WARNING/ALARM 35, Out of frequency range:
This warning is active if the output frequency has reached the high limit (set in parameter 4-53)
or low limit (set in parameter 4-52). In
Mode
, this warning is displayed.
WARNING/ALARM 36, Mains failure
This warning/alarm is only active if the supply voltage to the adjustable frequency drive is lost
and par. 14-10
ALARM 38, Internal fault
It may be necessary to contact your Danfoss supplier. Some typical alarm messages:
0
256-258 Power EEPROM data is defective or too old
512
513
514
515
516
517
518
519
783
1024-12
79
1281
1282
1283
1284
1299
1300
1301
1302
1315
1316
1317
1318
1379
1380
1381
1382
1536
ALARM 39, Heatsink sensor
No feedback from the heatsink temperature sensor.
The signal from the IGBT thermal sensor is not available on the power card. The problem could
be on the power card, on the gate drive card, or the ribbon cable between the power card and
gate drive card.
®
FC Series
Line Failure
is NOT set to OFF. Check the fuses to the adjustable frequency drive
Serial port cannot be initialized. Serious
hardware failure
Control board EEPROM data is defective or
too old
Communication time out reading EEPROM
data
Communication time out reading EEPROM
data
Application Orientated Control cannot rec-
ognize the EEPROM data
Cannot write to the EEPROM because a
write command is on progress
Write command is under timeout
Failure in the EEPROM
Missing or invalid Barcode data in EEPROM
Parameter value outside of min/max limits
A CAN message that must be sent, couldn't
be sent
Digital Signal Processor flash timeout
Power micro software version mismatch
Power EEPROM data version mismatch
Cannot read Digital Signal Processor soft-
ware version
Option SW in slot A is too old
Option SW in slot B is too old
Option SW in slot C0 is too old
Option SW in slot C1 is too old
Option SW in slot A is not supported (not
allowed)
Option SW in slot B is not supported (not
allowed)
Option SW in slot C0 is not supported (not
allowed)
Option SW in slot C1 is not supported (not
allowed)
Option A did not respond when calculating
Platform Version.
Option B did not respond when calculating
Platform Version.
Option C0 did not respond when calculating
Platform Version.
Option C1 did not respond when calculating
Platform Version.
An exception in the Application Orientated
Control is registered. Debug information
written in LCP
MG.90.L1.22 - VLT
®
is a registered Danfoss trademark
Process Control, Closed-loop
1792
DSP watchdog is active. Debugging of
power part data Motor Orientated Control
data not transferred correctly
2049
Power data restarted
2064-207
H081x: option in slot x has restarted
2
2080-208
H082x: option in slot x has issued a pow-
8
er-up wait
2096-210
H083x: option in slot x has issued a legal
4
power-up wait
2304
Could not read any data from power EE-
PROM
2305
Missing SW version from power unit
2314
Missing power unit data from power unit
2315
Missing SW version from power unit
2316
Missing io_statepage from power unit
2324
The power card configuration is deter-
mined to be incorrect at power-up
2325
A power card has stopped communicating
while main power is applied
2326
The power card configuration is deter-
mined to be incorrect after the power
card register delay.
2327
Too many power card locations have
been registered as present.
2330
Power size information between the pow-
er cards does not match.
2561
No communication from DSP to ATACD
2562
No communication from ATACD to DSP
(state running)
2816
Stack overflow of control board module
2817
Scheduler slow tasks
2818
Fast tasks
2819
Parameter thread
2820
LCP Stack overflow
2821
Serial port overflow
2822
USB port overflow
2836
cfListMempool to small
3072-512
Parameter value is outside its limits
2
5123
Option in slot A: Hardware incompatible
with control board hardware
5124
Option in slot B: Hardware incompatible
with control board hardware
5125
Option in slot C0: Hardware incompatible
with control board hardware
5126
Option in slot C1: Hardware incompatible
with control board hardware
5376-623
Out of memory
1