Testing the static and supply pressure

Danger
CO formation can have serious health implica-
tions.
Always carry out a CO test before and after
work on gas appliances.
14
No
Fault EE
No
Shuts down below the set
boiler water temperature and
restarts immediately.
Fault E3
No
Fault EB
Fig. 3
(cont.)
Check setting for ionisation
electrode.
Purge the gas line.
Check the flue system for
tightness (flue gas recircula-
tion); check the gas flow
pressure.
Ensure adequate heat trans-
fer. Press reset button R.
Check gap between ionisa-
tion electrode and burner
gauze assembly.
Check allocation of gas type
(coding address 82, gas train
setting).
Check flue system; remove
flue gas recirculation if re-
quired.
Press reset button R.
Up to 80 kW
A