Assembly Speed-Bus - YASKAWA VIPA 300S Manual

Hide thumbs Also See for VIPA 300S:
Table of Contents

Advertisement

Chapter 1 Assembly and installation guidelines

Assembly SPEED-Bus

For the deployment of SPEED-Bus modules, a pre-manufactured SPEED-
Pre-manufactured
Bus rail is required. This is available mounted on a profile rail with 2, 6 or
SPEED-Bus
10 extension plug-in locations.
profile rail
Installation of the
profile rail
65mm
CPU
SLOT2
SLOT1
DCDC
40mm
Profile rail
G
1-4
All manuals and user guides at all-guides.com
SLOT6
SLOT5
SLOT4
• Bolt the profile rail with the background (screw
size: M6), so that you still have minimum 65mm
space above and 40mm below the profile rail.
• Please look for a low-impedance connection
between profile rail and background
• Connect the profile rail with the protected earth
conductor.
The minimum cross-section of the cable to the
protected earth conductor has to be 10mm
CPU
SLOT2
SLOT1
DCDC
Order number
VIPA 390-1AB60
VIPA 390-1AE80
VIPA 390-1AF30
VIPA 390-1AJ30
VIPA 390-9BC00*
VIPA 391-1AF10
VIPA 391-1AF30
VIPA 391-1AF50
VIPA 391-1AF80
* Unit pack 10 pieces
Manual VIPA System 300S SPEED7
CPU
SLOT3
SLOT2
SLOT1
DCDC
SPEED-
Bus Slot
-
160mm
-
482mm
-
530mm
-
830mm
-
2000mm
2
530mm
6
530mm
10
530mm
16
830mm
HB140E - PS - RE_307-1FB70 - Rev. 13/43
2
.
A
B
C
140mm
10mm
466mm
8,3mm
500mm
15mm
800mm
15mm
-
15mm
500mm
15mm
500mm
15mm
500mm
15mm
800mm
15mm