Dnp3 Implementation Table - ABB 630 Series Manual

Hide thumbs Also See for 630 Series:
Table of Contents

Advertisement

Section 3
DNP3 protocol implementation
3.2
Table 4:
Implementation table
OBJECT
Object
Variation
number
number
1
0
Binary input – any
1
1
(default)
1)
1
2
Binary input with status
2
1
Binary input change
2
2
Binary input change
2
3
Binary input change
with relative time
3
0
Double bit input – any
3
1
Double bit output
3
2
Double bit input with
4
0
Double bit input
change - any variation
4
1
Double bit input
change without time
4
2
Double bit input
change with time
4
3
Double bit input
change with relative
Table continues on next page
44

DNP3 implementation table

The following table identifies which object variations, function codes, and
qualifiers the IED supports in both request messages and in response messages. For
static (non-change-event) objects, requests sent with qualifiers 00, 01, 06, 07, or
08, will be responded with qualifiers 00 or 01. Requests sent with qualifiers 17 or
28 will be responded with qualifiers 17 or 28. For change-event objects, qualifiers
17 or 28 are always responded.
REQUEST (Slave will parse)
Function codes
Description
(dec)
1 (read)
variation
22 (assign class)
Binary input
1 (read)
1 (read)
1 (read)
without time
1 (read)
with time
1 (read)
1 (read)
variation
22 (assign class)
1 (read)
1 (read)
status
1 (read)
1 (read)
1 (read)
1 (read)
time
RESPONSE (Slave will respond with)
Function codes
Qualifier codes (hex)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
00, 01 (start-stop)
129 (response)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
00, 01 (start-stop)
129 (response)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
06 (no range, or all)
129 (response)
07, 08 (limited qty)
130 (unsol. resp)
06 (no range, or all)
129 (response)
07, 08 (limited qty)
130 (unsol. resp)
06 (no range, or all)
129 (response)
07, 08 (limited qty)
130 (unsol. resp)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17 ,27, 28 (index)
00, 01 (start-stop)
129 (response)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
00, 01 (start-stop)
129 (response)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
06 (no range, or all)
07, 08 (limited qty)
06 (no range, or all)
129 (response)
07, 08 (limited qty)
130 (unsol. resp)
06 (no range, or all)
129 (response)
07, 08 (limited qty)
130 (unsol. resp)
06 (no range, or all)
129 (response)
07, 08 (limited qty)
130 (unsol. resp)
1MRS756791 A
Qualifier codes
(dec)
(hex)
00, 01 (start-stop)
17, 28 (index)
00, 01 (start-stop)
17, 28 (index)
17, 28 (index)
17, 28 (index)
17, 28 (index)
00, 01 (start-stop)
17, 28 (index)
00, 01 (start-stop)
17, 28 (index)
17, 28 (index)
17, 28 (index)
17, 28 (index)
630 series