 300 HART Operation Parameter overview with brief description Parameter Description User interface Output current 1 Displays the current value currently calculated for the current 3.59 to 22.5 mA output. Measured current Displays the current value currently measured for the current 0 to 30 mA output.
  • Page 126: Adapting The Measuring Device To The Process

    Operation Proline Promass P 300 HART Navigation "Diagnostics" menu → Measured values → Output values → Relay output 1 to n ‣ Relay output 1 to n →  126 Switch status →  126 Switch cycles Max. switch cycles number →...
  • Page 127: Function Scope Of The "Control Totalizer" Parameter

    Proline Promass P 300 HART Operation Navigation "Operation" menu → Totalizer handling ‣ Totalizer handling →  127 Control Totalizer 1 to n →  127 Preset value 1 to n Reset all totalizers →  127 Parameter overview with brief description...
  • Page 128: Function Scope Of The "Reset All Totalizers" Parameter

    Operation Proline Promass P 300 HART 11.6.2 Function scope of the "Reset all totalizers" parameter Options Description Cancel No action is executed and the user exits the parameter. Reset + totalize Resets all totalizers to 0 and restarts the totaling process. This deletes all the flow values previously totalized.
  • Page 129 Proline Promass P 300 HART Operation Data logging control →  129 Data logging status →  130 Entire logging duration →  130 Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting entry / User interface Assign channel 1 to n...
  • Page 130 Operation Proline Promass P 300 HART Parameter Prerequisite Description Selection / User Factory setting entry / User interface Data logging status In the Data logging Displays the measured value • Done Done parameter, the Not logging status. • Delay active overwriting option is selected.
  • Page 131: Diagnostics And Troubleshooting

    Proline Promass P 300 HART Diagnostics and troubleshooting Diagnostics and troubleshooting 12.1 General troubleshooting For local display Error Possible causes Solution Local display dark and no output Supply voltage does not match the Apply the correct supply voltage signals value indicated on the nameplate.
  • Page 132 Diagnostics and troubleshooting Proline Promass P 300 HART Error Possible causes Solution Device shows correct value on local Configuration error Check and correct the parameter display, but signal output is configuration. incorrect, though in the valid range. Device measures incorrectly.
  • Page 133: 12.2 Diagnostic Information Via Light Emitting

    Proline Promass P 300 HART Diagnostics and troubleshooting Error Possible causes Solution Parallel WLAN and Ethernet • Check network settings. communication • Temporarily enable only the WLAN as an interface. Web browser frozen and operation Data transfer active Wait until data transfer or current no longer possible action is finished.
  • Page 134 Diagnostics and troubleshooting Proline Promass P 300 HART Color Meaning Flashing red Warning Not used – – Communication White Communication active Service interface (CDI) Yellow Connection established Flashing yellow Communication active No connection Endress+Hauser...
  • Page 135: Diagnostic Information On Local Display

    Proline Promass P 300 HART Diagnostics and troubleshooting 12.3 Diagnostic information on local display 12.3.1 Diagnostic message Faults detected by the self-monitoring system of the measuring device are displayed as a diagnostic message in alternation with the operational display. Operational display in alarm condition...
  • Page 136 Diagnostics and troubleshooting Proline Promass P 300 HART Diagnostic behavior Symbol Meaning Alarm • Measurement is interrupted. • Signal outputs and totalizers assume the defined alarm condition. • A diagnostic message is generated. Warning Measurement is resumed. The signal outputs and totalizers are not affected. A diagnostic message is generated.
  • Page 137: Calling Up Remedial Measures

    Proline Promass P 300 HART Diagnostics and troubleshooting 12.3.2 Calling up remedial measures X X X X X X X X X X X X X X 20.50 S801 Supply voltage Menu Diagnostic list Diagnostics 1 S801 Supply voltage Diagnostics 2...
  • Page 138: Calling Up Remedy Information

