Viessmann VITOLIGNO 300-S Operating Instructions Manual page 55

High performance wood gasification boiler for split logs up to 50 cm long
Hide thumbs Also See for VITOLIGNO 300-S:
Table of Contents

Advertisement

Approved logs
For combustion in the Vitoligno 300-S, the following
requirements apply for logs, such as split or round
logs:
Property class
Diameter
Length for Vitoligno 300-S with 33, 49, 60
and 75 kW
Water content
Approved wood in small pieces
A proportion of the wood fuel may be wood in small pieces as described below.
Coarse woodchips:
Class B1/P31S/M20/A0.8 (properties to
EN ISO 17225-4)
Joinery waste:
Glued wood and wood remnants
Must not be coated in or contain wood preservative.
Non-approved fuels
Danger
The use of unsuitable fuels leads to risk of poi-
soning. Burning waste or wood that has been
treated with timber preservatives or has been
coated with materials containing organic halo-
genated compounds creates highly poisonous
flue gases.
Only use permissible fuels.
!
Please note
If unsuitable fuels are used, there is a risk of
damaging the heating system. Burning waste or
wood that has been treated with timber preser-
vatives or has been coated with materials con-
taining organic halogenated compounds may
result in serious corrosion damage in the boiler.
Only use permissible fuels.
To EN ISO 17225-5
B
D15
L50
M20
The edge length must be > 5 cm.
Wood briquettes
The following must never be burnt:
anthracite and coke
Wood waste coated in materials made of organic
halogenated compounds (PVC)
Wood pellets
Ordering fuel
Additional details
Hardwood: 5 to 15 cm
Softwood: 5 to 12 cm
Max. 50 cm
Max. 20 %
55