Energon-fan coil digital controller
Hide thumbs Also See for NR9000:

Advertisement

Quick Links

Energon - Fan Coil Digital Controller
APPLICATION AND USE
NR9000 is a digital controller for 2- or 4-pipe terminal units (eg.
Fan Coil) with ON/OFF, 3-POINT floating or modulating con-
trol valves as well as with 3-speed or modulating fan. NR9000
is equipped with MODBUS (SLAVE) communication protocol
enabling the communication with other MODBUS devices (MA-
STER).
NR9000 is composed by a M6 DIN-BAR unit and a flush
mounting remote terminal (NR9000-RT) with integrated room
terminal sensor.
NR9000 and NR9000-RT do not have internal clock manage-
ment. Time schedule must be programmed by a supervisory
system.
TECHNICAL CHARACTERISTICS
Power supply:
Protection Degree:
Operation temperature:
Storage temperature:
Dimensions (mm):
Inputs:
Digital Input
Digital Input
Digital Input
Digital Input
Analog Input
Analog Input
Analog Input (S3)
Analog Input (S4)
"Remote Power off" or "Comfort/Economy" digital inputs can be
used to interface the controller with a Presence Detector to mi-
nimize costs for heating and cooling.
When digital inputs are in use they have priority on remote sen-
sor and supervisory system.
* Sensors with a sensing element NTC10K Ohm @ 25°C.
Accuracy ± 1K, β @ 25°C = 3435
(reference controlli room sensors S4xxA/B and SNTC-xL)
Digital inputs can be enabled using a configuration tool called
"Configuratore NR9000" thanks to which you can also reverse
the inputs action. It can be downloaded by our web site www.
controlli.eu.
The default status of digital inputs (factory setting) is the fol-
lowing:
DIGITAL INPUT
DEFAULT
WINDOW CONTACT
N.C (normally closed)
REMOTE POWER OFF
N.O (normally open)
WINTER/SUMMER
N.O (normally open)
CHANGEOVER
COMFORT/ECONOMY
N.O (normally open)
For example, in case the window switch is normally opened
(closed window is equivalent to open contact) it is necessary to
reverse the action of the digital input.
Outputs:
4 TRIAC Outputs to drive 3P valves (HOT valve and COOL
valve). Contact Rating 24..250V 4 A;
1
Issue
st
ISO 9001
85-265Vac (isolated)
IP 20
2T 45 °C
-25T 65 °C
DIN M6
Window Contact.
Remote Power off.
Winter/Summer Change Over.
Comfort/Economy.
Return Temperature Sensor.*
Remote Temperature Set.*
Auxiliary loop sensor
Auxiliary loop set selector
DESCRIPTION
OPEN – window opened
CLOSE – window closed
OPEN – Comfort
CLOSE – off (frost protection)
OPEN – winter
CLOSE – summer
OPEN – Comfort
CLOSE – economy
09/13
CONTROLLI S.p.A.
16010 SANT'OLCESE Genova - Italy
Tel.: +39 01073061
E-mail: info@controlli.eu
NR9000/NR9000-RT
NR9000-RT
3 RELAY Outputs to drive 3 speed FAN (V1, V2, V3). Con-
tact Rating 24..250V 8 A;
2 Analog Output 0-10V to drive proportional valves. It is
possible to use 0-10V outputs to drive a modulating FAN
plus modulating valves in sequence (0-5/6-10).
2 Open Collector Outputs: OC1 and OC2. They have a ma-
ximum load of 18mA and can be used to drive 12Vdc relays
whose maximum power is 220mW and winding resistance
>= 640Ohm (ref. Controlli relay module mod. DGSRMV).
OC1 output follows the ON/OFF input and it can be
used, through an external relay, to enable electrical
loads. If the local operation mode is enabled (through
controller password) OC1 follows the input DI2 (over-
ride turn off), so if DI2 is open, OC1 is ON too, instead
if DI2 input is closed, OC1 is OFF too. If the local ope-
ration mode is disabled, OC1 follows the value set at
9011 ModBus address.
OC2 output is used to enable auxiliary functions de-
scribed in the "Controller functions" paragraph. If the
temperture sensor S3 is present, the ON/OFF auxilia-
ry loop which controls OC2 will be automatically ena-
bled; otherwise it is possible to enable the electrical
coil in emergency (through controller password) wich
controls OC2. If the sensor S3 is not present, OC2
follows the value set at 9013 ModBus address.
Bus to connect Remote Terminal NR9000-RT.
Bus Modbus to connect Supervisor System.
Bus Link to connect IO expansion.
Terminals:
Pluggable terminals (J1 & J2) 5 mm pitch for low voltage si-
gnals (230VAC) and 3,5 mm pitch (J3 & J4) for very low voltage
signals.
Look at the table on the next page for details.
Directive and Standards:
Standard CEI EN 60730-1 for EMC directive.
Standard CEI EN 60730-1 and CEI EN 60730-2-9 for LVD di-
rective.
INSTALLATION
NR9000 are suitable for mounting on a DIN rail with a quick
coupling; NR9000-RT is suitable for wall mounting or flush
mounting in A503 electrical Box with B-TICINO (Living & Light)
and VIMAR (Plana & Idea) finishing plates.
Connections shall be in compliance with existing rules and
using max 2,5mm
cross section wires for J1 and J2 terminals
2
and 1,5mm
cross section wires for J3 and J4.
2
To use wire terminals on power supply wires follow the instruc-
tions in order to prevent accidental contacts between cables at
different voltages in case of wrong installation.
1
Fax: +39 0107306870/871
Web: www.controlli.eu
NR9000
DBL408e

