Rheem RAYPAK MVB 504 Installation & Operating Instructions Manual page 28

Table of Contents

Advertisement

NOTE: While a drain connection is required in the
vent of all Cat. III horizontal MVB installations, the
drain can be accomplished in several different ways.
The figures in this manual show the drain in a vent
tee, however, this can also be accomplished using
an inline collector for condensing stacks or an inline
vertical or horizontal collector available from several
of the listed vent manufacturers.
Fig. 27: Horizontal Through-the-Wall Direct Venting
CAUTION: This venting system requires the
installation of a condensate drain in the vent piping
per the vent manufacturer's instructions. Failure to
install a condensate drain in the venting system will
void all warranties on this heater.
Installation
These installations utilize the heater-mounted blower
to vent the combustion products to the outdoors.
Combustion air is taken from inside the room and the
vent is installed horizontally through the wall to the out-
doors. Adequate combustion and ventilation air must
be supplied to the equipment room in accordance with
the NFGC (U.S.) or B149 (Canada).
The total length of the horizontal through-the-wall flue
system should not exceed 75 equivalent ft in length. If
horizontal run exceeds 75 equivalent ft, an appropri-
ately sized variable-speed extractor must be used.
Each elbow used is equal to 10 ft of straight pipe. This
will allow installation in one of the four following
arrangements:
All manuals and user guides at all-guides.com
The vent cap is not considered in the overall length of
the venting system.
The vent must be installed to prevent flue gas leakage.
Care must be taken during assembly to ensure that all
joints are sealed properly and are airtight. The vent
must be installed to prevent the potential accumulation
of condensate in the vent pipes. It is required that:
1. The vent must be installed with a condensate
2. The vent must be installed with a slight upward
3. The vent must be insulated through the length of
Termination
The flue direct vent cap MUST be mounted on the ex-
terior of the building. The direct vent cap cannot be
installed in a well or below grade. The direct vent cap
must be installed at least 1 ft above ground level and
above normal snow levels. The Raypak-approved
stainless steel flue direct vent cap must be used (sales
order option D-15). The vent terminal must be located
NO CLOSER than 12" off the wall.
WARNING: No substitutions of flue pipe or vent
cap material are allowed. Such substitutions would
jeopardize the safety and health of inhabitants.
Direct Vent—Vertical
Installation
These installations utilize the heater-mounted blower
to draw combustion air from outdoors and force the
heated flue products through the vent pipe under posi-
tive pressure. The vent material must be in
accordance with the above instructions for vent mate-
rials. Vent material must be listed by a nationally
recognized test agency.
The connection from the appliance flue to the stack
must be as direct as possible and should be the same
size or larger than the vent outlet.
28
75' of straight flue pipe
65' of straight flue pipe and one elbow
55' of straight flue pipe and two elbows
45' of straight pipe and three elbows
drain located in proximity to the heater as directed
by the vent manufacturer.
slope of not less than 1/4 inch per foot of horizon-
tal run to the vent terminal.
the horizontal run.

Advertisement

Table of Contents
loading

Table of Contents