CODE
NR9001
Digital fan coil controller with Modbus sensors
STA60M
Modbus 24 Vac/dc temperature sensor
STA60MP
Flush-mounting Modbus 24 Vac/dc temperature sensor
STA60M-2
Wall mounting Modbus 24 Vac/dc temperature sensor
STA60MP-2
Flush-mounting Modbus 230 Vac temperature sensor
STA70M
Wall mounting remote 24 Vac/dc touch sensor
APPLICAZIONE ED USO
NR9001 is a digital controller for 2- or 4-pipe terminal units (eg. Fan
Coil) with ON/OFF, 3-POINT floating or modulating control valves as
well as with 3-speed or modulating fan. NR9001 is equipped with
Modbus (SLAVE) communication protocol enabling the communi-
cation with other Modbus devices (MASTER).
NR9001 is also equipped with a second Modbus communication bus
dedicated to communicating with the sensors placed in the envi-
ronment.
NR9001 is composed of an M6 module for DIN rail mounting and can
be equipped with Modbus room sensors STA60M or STA70M.
TECHNICAL CHARACTERISTICS
Power supply NR9001:
Protection Degree:
Operation temperature:
Storage temperature:
NR9001 controller inputs
Digital Input (DI1)
Digital Input (DI2)
Digital Input (DI3)
Digital Input (DI4)
Analogue Input (S1)
Analogue Input (S2)
Analogue Input (S3)
Analogue Input (S4)
Remote Power off" or "Comfort/Economy" digital inputs can be
(1)
used to interface the controller with a Presence Detector to mini-
mize costs for heating and cooling.
When digital inputs are in use they have priority on remote sensor
and supervisory system. If, on the configurator is enabled "BADGE"
function, the digital input DI4 loses its meaning, while the digital
input DI2 enables the electrical loads and switches the operating
mode between Comfort and Economy.
Sensors with a sensing element NTC10K Ohm @ 25°C.
(2)
Accuracy ± 1K, β @ 25°C = 3435
(reference Controlli room sensors S4xxA/B and SNTC-xL)
S3 and S4 inputs have a different meaning if "changeover auto"
(3)
(instead of "Aux Loop") function is disabled from the configuration
tool. S4 sensor is used to switch the controller operation mode to
Controlli S.p.A.
16010 Sant'Olcese (GE)
Tel. 010 73 06 1
Fax. 010 73 06 870/871
www.controlli.eu
DESCRIPTION
85-265 Vac (isolated);
IP 20;
2T45°C;
-25T65°C.
Window Contact
Remote Power off / Badge
(1)
Winter/Summer Change Over-
Comfort/Economy
(1)
Return Temperature Sensor
(2)
Remote Temperature Set
(2)
Auxiliary loop sensor
(3) (2)
Auxiliary loop set selector
(3) (2)
The device contains electrical and electronic components and is not allowed to be disposed
of as household refuse. All locally valid regulations and requirements must be observed.
1
Issue
st
NR9001
STA60MP
Summer or Winter on the basis of the fluid temperature and for fan
minimum limit function. As an alternative this function can be asso-
ciated to S3 sensor (if present). S3 sensor is used as minimum limit to
hold the fun if fluid is not warm.
Digital inputs can be enabled using a configuration tool called
"Configuratore NR9001" thanks to which you can also reverse the in-
puts action. It can be downloaded by our web site www.controlli.eu.
The default status of digital inputs (factory setting) is the following:
DIGITAL INPUT
DEFAULT
WINDOW CONTACT
N.C.(normally closed)
(4)
REMOTE POWER
N.O.(normally open)
OFF
(4)
WINTER/SUMMER
N.O.(normally open)
CHANGEOVER
COMFORT/
N.O.(normally open)
ECONOMY
(4)
These inputs are disabled by default (except winter/summer
(4)
changeover, look at table page 16). If you need to enable them
a supervisory system is required.
See Badge function
(5)
For example, in case the window switch is normally opened (closed
window is equivalent to open contact), it is necessary to reverse the
action of the digital input.
NR9001 outputs
06/2019
DBL585e
NR9001
STA70M
DESCRIPTION
OPEN – window opened
CLOSED – window closed
OPEN – comfort
CLOSED – off (frost
protection)
(5)
OPEN – Winter
CLOSED – Summer
APERTO – comfort
CHIUSO – economy
(5)
Page 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the NR9001 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Controlli NR9001

  • Page 1 Wall mounting remote 24 Vac/dc touch sensor APPLICAZIONE ED USO NR9001 is a digital controller for 2- or 4-pipe terminal units (eg. Fan Coil) with ON/OFF, 3-POINT floating or modulating control valves as well as with 3-speed or modulating fan. NR9001 is equipped with Modbus (SLAVE) communication protocol enabling the communi- cation with other Modbus devices (MASTER).
  • Page 2: Installation

    Standard CEI EN 61010-1 and CEI EN 60730-2-9 for LVD directive. INSTALLATION Installation of NR9001 controller NR9001 are suitable for mounting on a DIN rail with a quick coupling. Connections shall be in compliance with existing rules and using max 2,5 mm...
  • Page 3 CONN # pin Signal Direction Type of signal Description input 85-265Vac phase Power supply input 85-265Vac neutral Power supply HOT_CL output 24..230Vac TRIAC 4A Hot 4-pipe - heat/cool 2-pipe 3P valve (close) HOT_COM output 24..230Vac TRIAC COM Common HOT_OP output 24..230Vac TRIAC 4A Hot 4-pipe - heat/cool 2-pipe 3P valve (open) - ON/OFF COLD_CL...
  • Page 4: Wiring Diagrams