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the NR9000 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Controlli NR9000

  • Page 1 Energon - Fan Coil Digital Controller APPLICATION AND USE NR9000 is a digital controller for 2- or 4-pipe terminal units (eg. Fan Coil) with ON/OFF, 3-POINT floating or modulating con- trol valves as well as with 3-speed or modulating fan. NR9000...
  • Page 2: Maintenance

    +12Vcc output 12V (sonda/sensor NR9000-RT) 12V (sonda / sensor NR9000-RT) Bidir BUS TX (sonda/sensor NR9000-RT) BUS TX (sonda / sensor NR9000-RT) Bidir BUS RX (sonda/sensor NR9000-RT) BUS RX (sonda / sensor NR9000-RT) Bidir GND (sonda/sensor NR9000-RT) GND (sonda / sensor NR9000-RT)
  • Page 3: Wiring Diagrams

    WIRING DIAGRAMS Example of 4-pipe plant with 230V 3-point valves Example of 4-pipe plants with 230V ON/OFF valves Issue 09/13 DBL408e ISO 9001...
  • Page 4 Example of 4-pipe plants with 24V 3-point valves Example of 4-pipe plant with 24V ON/OFF valves Issue 09/13 DBL408e ISO 9001...
  • Page 5 Example of 2-pipe plant with 230V 3-point valves Example of 2-pipe plant with 230V ON/OFF valves Issue 09/13 DBL408e ISO 9001...
  • Page 6 Example of 2-pipe plant with 24V 3-point valves Example of 2-pipe plant with 24V ON/OFF valves Issue 09/13 DBL408e ISO 9001...
  • Page 7: Operation

    NR9000-RT Remote Sensor ROOM 1 or using a Supervisory System (MODBUS protocol). Remote Sensor NR9000-RT allows to change the operation mode, the Link-Bus set point and the fan speed; all other parameters can be modi- fied only through the supervisory system or the dedicated con- figuration tool.
  • Page 8 The network must be wired only in accordance with the principle shown here, called “daisy chain” (the device is composed by a sin- gle RS485 port). Star connections are not allowed. Connection warnings For proper network cabling is recommended to take the fol- Do not reverse the polarity “+”...
  • Page 9 Auxiliry regulation ON/OFF (P action) This function can be automatically enable when the sensor in NR9000 works with 3 different operation modes: position S3 is connected. If the remote set in S4 is connected, it is possible to have a set in the range 10-30°C, otherwise it •...
  • Page 10 Control modes NR9000 works with 7 different control modes selectable via dip The 0-10V proportional outputs are always presents and they switch or by supervisory system: follow the ON-OFF (or 3-point) valves characteristics. ON/OFF Valves and 3-speed fan (“FAST” operation mode The diagrams of the valves and fans share the Set point.
  • Page 11 3 point valves and 3 Speed FAN The valves are activated in Pro- portional mode (0-100%) using the set proportional band. Speed 1, 2 and 3 follow to the Proportional Band as shown in the following diagram. ON/OFF valves and 1 Speed FAN The valves are activated in ON- OFF mode with hysteresis.
  • Page 12 ON/OFF Valves and Proportional Speed Fan (0-10V) The valves are activated in ON- OFF mode with hysteresis. Speed fan follow to the Pro- portional Band as shown in the following diagram generating a 0-10V output control signal. 0-5/6-10 V Sequence Valves and Proportional Speed Fan (0-10V) The valves are activated in se- quence mode (0-5/6-10) with hysteresis.
  • Page 13: Modbus Address

    DIP SWITCHES AND LEDs Dip Switches 5-7 settings The controller has 8 dip switches accessible by removing the DIP5 DIP6 DIP7 CONFIGURATION DIAGRAM top cover and two leds to check operation anomalies. ON/OFF Valves and 3 FAN speed (factory OFF OFF OFF setting) ON/OFF Valves and 3 FAN speed “FAST”...
  • Page 14: Default Parameters

    Minimum fan speed 0 (DISABLE) Controller Modbus Address Operation Diagram 2/4 Pipe system 0 (2 PIPE) NR9000-RT (*) “STATUS WORD” 8 (FULL ENABLE) NR9000 (**) “STATUS WORD” Fan Operation Mode (STOP(0),V1(1),V2(2),V3(3),AUTO(4)) 4 (AUTO) Bit0: WINDOW CONTACT (N.C) Bit1:REMOTE POWER OFF Digital Inputs reverse action (4 BIT, N.O(0),N.C.(1))
  • Page 15 Remote (Disable digital input Comfort/ Local (Enable digital input Comfort/Economy and Power Operation Mode Economy and Power Off) Off) Remote (comes from NR9000-RT) Local (comes from “dedicated” analog input S1) Ambient Temperature Remote (Disable digital input Summer/ Summer / Winter...
  • Page 16: Dimensions (Mm)

    Wiring connections NR9000-RT is connected to NR9000 by means 4 wires, 2 for +12V power (pin 4) and GND (pin 1) and 2 for data (pin 2 and 3). For wiring is suggested Belden ®, model 9502 – 2 pairs (one pair for power and one pair for data).