    Diagnostics and troubleshooting Proline Promass P 300 HART A0031056 Status area with status signal Diagnostic information→  136 Remedy information with Service ID In addition, diagnostic events which have occurred can be shown in the Diagnostics menu: • Via parameter •...
  • Page 139: 12.5 Diagnostic Information In Devicecare Or

    Proline Promass P 300 HART Diagnostics and troubleshooting 12.5 Diagnostic information in DeviceCare or FieldCare 12.5.1 Diagnostic options Any faults detected by the measuring device are displayed on the home page of the operating tool once the connection has been established.
  • Page 140: Calling Up Remedy Information

    Diagnostics and troubleshooting Proline Promass P 300 HART 12.5.2 Calling up remedy information Remedy information is provided for every diagnostic event to ensure that problems can be rectified quickly: • On the home page Remedy information is displayed in a separate field below the diagnostics information.
  • Page 141: Overview Of Diagnostic Information

    Proline Promass P 300 HART Diagnostics and troubleshooting Available status signals Configuration as per HART 7 Specification (Condensed Status), in accordance with NAMUR NE107. Symbol Meaning Failure A device error is present. The measured value is no longer valid. A0013956 Function check The device is in service mode (e.g.
  • Page 142 Diagnostics and troubleshooting Proline Promass P 300 HART Diagnostic Short text Remedy instructions Status Diagnostic number signal behavior [from the [from the factory] factory] Memory content 1. Restart device Alarm 2. Restore HistoROM S-DAT backup (' D evice reset' parameter) 3.
  • Page 143 Proline Promass P 300 HART Diagnostics and troubleshooting Diagnostic Short text Remedy instructions Status Diagnostic number signal behavior [from the [from the factory] factory] Sensor electronic (ISEM) 1. Restart device Warning faulty 2. Check if failure recurs 3. Replace sensor electronic module...
  • Page 144 Diagnostics and troubleshooting Proline Promass P 300 HART Diagnostic Short text Remedy instructions Status Diagnostic number signal behavior [from the [from the factory] factory] Simulation frequency Deactivate simulation frequency Warning output 1 to n output Simulation pulse output 1 Deactivate simulation pulse output...
  • Page 145: Pending Diagnostic Events

    Proline Promass P 300 HART Diagnostics and troubleshooting Diagnostic Short text Remedy instructions Status Diagnostic number signal behavior [from the [from the factory] factory] Partly filled pipe 1. Check for gas in process Warning 2. Adjust detection limits Input signal 1.
  • Page 146: Diagnostic List

    Diagnostics and troubleshooting Proline Promass P 300 HART Parameter overview with brief description Parameter Prerequisite Description User interface Actual diagnostics A diagnostic event has occurred. Shows the current occured diagnostic Symbol for diagnostic event along with its diagnostic behavior, diagnostic code information.
  • Page 147: 12.10.2 Filtering The Event Logbook

    Proline Promass P 300 HART Diagnostics and troubleshooting / ../Eventlist I1091 Config. change I1157 Mem.err. ev.list 0d01h19m10s F311 Electr. failure A0014008-EN  32 Taking the example of the local display • Max. 20 event messages can be displayed in chronological order.
  • Page 148 Diagnostics and troubleshooting Proline Promass P 300 HART Info number Info name I1092 Embedded HistoROM deleted I1111 Density adjust failure I1137 Electronic changed I1151 History reset I1155 Reset electronic temperature I1156 Memory error trend I1157 Memory error event list I1184...
  • Page 149: 12.11 Resetting The Measuring Device

    Proline Promass P 300 HART Diagnostics and troubleshooting Info number Info name I1624 Reset all totalizers I1625 Write protection activated I1626 Write protection deactivated I1627 Web server login successful I1628 Display login successful I1629 CDI login successful I1631 Web server access changed...
  • Page 150 Diagnostics and troubleshooting Proline Promass P 300 HART Navigation "Diagnostics" menu → Device information ‣ Device information →  150 Device tag →  150 Serial number Firmware version →  150 Device name →  150 Order code →  150 Extended order code 1 →...
  • Page 151: 12.13 Firmware History

