Instructions For The Installer; Installation Of The Cooker - Belling BE444444690 User Manual

Freestanding cooker
Hide thumbs Also See for BE444444690:
Table of Contents

Advertisement

2.1. Instructions for the Installer

Ventilation requirements
• For rooms with a volume of less than
5 m
permanent ventilation of 100 cm
3
free area is required.
• For rooms with a volume of between 5
m
and 10 m
permanent ventilation of
3
3
50 cm
free area will be required, unless
2
the room has a door which opens
directly the outside air in which case no
permanent ventilation is required.
• For rooms with a volume greater than
10 m
no permanent ventilation is
3
required.
Important: Regardless of room size, all
rooms containing the appliance must have
direct access to outside air via an openable
window or equivalent.
Emptying of the burned gases from
environment
Gas appliances expel burned gas waste
to the outside air, either directly or via a
cooker hood with a chimney. If it is not
possible to install a cooker hood, install a
fan on the window or wall that has access
to fresh air. The fan must have the capacity
to change the volume of air in the kitchen a
minimum of 4-5 times per hour.
Air inlet section
min. 100 cm
Air inlet section
min. 100 cm
2
2
2
General instructions
• After removing the packaging material
from the appliance and its accessories,
ensure that the appliance is not
damaged. If you suspect any damage,
do not use it and contact an authorised
service person or qualified technician
immediately.
• Make sure that there are no flammable
or combustible materials in the close
vicinity, such as curtains, oil, cloth etc.
which may catch fire.
• The worktop and furniture surrounding
the appliance must be made of
materials resistant to temperatures
above 100°C.
• The appliance should not be installed
directly above a dishwasher, fridge,
freezer, washing machine or clothes
dryer.
• The appliance can be placed close to
other furniture on condition that in the
area where the
furniture's height does not exceed the
height of the cooktop.

2.2. Installation of the Cooker

• If the kitchen furniture is higher than the
cooktop, the kitchen furniture must be
at least 10 cm away from the sides of
appliance for air circulation.
• There should be a minimum 2cm blank
space around the appliance for air
circulation.
• If a cooker hood or any cupboard is to
EN - 12
Cooker
hood
flue
Air inlet section
min. 100 cm
2
Electrical ventilator
Air inlet section
min. 100 cm
2
appliance
is set up, the

Advertisement

Table of Contents
loading

This manual is also suitable for:

Be444444691Be444444692Be444444693Be444444694

Table of Contents