Coding
Code 2
(cont.)
Coding in the delivered condition
F7:25
In "Standby mode", the
internal circulation
pump is permanently
ON (only for constant
temperature control
units)
F8: 5
Temperature limit for
terminating the reduced
mode 5 ºC, see exam-
ple of page 103.
Observe the setting of
coding address "A3"
(only for weather com-
pensated control units)
F9: 14
Temperature limit for
raising the reduced set
room temperature
14 ºC, see example on
page 103 (only for
weather compensated
control units)
FA:20
Raising the set boiler
water temperature or
the set flow temperature
when changing from op-
eration with reduced
room temperature to op-
eration with standard
room temperature by
20 %. See example on
page 104 (only for
weather compensated
control units)
60
Possible change
F7:0
In "Standby mode", the
internal circulation pump
is permanently OFF
F7:1
In "Standby mode", the
to
internal circulation pump
F7:24
in operating mode will be
started 1 to 24 times per
day for 10 min respec-
tively.
F8:+10
Temperature limit adjus-
to
table from
F8: 60
+10 to 60 °C
F8: 61
Function disabled
F9:+10
Temperature limit adjus-
to
table from
F9: 60
+10 to 60 °C
FA:0
Temperature rise adjusta-
to
ble from 0 to 50%
FA:50