    WIRING DIAGRAMS Example of 4-pipe plant with 230V 3-point valves * Or fan min. limit ** Or Changeover Auto *** Or Badge input Example of 4-pipe plants with 230V ON/OFF valves * Or fan min. limit ** Or Changeover Auto *** Or Badge input Issue 06/2019...
  • Page 5 Example of 4-pipe plants with 24V 3-point valves * Or fan min. limit ** Or Changeover Auto *** Or Badge input Example of 4-pipe plant with 24V ON/OFF valves * Or fan min. limit ** Or Changeover Auto *** Or Badge input Issue 06/2019 DBL585e...
  • Page 6 Example of 2-pipe plant with 230V 3-point valves * Or fan min. limit ** Or Changeover Auto *** Or Badge input Example of 2-pipe plant with 230V ON/OFF valves * Or fan min. limit ** Or Changeover Auto *** Or Badge input Issue 06/2019 DBL585e...
  • Page 7 Example of 2-pipe plant with 24V 3 points valves * Or fan min. limit ** Or Changeover Auto *** Or Badge input Example of 2-pipe plant with 24V ON/OFF valves * Or fan min. limit ** Or Changeover Auto *** Or Badge input Issue 06/2019 DBL585e...
  • Page 8: Operation

    OPERATION PC Supervisor: configuration tool “Configuratore NR9000” down- loadable from www.controlli.eu site; in this case it is possible to connect up to 250 controllers. It is possible to use also Micronet View or Touch Screen GTO series on demand getting in touch The internally stored parameters used by the controller during op- with our technical dept.;...
  • Page 9: Controller Functions

    20°C with dead zone = 1K. The output will be available Operation modes in OC2 and it will exclude the management of the electrical coil. NR9001 works with 3 different operation modes: Air recirculation function COMFORT: the controller will control the temperature (driving This function manages the minimum fan speed.
  • Page 10 Valve proportional band ON/OFF = 1 Plant = 2 pipes Loop = heating Control modes NR9001 works with 8 different control modes selectable via dip switch or by supervisory system: ON/OFF Valves and 3-speed fan (“FAST” operation mode - Oper- ation Diagram 1).
  • Page 11 ON/OFF Valves and 3 Speed FAN - “FAST” operation mode The valves are activated in ON-OFF mode with a hysteresis. Speed 1 is ON when the error (E) is greater than 10%. TSET-T E % = ----------- * 100 Speed 2 and 3 follow to the Propor- tional Band as shown in the diagram aside.
  • Page 12 ON/OFF valves and 1 Speed FAN The valves are activated in ON- OFF mode with hysteresis. Speed 1 follows to the Proportion- al Band as shown in the diagram aside. Proportional Valves (3 point or 0-10V) and 3-speed fan The valves are activated in Pro- portional mode (0-100%) using a proportional band.
  • Page 13 Proportional Valve (0-10V) and Proportional Speed Fan (0-10V) (2-pipe plant) The valves are activated in Pro- portional mode (0-100%) using the set proportional band, (heat- ing during winter, cooling during summer). Fan speeds follow the Proportion- al Band as shown in the diagram aside generating a 0-10V output control signal.
  • Page 14: Configuration Diagram

    NR9001 CONTROLLER DIP SWITCHES AND LEDs DIP switches 5-7 settings CONFIGURATION DIAGRAM DIP 5 DIP 6 DIP 7 The controller has 8 DIP switches accessible by removing the top co- ver and 2 LEDs to identify the state of the valves (open or closed) and ON/OFF Valves and 3 FAN speed (factory the communication anomalies.
  • Page 15: Default Parameters

    DEFAULT PARAMETERS The controller is released with the DIP switches in OFF position (2-pipe, Modbus Address 1, ON / OFF valves and 3 fan speed) and with regu- lation parameters shown in the following table: Parameter Vmin Vmax Default Hot Loop Set Point 100 (10°C) 350 (35°C) 200 (20°C) Stroke Time for 3 Points actuators...
  • Page 16 Temperature display in “big area” and CLOCK key “disabled” with Set adjustable + - X (X defined by configurator X maximum 5 °C). “STATUS WORD” parameter STA70M VALUE CONFIGURAZIONE Temperature display Setpoint display “STATUS WORD” parameter NR9001 Description “0” “1” Default Remote (Disable digital input Comfort/ Local (Enable digital input Comfort/...
  • Page 17 Press the knob to set the first time band: a sym- bol representing it flashes on the right. STA60M sensor, in order to be connected to the 485 bus of the NR9001 controller, requires a preconfiguration with regard to the communi- cation speed and the Modbus address.
  • Page 18 STA70M sensor is a room terminal that allows the user to control the temperature in a residential environment. It communicates with the Modbus protocol and can be connected to the NR9001 controller. The power supply can be 24 Vac/dc. Setting Communication Parameters...
  • Page 19 The sensor will read the configuration from the controller at start-up. of the parameters of Set Warm, Dead Zone and Reduction on the controller. After setting the display type, switch the NR9001 controller off and NOTE: the modification of one of the economy sets is also reflected on again.
  • Page 20 Management of the Modbus address of the controller STA70M sensor allows you to view and modify (Settings page -> Pa- ram) the Modbus address of the NR9001 controller stored in EEPROM memory. The address can be changed only if the controller Dipswitch is not active.
  • Page 21: Dimensions (Mm)

    DIMENSIONS [mm] STA70M NR9001 STA60M / STA60M-2 STA60MP / STA60MP-2 8 22,55 The performances stated in this sheet can be modifi ed without any prior notice Issue 06/2019 DBL585e Page 21...