Viessmann VITOCROSSAL Service Instructions Manual page 59

Single boiler: 80 to 318 kw. twin boiler: 240 to 636 kw. gas condensing boiler with matrix cylinder burner. open flue and room sealed operation
Table of Contents

Advertisement

Heating circuit 1, heating circuit 2, heating...
Parameter address
With heating circuit pump logic function:
b5:...
Heating circuit pump "OFF"
3
RT
4
RT
5
RT
6
RT
7
RT
8
RT
Coding in the delivered condition
C5:20
Electronic minimum flow tempera-
ture limit 20 °C (only for weather-
compensated control units)
C6:74
Electronic maximum flow tempera-
ture limit 90 °C (only for weather-
compensated control units)
D3:14
Heating curve slope = 1.4
(only for weather-compensated
control units)
D4:0
Heating curve level = 0
(only for weather-compensated
control units)
D5:0
External operating program
changeover switches the operating
program to "Constant operation at
reduced room temperature" or
"Standby mode". (only for weather-
compensated control units)
D6:0
Heating circuit pump remains in
control mode at "External blocking"
signal.
D7:0
Heating circuit pump remains in
control mode at "External demand"
signal.
D8:0
No operating program changeover
via EA1 extension (only for weath-
er-compensated control units)
E1:1
Never adjust.
E2:50
With remote control: No display
correction of the actual room tem-
perature
E5:...
Never adjust.
RT
+ 3 K
>
actual
set
RT
+ 2 K
>
actual
set
RT
+ 1 K
>
actual
set
RT
>
actual
set
RT
- 1 K
>
actual
set
RT
- 2 K
>
actual
set
(cont.)
Heating circuit pump "ON"
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
Possible change
C5:1
Minimum limit adjustable from 1 to
to
127 °C (limited by boiler-specific pa-
C5:127
rameters)
C6:10
Maximum limit adjustable from 10 to
to
127 °C (limited by boiler-specific pa-
C6:127
rameters)
D3:2
Heating curve slope adjustable from
to
0.2 to 3.5 (see page 31)
D3:35
D4:–13
Heating curve level adjustable from
to
13 to 40 (see page 31)
D4:40
D5:1
The external operating program
changeover switches to "Continuous
operation with standard room tem-
perature" (subject to coding ad-
dresses 3A, 3B and 3C)
D6:1
Heating circuit pump stops at signal
"External blocking".
D6:2
Heating circuit pump starts at signal
"External blocking".
D7:1
Heating circuit pump stops at signal
"External demand".
D7:2
Heating circuit pump starts at signal
"External demand" (subject to cod-
ing addresses 3A, 3B and 3C)
D8:1
Operating program changeover via
input DE1 at EA1 extension
D8:2
Operating program changeover via
input DE2 at EA1 extension
D8:3
Operating program changeover via
input DE3 at EA1 extension
E2:0
Display correction
to
to
E2:49
Display correction
E2:51
Display correction +0.1 K
to
to
E2:99
Display correction +4.9 K
Code 2
+ 2 K
+ 1 K
- 1 K
- 2 K
- 3 K
5 K
0.1 K
59