Coding

Code 1

Calling up code 1
Note
On weather compensated control
units, codes are displayed as plain
text.
Codes, which are irrelevant (due to
the system equipment level or the
setting of other codes) will not be
displayed.
For heating systems with one heat-
ing circuit without mixer and one
heating circuit with mixer, initially
the possible coding addresses "A0"
to "d4" are scrolled for the heating
circuit without mixer A1 and then
those for the heating circuit with
mixer M2.
Press the following keys:
1. K + L simultaneously for
approx. 2s.
Overview
Coding
Coding in the delivered condition
System designs
00:2
System version 1:
1 heating circuit without
mixer A1, with DHW
heating
42
2. a/b
for the required coding
address; the address
flashes
3. d
to confirm
4. a/b
for the selected value
5. d
to confirm; the display
briefly shows "accepted"
(weather compensated
control unit); the address
flashes again.
6. a/b
for the selection of further
addresses.
7. K + L approx. 1 s simulta-
neously, to terminate
coding 1.
Possible change
00:4
System version 2, 5:
1 heating circuit with
mixer M2, with DHW
heating
00:6
System version 3, 4:
1 heating circuit without
mixer A1 and 1 heating
circuit with mixer M2, with
DHW heating