Sensor Field Wiring; Sealing Field Connections; Wiring Run Through Rigid Conduit; Figure 3. Def Temperature Sensor And Recirculating Return Valve Example Installation - Veeder-Root DEF Installation Manual

Recirculation control
Table of Contents

Advertisement

Installation
.

Figure 3. DEF Temperature Sensor And Recirculating Return Valve Example Installation

Sensor Field Wiring

Figure 4 contains diagrams for connecting, at the field junction box, cables from the sensor to cables from the
console. Check diagrams closely for polarity requirements.
To Console

Sealing Field Connections

WIRING RUN THROUGH RIGID CONDUIT

1. Pull the wires from the sensor into the junction box. Pull the two wires from the console through the seal-off
box, the conduit attaching the junction box to the seal-off box and into the junction box.
2. Using wire nuts, connect the two wires from the sensor to the two wires coming from the console. Be sure to
observe color codes or tags when making these connections so that the sensor outputs are attached to the
correct terminals in the console and that polarity is maintained when required.
3. Seal wire nuts with epoxy sealant following the instructions in Figure 5.
DEF Tank Sump
DEF Flow
To Dispensers
DEF Return
Flow To Tank
Seal-off
1/2'' rigid
conduit

Figure 4. Field Wiring Sensor Cable To Console Cable

99
DEF Pump
Return Shut-off Valve
(Customer Supplied)
Black
Black
White
Brown
Epoxy sealed connections in a
weatherproof junction box
Sensor Field Wiring
From
Sensor