    Proline Promass P 300 HART Diagnostics and troubleshooting Parameter Description User interface Factory setting Extended order code 1 Shows the 1st part of the extended order Character string – code.  The extended order code can also be found on the nameplate of the sensor and transmitter in the "Ext.
  • Page 152: Maintenance

    Maintenance Proline Promass P 300 HART Maintenance 13.1 Maintenance tasks No special maintenance work is required. 13.1.1 Exterior cleaning When cleaning the exterior of measuring devices, always use cleaning agents that do not attack the surface of the housing or the seals.
  • Page 153: Repairs

    Proline Promass P 300 HART Repairs Repairs 14.1 General notes 14.1.1 Repair and conversion concept The Endress+Hauser repair and conversion concept provides for the following: • The measuring devices have a modular design. • Spare parts are grouped into logical kits with the associated Installation Instructions.
  • Page 154: Disposal

    Repairs Proline Promass P 300 HART 14.5 Disposal 14.5.1 Removing the measuring device 1. Switch off the device. WARNING Danger to persons from process conditions. ‣ Beware of hazardous process conditions such as pressure in the measuring device, high temperatures or aggressive fluids.
  • Page 155: Accessories

    If using oil as a heating medium, please consult with Endress+Hauser.  For details, see Operating Instructions BA00099D 15.2 Communication-specific accessories Accessories Description Commubox FXA195 For intrinsically safe HART communication with FieldCare via the USB interface. HART  For details, see "Technical Information" TI00404F Endress+Hauser...
  • Page 156: Service-Specific Accessories

    Accessories Proline Promass P 300 HART HART Loop Converter Is used to evaluate and convert dynamic HART process variables to analog current HMX50 signals or limit values.  For details, see "Technical Information" TI00429F and Operating Instructions BA00371F Fieldgate FXA320 Gateway for the remote monitoring of connected 4 to 20 mA measuring devices via a Web browser.
  • Page 157: System Components

    Proline Promass P 300 HART Accessories 15.4 System components Accessories Description Memograph M graphic The Memograph M graphic display recorder provides information on all relevant display recorder measured variables. Measured values are recorded correctly, limit values are monitored and measuring points analyzed. The data are stored in the 256 MB internal memory and also on a SD card or USB stick.
  • Page 158: Technical Data

    Technical data Proline Promass P 300 HART Technical data 16.1 Application The measuring device is suitable for flow measurement of liquids and gases only. Depending on the version ordered, the measuring device can also measure potentially explosive, flammable, poisonous and oxidizing media.
  • Page 159: Input

    Proline Promass P 300 HART Technical data 16.3 Input Measured variable Direct measured variables • Mass flow • Density • Temperature Calculated measured variables • Volume flow • Corrected volume flow • Reference density Measuring range Measuring ranges for liquids Measuring range full scale values ...
  • Page 160 Technical data Proline Promass P 300 HART HART protocol The measured values are written from the automation system to the measuring device via the HART protocol. The pressure transmitter must support the following protocol-specific functions: • HART protocol • Burst mode...
  • Page 161: Output

    Proline Promass P 300 HART Technical data 16.4 Output Output signal HART current output Current output 4 to 20 mA HART Current span Can be set to: 4 to 20 mA (active/passive) Open-circuit voltage DC 28.8 V (active) Maximum input voltage...
  • Page 162 Technical data Proline Promass P 300 HART Pulse output Maximum input values DC 30 V, 250 mA (passive) Maximum output current 22.5 mA (active) Open-circuit voltage DC 28.8 V (active) Pulse width Adjustable: 0.05 to 2 000 ms Maximum pulse rate...
  • Page 163 Proline Promass P 300 HART Technical data Double pulse output Function Double pulse Version Open collector Can be set to: • Active • Passive Maximum input values DC 30 V, 250 mA (passive) Open-circuit voltage DC 28.8 V (active) Voltage drop For 22.5 mA: ≤...
  • Page 164 Technical data Proline Promass P 300 HART The following inputs and outputs are available for assignment: • Choice of current output: 4 to 20 mA (active), 0/4 to 20 mA (passive) • Pulse/frequency/switch output • Choice of current input: 4 to 20 mA (active), 0/4 to 20 mA (passive) •...
  • Page 165 Proline Promass P 300 HART Technical data Local display Plain text display With information on cause and remedial measures Backlight Red backlighting indicates a device error. Status signal as per NAMUR recommendation NE 107 Interface/protocol • Via digital communication: HART protocol •...
  • Page 166: Power Supply

