6.2.1 Parameter Modification
To modify the parameters of the sensor, refer to the following steps in the Production page.
1. Connect to the sensor (click "Link" to change the button into "Stop").
2. Stop syncing (click "Stop Sync" to change the button into "Sync").
3. Select the parameter or setting to be modified.
4. Start syncing (click "Sync" to change the button into "Stop Sync").
6.2.2 Saving and Loading
Refer to the following steps in the "Production" page.
Save Parameter: Click "Save Parameter" to select the path to be saved and enter the file
name. You can save the parameter data in the Production or Advance item to a file.
Load Parameter: You can copy saved parameter data to the current settings page. Refer
to the following steps.
1. Connect to the sensor (click "Link" to change the button into "Stop").
2. Stop syncing (click "Stop Sync" to change the button into "Sync").
3. Load the file (click "Load Parameter" to select the file to be loaded).
4. Start syncing (click "Sync" to change the button into "Stop Sync").
6.2.3 Output Function Selection
Hysteresis: Output is active when the sensitivity ≧ the "start point" setting, and reset
when the sensitivity ≦ the "reset point" setting.
Window: Output is active when the sensitivity is between the "start point" and "reset
point" settings, and reset when > the "start point" or <the "reset point" setting.
6.2.4 Output Delay Time Setting
Start Point Delay Time: This setting does not change any state when material contact is
detected by the sensor, and changes the output and LED state after the specified delay time.
Reset Point Delay Time: This setting does not change any state when material separation is
detected by the sensor, and changes the output and LED state after the specified delay time.
6.2.5 Fault Alarm Output Setting
When a fault occurs, output is executed according to the mode specified.
 OFF : The green LED light keeps flashing per second, and the output kept circuit
opening.
 ON : The green LED light keeps flashing per second. OUT1 and OUT2 will be switched in
ON and OFF by " but time of switching ON is always 0.5 second.
 When a fault alarm occurs, the following situations are possible:
The detection signal of the sensor is out of range.
The internal parameter settings are incorrect.