Rheem RAYPAK MVB 504 Installation & Operating Instructions Manual page 35

Table of Contents

Advertisement

Item
Boil Target
Boil Max
Boil Min
'Burner' Delay
Boil Mass
Diff
DHW Target
DHW Diff
'Pump' Dly
Units
Mode
External Input Signal
Offset
Table S: Modulating Temperature Control Default Setpoints—Water Heater
EXTERNAL INPUT SIGNAL – Selects external input
signal range (0-10VDC or 2-10VDC):
0-10VDC or 0-20 mA external input signal – When
the 0-10VDC signal is selected, an input voltage of 1
VDC corresponds to a boiler target temperature of
50°F (10°C). An input voltage of 10 VDC corresponds
to a boiler target temperature of 220°F (104°C). As the
voltage varies between 1 VDC and 10 VDC, the boiler
target temperature varies linearly between 50°F
(10°C) and 220°F (104°C) (refer to Table O). If a volt-
age below 0.5 VDC is received, the boiler target
temperature is displayed as "– – –" indicating that
there is no longer an internal call for heat. A 0-20 mA
signal can be converted to a 0-10 VDC signal by
installing a 500 Ω resistor on the external input signal
device's terminals.
2-10VDC or 4-20 mA external input signal – When
the 2-10VDC signal is selected, an input voltage of 2
VDC corresponds to a boiler target temperature of
50°F (10°C). An input voltage of 10 VDC corresponds
to a boiler target temperature of 220°F (104°C). As the
voltage varies between 2 VDC and 10 VDC, the boiler
target temperature varies linearly between 50°F
(10°C) and 220°F (104°C) (refer to Table P). If a volt-
age below 1.5 VDC is received, the boiler target
temperature is displayed as "– – –" indicating that
there is no longer an internal call for heat. A 4-20 mA
signal can be converted to a 2-10 VDC signal by
All manuals and user guides at all-guides.com
Water Heater (WH1)
Modes
2
3, 7
2, 3, 6, 7
2, 3, 7
All
All
2, 3, 7
3
3
All
All
N/A
7
7
Default Setting
140°F
160°F
180°F
135°F
0:00 min
1 (Low)
1 (Low), 2 (Med), 3 (High)
Auto
120°F
5°F
3:00 min
OFF, 0:20 to 9:55 min, ON
°F
3
2 to 10 VDC
2 to 10 VDC or 0 to 10 VDC
0°F
installing a 500 Ω resistor on the external input signal
device's terminals.
FP - Flame proof warning.
MODE - Operating mode of the heater.
OFFSET - The Offset setting allows the boiler target
temperature to be fine tuned to the external input sig-
nal. The control reads the external input signal and
converts this to a boiler target temperature. The Offset
setting is then added to the boiler target temperature.
OUTDR - Outdoor air temperature.
OUTDR DESIGN - Design outdoor air temperature
used in the heat loss calculation.
OUTDR START - Starting outdoor air temperature.
PUMP DLY - Sets the operating time of the pump once
the CFH is satisfied.
TANK - Current DHW tank temperature (Mode 3).
TANK DIFF - Storage tank differential (Mode 3).
TANK TARGET - Target temperature in the DHW
storage tank (Mode 3).
35
Range
OFF, 70 to 190°F
OFF, 70 to 190°F
OFF, 120 to 190°F
OFF, 80 to 180°F
0:00 to 3:00 min
Auto, 2 to 42°F
OFF, 70 to 190°F
2 to 10°F
°F or °C
2, 3, 7
-10°F to 10°F