(2) Indoor Unit
Power source
✻ 1
Cooling capacity
Power consumption
Current
External finish
Height
Dimensions
Width
Depth
Net weight
Heat exchanger
Type
Airflow rate
Fan
External static
pressure
Type
Motor
Output
Starting current
Air filter
Gas
(Flare)
Refrigerant
pipe dimension
Liquid
(Flare)
Drain pipe dimension
✻ 2
Noise level (Lo-Mid2-Mid1-Hi)
Note: ✻1 Cooling capacity indicates the maximum value at operation under the following conditions;
Indoor 27˚CDB/19˚CWB, Outdoor 35˚CDB
✻2 Measured in an anechoic room.
PFD-P250VM-A
kW
28.0
kW
2.5
A
5.5/5.3/5.1
mm
mm
1,200
mm
kg
350
Sirocco fan
160
m
3
/min
Pa
kW
3.7
A
60
mm
ø 28.58
mm
ø 12.7
dB(A)
59
3
3N~380-415V 50Hz / 3N~400-415V 60Hz
<5Y 7/1>
1895
800
Cross fin (Aluminum-plate fin and copper tube)
120
3 phases induction motor
PP Honeycomb fabric
Rp1
PFD-P500VM-A
56.0
5.0
9.5/9.0/8.7
1,800
480
Sirocco fan ✕ 2
320
5.5
75
ø 28.58 ✕ 2
ø 12.7 ✕ 2
64