• Electrical work must be performed by a qualifi ed electrician
in accordance with the Installation Manual. Make sure the air
conditioner uses an exclusive power supply.
An insuffi cient power supply capacity or inappropriate installation
may cause fi re.
• Use the specifi ed wires for wiring connect the terminals
securely fi x.
To prevent external forces applied to the terminals from
affecting the terminals.
• Conform to the regulations of the local electric company
when wiring the power supply.
Inappropriate grounding may cause electric shock.
• Do not install the air conditioner in a location subject to a
risk of exposure to a combustible gas.
If a combustible gas leaks, and stays around the unit, a fi re may
occur.
• This appliance is intended to be used by expert or trained
users in shops, in light industry, or for commercial use by
lay persons.
EN-7
New Refrigerant Air Conditioner Installation
• THIS AIR CONDITIONER ADOPTS THE NEW HFC
REFRIGERANT (R410A) WHICH DOES NOT DESTROY
OZONE LAYER.
The characteristics of R410A refrigerant are ; easy to absorb
water, oxidizing membrane or oil, and its pressure is approx.
1.6 times higher than that of refrigerant R22. Accompanied with
the new refrigerant, refrigerating oil has also been changed.
Therefore, during installation work, be sure that water, dust, former
refrigerant, or refrigerating oil does not enter the refrigerating
cycle.
To prevent charging an incorrect refrigerant and refrigerating oil,
the sizes of connecting sections of charging port of the main unit
and installation tools are changed from those for the conventional
refrigerant.
Accordingly the exclusive tools are required for the new refrigerant
(R410A).
For connecting pipes, use new and clean piping designed for
R410A, and please care so that water or dust does not enter.
Moreover, do not use the existing piping because there are
problems with pressure-resistance force and impurity in it.