Item
Boil Target
Boil Max
Boil Min
'Burner' Delay
Boil Mass
Diff
DHW Target
DHW Diff
'Pump' Dly
Outdr Start
Outdr Design
Boil Start
Boil Dsgn
WWSD
Units
Mode
External Input Signal
Offset
Table Q: Temperature Control Default Setpoints—Boiler
Item
Boil Target
Boil Max
Boil Min
'Burner' Delay
Boil Mass
Diff
'Pump' Dly
Units
Mode
Table R: Temperature Control Default Setpoints—Pool Heater
Boiler (H7)
Modes
Default Setting
2
140°F
3
160°F
5, 7
180°F
2, 5, 7, 8
200°F
3
180°F
2, 3, 5, 7
135°F
All
0:00 min
All
1 (Low)
2, 3, 5, 7
Auto
3
120°F
3
5°F
All
3:00 min
5
70°F
5
-10°F
5
135°F
5
180°F
5
70°F
All
°F
N/A
2
7
2 to 10 VDC
7
0°F
Pool Heater (P, WHP)
Modes
Default Setting
2
78°F
2
86°F
2
70°F
All
0:00 min
All
1 (Low)
2
1°F
All
3:00 min
All
°F
N/A
2
34
Range
OFF, 70 to 220°F
OFF, 70 to 190°F
OFF, 70 to 220°F
OFF, 120 to 225°F
OFF, 120 to 190°F
OFF, 80 to 180°F
0:00 to 3:00 min
1 (Low), 2 (Med), 3 (High)
Auto, 2 to 42°F
OFF, 70 to 190°F
2 to 10°F
OFF, 0:20 to 9:55 min, ON
35 to 85°F
-60 to 32°F
35 to 150°F
120 to 220°F
35 to 100°F
°F or °C
2, 3, 5, 7, 8
2 to 10 VDC or 0 to 10 VDC
-10°F to 10°F
Range
OFF, 45 to 106°F
OFF, 70 to 106°F
OFF, 45 to 106°F
0:00 to 3:00 min
1 (Low), 2 (Med), 3 (High)
1 to 3°F
OFF, 0:20 to 9:55 min, ON
°F or °C
2