    Technical data Proline Promass P 300 HART Dynamic variables Read out the dynamic variables: HART command 3 The measured variables can be freely assigned to the dynamic variables. Measured variables for PV (primary dynamic variable) • Mass flow • Volume flow •...
  • Page 167: Performance Characteristics

    Proline Promass P 300 HART Technical data Current consumption Transmitter • Max. 400 mA (24 V) • Max. 200 mA (110 V, 50/60 Hz; 230 V, 50/60 Hz) Power supply failure • Totalizers stop at the last value measured. • Configuration is retained in the plug-in memory (HistoROM DAT).
  • Page 168 Technical data Proline Promass P 300 HART Density (liquids) Under Standard density Wide-range 2) 3) reference operating conditions calibration Density specification [g/cm³] [g/cm³] [g/cm³] ±0.0005 ±0.01 ±0.002 Valid over the entire temperature and density range Valid range for special density calibration: 0 to 2 g/cm³, +10 to +80 °C (+50 to +176 °F) Order code for "Application package", option EF "Special density"...
  • Page 169 Proline Promass P 300 HART Technical data Accuracy of outputs The outputs have the following base accuracy specifications. Current output Accuracy ±5 µA Pulse/frequency output o.r. = of reading Accuracy Max. ±50 ppm o.r. (across the entire ambient temperature range) Repeatability o.r.
  • Page 170 Technical data Proline Promass P 300 HART [kg/m ] [°C] 40 80 120 160 200 240 280 320 360 400 [°F] -40 0 A0016610 Field density calibration, for example at +20 °C (+68 °F) Special density calibration Temperature ±0.005 · T °C (± 0.005 · (T – 32) °F)
  • Page 171: Installation

    Proline Promass P 300 HART Technical data Calculation of the maximum repeatability as a function of the flow rate Flow rate Maximum repeatability in % o.r. ⋅ ½ ZeroPoint ⋅ ³ BaseRepeat A0021340 A0021335 ⋅ ½ ZeroPoint ZeroPoint ⋅ ⋅...
  • Page 172: Process

    Technical data Proline Promass P 300 HART Vibration resistance • Vibration, sinusoidal according to IEC 60068-2-6 – 2 to 8.4 Hz, 3.5 mm peak – 8.4 to 2 000 Hz, 1 g peak • Vibration broad-band random, according to IEC 60068-2-64 –...
  • Page 173 Proline Promass P 300 HART Technical data Density 0 to 5 000 kg/m (0 to 312 lb/cf) Pressure-temperature An overview of the pressure-temperature ratings for the process connections is ratings provided in the "Technical Information" document Secondary containment The sensor housing is filled with dry inert gas and protects the electronics and mechanics pressure rating inside.
  • Page 174: 16.10 Mechanical Construction

    Technical data Proline Promass P 300 HART Pressure loss To calculate the pressure loss, use the Applicator sizing tool →  156 System pressure →  24 16.10 Mechanical construction Design, dimensions For the dimensions and installation lengths of the device, see the "Technical Information"...
  • Page 175 Proline Promass P 300 HART Technical data Cable entries/cable glands A0020640  33 Possible cable entries/cable glands Cable entry with M20 × 1.5 internal thread Cable gland M20 × 1.5 Adapter for cable entry with internal thread G ½" or NPT ½"...
  • Page 176 Technical data Proline Promass P 300 HART Seals Welded process connections without internal seals Accessories Protective cover Stainless steel, 1.4404 (316L) External WLAN antenna • WLAN antenna: ASA plastic (acrylic ester-styrene-acrylonitrile) and nickel-plated brass • Adapter: Stainless steel and copper Process connections •...
  • Page 177: 16.11 Operability

