WPLLD Site Prep and Installation Guide
Pressurstat
Assembly
Red Jacket Quantum Pump (w/ and w/o SpikeCheck Valve Assy.)
OFF
1. Turn Off, tag, and lockout power to pump.
2. After referring to Figure 4-9 remove the Line Test Port plug, the Pressurstat (if installing a SpikeCheck), and the
cover from the pump's capacitor housing (do not discard cover).
Cover - remove for
WPLLD Transducer &
Adaptor
Warning Tag
Figure 4-8. WPLLD Transducer Installation--Red Jacket Pump w/o SwiftCheck
wplld/quantumw1.eps
Red Jacket Quantum Pump (w/ and w/o SpikeCheck Valve Assy.)
Sensing Line
Wireless Line Leak Sensor
6-32 x .375 Thread-Forming
Screws (2)
Capacitor Cover
Snapped in Bracket
Line Test Port
wplld\rjnosck.eps
Line Test Port -
remove plug for
Sensing Line
fitting
If installing SpikeCheck assy.
(Red Jacket P/N 388-080-5)
remove Pressurstat valve assy.
and replace with SpikeCheck
following Red Jacket's instructions.
4-7
Capacitor
Cover
Bracket
Tank Test Port
Figure 4-9. Red Jacket Quantum Pump