    Proline Promass P 300 HART Technical data 16.11 Operability Languages Can be operated in the following languages: • Via local operation English, German, French, Spanish, Italian, Dutch, Portuguese, Polish, Russian, Turkish, Chinese, Japanese, Korean, Arabic, Bahasa (Indonesian), Thai, Vietnamese, Czech, Swedish •...
  • Page 178 Technical data Proline Promass P 300 HART Via remote display and operating module DKX001 The remote display and operating module DKX001 is available as an optional extra: Order code for "Display; operation", option O "Separate backlit, 4-line display; 10 m (30 ft) Cable;...
  • Page 179 Proline Promass P 300 HART Technical data Service interface →  63 Supported operating tools Different operating tools can be used for local or remote access to the measuring device. Depending on the operating tool used, access is possible with different operating units and via a variety of interfaces.
  • Page 180 Technical data Proline Promass P 300 HART – Export parameter settings (.csv file, create documentation of the measuring point configuration) – Export the Heartbeat verification log (PDF file, only available with the "Heartbeat Verification" application package) – Flash firmware version for device firmware upgrade, for instance HistoROM The measuring device features HistoROM data management.
  • Page 181: 16.12 Certificates And Approvals

    Proline Promass P 300 HART Technical data Event list Automatic • Chronological display of up to 20 event messages in the events list • If the Extended HistoROM application package (order option) is enabled: up to 100 event messages are displayed in the events list along with a time stamp, plain text description and remedial measures •...
  • Page 182 Technical data Proline Promass P 300 HART The following types of monitoring in safety equipment are possible: • Mass flow • Volume flow • Density Functional Safety Manual with information on the SIL device →  185 HART certification HART interface The measuring device is certified and registered by the FieldComm Group.
  • Page 183: 16.13 Application Packages

    Proline Promass P 300 HART Technical data • EN 61010-1 Safety requirements for electrical equipment for measurement, control and laboratory use - general requirements • IEC/EN 61326 Emission in accordance with Class A requirements. Electromagnetic compatibility (EMC requirements). • NAMUR NE 21...
  • Page 184: 16.14 Accessories

    Technical data Proline Promass P 300 HART Heartbeat Technology Package Description Heartbeat Verification Heartbeat Monitoring +Monitoring Continuously supplies data, which are characteristic of the measuring principle, to an external condition monitoring system for the purpose of preventive maintenance or process analysis. These data enable the operator to: •...
  • Page 185: Technical Information

    Proline Promass P 300 HART Technical data Part 2 of 2: Transmitter Measuring device Documentation code Proline 300 KA01226D Technical Information Measuring device Documentation code Promass P 300 TI01276D Description of device parameters Measuring device Documentation code Promass 300 GP01057D...
  • Page 186 Technical data Proline Promass P 300 HART Contents Documentation code Heartbeat Technology SD01642D Concentration measurement SD01644D Installation Instructions Contents Documentation code  Installation Instructions for spare part sets Overview of accessories available for order →  155 Endress+Hauser...
  • Page 187: Index

    Index Index Current consumption ......167 Access authorization to parameters Read access ......55 Declaration of Conformity .
  • Page 188 Web server ......63 HART certification ......182 WLAN interface .
  • Page 189 Index Mounting tools ......28 Keypad lock Disabling ....... 55 Nameplate Enabling .
  • Page 190 Index Partially filled pipe detection (Wizard) ..101 Replacement Pulse/frequency/switch output ....85 Device components ..... . . 153 Pulse/frequency/switch output (Wizard) .
  • Page 191 Index Status signals ......135, 138 System design Storage conditions ......20 Measuring system .
  • Page 192 Index Current output ......82 Define access code ..... . . 113 Display .
  • Page 194 www.addresses.endress.com...

Table of Contents